23
INTAC
®
MENU
DISPLAY
OPTIONS
MFG
DEFAULT
DESCRIPTION
505
RH Process Lo
RANGE: 0.0 to 20.00 mA
4.00
Low range in milliamps for signal on plug J2 terminal 2 and 3
RANGE: 0.00 to 10.00 VDC
0.00
Low range in Volts for signal on plug J2 terminal 1 and 3
506
RH Process Hi
RANGE: 0.00 to 20.00 mA
20.00
High range in milliamps for signal on plug J2 terminal 2 and 3
RANGE: 0.0.0 to 10.0 VDC
10.00
High range in Volts for signal on plug J2 terminal 1 and 3
508
Hi
-
Limit Sensor
None
Option
No High Limit input available (set with menu 707)
Current
Option
Used when a supply air high
-
limit humidity sensor is a mA current
type of signal on plug J4 terminal 6 and 7
Voltage
Option
Used when a supply air high
-
limit humidity sensor is a VDC type
of signal on plug J4 terminal 5 and 7
509
HL Process Lo
RANGE: 0.00 to 20.00 mA
4.00
Low range in mA for humidity signal on plug J4 terminal 6 and 7
RANGE: 0.00 to 10.00 VDC
0.00
Low range in volts for signal on plug J4 terminal 5 and 7
510
HL Process Hi
RANGE: 0.00 to 20.00 mA
20.00
High range in mA for humidity signal on plug J4 terminal 6 and 7
RANGE: 0.00 to 10.00 VDC
10.00
Low range in volts for humidity signal on plug J4 terminal 5 and 7
511
Air Sensor
None
Option
No air temperature sensor input available (set with menu 704)
Current
Option
Current input for outside air temperature sensor
512
Air Process Lo
RANGE: 2.00 to 20.00 mA
4.00
Low range in mA for outside air temp signal on plug J4 terminal 3
and 4
513
Air Process Hi
RANGE: 2.00 to 20.00 mA
20.00
High range in mA for outside air temp signal on plug J4 terminal 3
and 4
514
Air Range Lo
RANGE:
-
100° to +1000°C
0.0
Low range scale for outside air temperature sensor in °C
RANGE:
-
100° TO +1000°F
-
30
Low range scale for outside air temperature sensor in °F
515
Air Range Hi
RANGE:
-
100° to +1000°C
55
High range scale for outside air temperature sensor in °C
RANGE:
-
100° TO +1000°F
130
High range scale for outside air temperature sensor in °F
516
Air Offset
RANGE : 0° to +60°F
0
Offset to calibrate temperature sensor to outside air temp in
degrees Fahrenheit
RANGE: 0° to +33°C
0
Offset to calibrate temperature sensor to outside air temp in
degrees Celsius
517
Process Output
Current
Output signal (mA DC) for device or actuator—INTAC
®
Plug J3 terminal 5 and 6
Voltage
x
Output signal (VDC) for device or actuator—INTAC
®
Plug J3 terminal 4 and 6
518
Out Process Lo
RANGE:0.00 to 8.00 mA
4.00
Process output signal—Low range in Milliamps
RANGE: 0.00 to 3.00 VDC
0.00
Process output signal—Low range in Volts
Содержание INTAC