PLX51-HART-4I / PLX51-HART-4O
♦
HART Input/Output
Operation
Multidrop Field Devices
User Manual
ProSoft Technology, Inc.
Page 82 of 127
4.5 PCCC Operation
The PCCC operation is enabled when the configuration protocol is set to
SLC 500 /
MicroLogix / PLC5
. The module will then operate as a PCCC (AB-ETH) Slave
allowing SLC500, MicroLogix, and PLC5 controllers to read and write data to the
HART devices.
Important
: Only
SLC Typed Read
and
SLC Typed Write
commands are supported by the PLX51-
HART-4x when operating in PCCC mode.
The following PLC Files are supported for the main device.
Table 4.19 – PLC File Map
Parameter
Files
Channel 0
Channel 1 Channel 2 Channel 3
Integers
Device Status
Bit 0 - Loop Open/Current output fault
Bit 1 - Current Underrange/reserved
Bit 2 - Current Overrange/reserved
Bit 3 - Loop Shorted/reserved
Bit 4 - Calibration Busy
Bit 5 - Calibration Failed
Bit 6 - HART Comms Fault
Bit 7 - Relay Message Inhibit
N10:0
N11:0
N12:0
N13:0
HART Status
See the HART section at the end of the document
for information regarding the HART status.
N10:1
N11:1
N12:1
N13:1
Live List
When using Multidrop functionality this will
indicate which of the devices that have been
configured are online. Note that each bit
represents the configured Multidrop Device
Index (see the Multidrop configuration in the
Advanced Mapping section).
For example, if bit 3 is set, then Multidrop
device at MD 3 is online (for the specific
channel).
N10:2
N11:2
N12:2
N13:2
Manufacturer ID
N10:3
N11:3
N12:3
N13:3
Device ID
N10:4
N11:4
N12:4
N13:4
PV Unit
N10:5
N11:5
N12:5
N13:5
SV Unit
N10:6
N11:6
N12:6
N13:6
TV Unit
N10:7
N11:7
N12:7
N13:7
FV Unit
N10:8
N11:8
N12:8
N13:8