PLX51-HART-4I / PLX51-HART-4O 

 HART Input/Output 

Setup 

Multidrop Field Devices  

User Manual 

ProSoft Technology, Inc. 

Page 41 of 127 

3.8  Module Download  

Once the module configuration has been completed, it must be downloaded to the 

module. 
Before downloading the Connection Path of the module should be set. This path will 

automatically default to the IP address of the module, as set in the module 

configuration. It can however be modified, if the module is not on a local network. 
The Connection path can be set by right-clicking on the module and selecting the 

Connection Path option. 

 

Figure 3.29 - Selecting Connection Path 

The new connection path can then be either entered manually or selected by means 

of the Target Browser. 

 

Figure 3.30 - Connection Path 

 

 

Содержание PLX51-HART-4I

Страница 1: ...PLX51 HART 4I PLX51 HART 4O HART Input Output Multidrop Field Devices July 6 2022 USER MANUAL...

Страница 2: ...y contain technical inaccuracies or typographical errors ProSoft Technology makes no warranty or representation as to its accuracy and assumes no liability for and reserves the right to correct such i...

Страница 3: ...ort 18 3 Setup 19 3 1 Install Configuration Software 19 3 2 Network Parameters 19 3 3 Creating a New Project 24 3 4 Module Parameters 26 3 5 Advanced Mapping 30 3 5 1 Diagnostics 31 3 5 2 Multidrop 33...

Страница 4: ...tistics 99 5 2 4 Security Statistics 101 5 2 5 Modbus 102 5 2 6 PCCC 103 5 3 Channel Status 105 5 4 Device List 113 5 5 MultiDrop 114 5 6 Calibration 114 5 6 1 PLX51 HART 4I Calibration 115 5 6 2 PLX5...

Страница 5: ...P Modbus TCP IP DNP3 TCP UDP or PCCC AB ETH protocols This includes 4 to 20 mA input and output devices with or without HART communications as well as 0 to 20 mA devices without HART The PLX51 HART 4x...

Страница 6: ...extraction and updating of multidrop HART devices which can be accessed via Modbus TCP IP FTView using CIP parameter objects or PCCC When using an EtherNet IP source the user can select either the new...

Страница 7: ...n example of the typical architecture for a PLX51 HART 4I interfacing to an EtherNet IP device e g Allen Bradley Logix Controller Figure 1 2 PLX51 HART 4I EtherNet IP typical architecture The figure b...

Страница 8: ...ure below provides an example of the typical architecture for a PLX51 HART 4I interfacing to a DNP3 Master SCADA Figure 1 4 PLX51 HART 4I DNP3 typical architecture The figure below provides an example...

Страница 9: ...of 127 The figure below provides an example of the typical architecture for a PLX51 HART 4I with multidrop HART devices Figure 1 6 PLX51 HART 4I multidrop architecture 1 4 Additional Information The...

Страница 10: ...n guide cde205_220_420_hig Connectors html 1 5 References Table 1 2 References Resource Link HART Communication Foundation http en hartcomm org DNP3 http www dnp org CIP Routing The CIP Networks Libra...

Страница 11: ...r The power port uses a three way connector for the DC power supply and the earth connection The Ethernet cable must be wired according to industry standards See the additional information section of...

Страница 12: ...DIP Switch 3 This DIP Switch is used to lock the configuration from being overwritten by the PLX50 Configuration Utility When set the PLX50 Configuration Utility will not be able to download to the m...

Страница 13: ...d earth The module requires an input voltage of 10 28Vdc Refer to the technical specifications section in this document Figure 2 5 Power connector 2 4 Analog HART Single Device The Analog HART channel...

Страница 14: ...urrent directly and therefore can also be connected directly to the field device signal terminals The input and output channels provide internal current limiting and electronic fuse protection Figure...

Страница 15: ...ology Inc Page 15 of 127 The PLX51 HART 4I module supports 2 wire loop powered and 4 wire devices in various configurations as illustrated below Figure 2 10 Channel Connection 2 wire Module Powered Fi...

Страница 16: ...mA The above table should be considered as a maximum count lower counts may be applicable for some field devices 2 5 1 Series Configuration The series connection method has the advantage of the 4 20 m...

Страница 17: ...devices in parallel is more common although it has the disadvantage that the 4 20 mA cannot be controlled by any device Here all of the field devices remain at 4 mA and all share a common supply volta...

Страница 18: ...igurations Figure 2 17 PLX51 HART 4I Multidrop Wiring Parallel Module Powered Figure 2 18 PLX51 HART 4I Multidrop Wiring Parallel Externally Powered Figure 2 19 PLX51 HART 4O Multidrop Wiring Parallel...

Страница 19: ...3 2 Network Parameters The module will have DHCP Dynamic Host Configuration Protocol enabled as factory default Thus a DHCP server must be used to provide the module with the required network paramet...

Страница 20: ...DHCP server will listen on all available network adapters for DHCP requests and display their corresponding MAC addresses Figure 3 3 DHCP Server NOTE If the DHCP requests are not displayed in the DHC...

Страница 21: ...ssign the IP address to the module and then read the Identity object Product name from the device The successful assignment of the IP address by the device is indicated by the green background of the...

Страница 22: ...using the Ethernet Port Configuration via the Target Browser The Target Browser can be accessed under the Tools menu Figure 3 6 Selecting the Target Browser The Target Browser automatically scans the...

Страница 23: ...ser Manual ProSoft Technology Inc Page 23 of 127 All the relevant Ethernet port configuration parameters can be modified using the Port Configuration window Figure 3 9 Port Configuration Alternatively...

Страница 24: ...module a new PLX50 Configuration Utility project must be created Under the File menu select New Figure 3 10 Creating a new project A PLX50 Configuration Utility project will be created showing the Pr...

Страница 25: ...entical Figure 3 12 Selecting a new module The device will appear in the Project Explorer tree as shown below and its configuration window opened The device configuration window can be reopened by eit...

Страница 26: ...rs When downloading this configuration into the module it will be saved in non volatile memory that persists when the module is powered down Important When a firmware upgrade is performed the module w...

Страница 27: ...ell Automation Logix family of controllers Modbus TCP IP When selected the device will respond as a Modbus TCP IP server DNP3 TCP When selected the device will respond as a DNP3 Outstation using a TCP...

Страница 28: ...lower milliamp value to be used for the scaling to engineering units EU Max The upper engineering value to be used for the scaling to engineering units The scaled engineering value will equal this val...

Страница 29: ...r can fix the address which the HART module will use to communicate with the attached field device When this is not enable the HART module will search for the device from node address 0 to 63 Note Thi...

Страница 30: ...lliseconds since the last packet has been received from the source before the communication is deemed to have been lost 3 5 Advanced Mapping The module supports multidrop functionality on each channel...

Страница 31: ...tidrop section for more details Applicable only for Multi Drop Action Address This is the short node address of the HART device on the multidrop channel The addresses can be found by using the Scan fu...

Страница 32: ...ength This is the length of the data that must be sent with the command Result Offset The byte offset in the response where the required parameter starts Data Type The Logix tag data type required to...

Страница 33: ...bus TCP IP or PCCC interface protocol only Multidrop action is supported see below The data from each multidrop HART device will be placed at specific Modbus Registers or SLC File numbers based on the...

Страница 34: ...ed as one of the multidrop devices EtherNet IP The required HART command will need to be entered into the builder window as shown below Figure 3 20 Custom HART Command Builder Mapping for EtherNet IP...

Страница 35: ...odbus Parameter Description Trigger Offset The Trigger Offset parameter is the Modbus HR offset in the Modbus HR range for the specific HART channel for the trigger of the HART custom message For exam...

Страница 36: ...is the length of the HART data to be sent in bytes NOTE A value of zero will result in no additional HART data being sent with the HART command Reply Offset The reply offset parameter is the location...

Страница 37: ...e and called the session keys and these keys may be updated frequently To exchange the session keys between two DNP3 devices the update key refer to the Secure Authentication section for further detai...

Страница 38: ...PLX51 HART 4I PLX51 HART 4O HART Input Output Setup Multidrop Field Devices User Manual ProSoft Technology Inc Page 38 of 127 Figure 3 23 DNP3 security configuration...

Страница 39: ...eter must be used see below This will ensure that the specified address is used as the main Should this not be specified then the PLX51 HART 4x will scan the specific HART channel and use the first HA...

Страница 40: ...elow Figure 3 26 Set Field Device Node Address Figure 3 27 Set Field Device Node Address The user will also need to ensure that each field device on the drop has its loop current mode set to Multidrop...

Страница 41: ...f the module should be set This path will automatically default to the IP address of the module as set in the module configuration It can however be modified if the module is not on a local network Th...

Страница 42: ...the Download option Figure 3 31 Selecting Download Once complete the user will be notified that the download was successful Figure 3 32 Successful download Within the PLX50 Configuration Utility envi...

Страница 43: ...t clicking on the Ethernet Bridge in the RSLogix 5000 and selecting New Module after which the ETHERNET MODULE is selected to be added as shown in the figure below Note See the next section for import...

Страница 44: ...bly Instance Size Input 113 119 32 bit Output 116 1 32 bit Configuration 102 0 8 bit Figure 3 35 RSLogix 5000 General module properties for PLX51 HART 4I module The required connection parameters for...

Страница 45: ...es are exchanged The recommended value is 200 ms Refer to the technical specification section in this document for further details on the limits of the RPI Figure 3 37 Connection module properties in...

Страница 46: ...file can be imported by right clicking on an empty rung in the MainRoutine and selecting the Import Rungs option Figure 3 39 RSLogix 5000 Importing module specific routine and UDTs Figure 3 40 Selecti...

Страница 47: ...to change the routine to map to the correct module instance name and make sure that the mapping routine is called by the Program s Main Routine Figure 3 41 Imported RSLogix 5000 objects Refer to the...

Страница 48: ...e general module configuration in the PLX50 Configuration Utility Temperature REAL The internal temperature of the module in C Module Status DINT Bit 0 Configuration Valid Bit 1 Channel 0 Enabled Bit...

Страница 49: ...error detected by field device Chx_HARTStatus OverrunError BOOL Field device buffer overrun Chx_HARTStatus FramingError BOOL HART Framing error detected by field device Chx_HARTStatus ChecksumError B...

Страница 50: ...d and filtered PV in engineering units Chx_DigitialCurrent REAL The field device s target current Chx_PV REAL Primary Variable in engineering units Chx_SV REAL Secondary Variable in engineering units...

Страница 51: ...L Analog output value in engineering units for Channel 1 Ch2_Data REAL Analog output value in engineering units for Channel 2 Ch3_Data REAL Analog output value in engineering units for Channel 3 4 1 3...

Страница 52: ...RT Message Request Structure HART Command Request Byte Offset Data Type Description 0 INT Request Length 2 SINT Start Character 0x82 for Long Address 3 SINT Long Address 0 0x80 Manufacturer ID 4 SINT...

Страница 53: ...t Output Operation Multidrop Field Devices User Manual ProSoft Technology Inc Page 53 of 127 HART Command Status Encoding The Status code returned in the HART relay command are as follows Examine the...

Страница 54: ...ted Second Byte Device Status Bit Description 0 PV out of limits 1 Variable non PV out of limits 2 Analog output saturated 3 Output current fixed 4 Undefined 5 Cold Start 6 Configuration Changed Table...

Страница 55: ...PLX51 HART 4O HART Input Output Operation Multidrop Field Devices User Manual ProSoft Technology Inc Page 55 of 127 Figure 4 3 Relay HART Message Example Configuration Figure 4 4 Relay HART Command Ex...

Страница 56: ...Technology Inc Page 56 of 127 Figure 4 5 Relay HART Command Example Response Note The HART Long Address for a device is comprised of the Manufacturer ID Device Type Code and Device ID These values are...

Страница 57: ...ag structure or the legacy MVI56Legacy tag structure The user will need to use either of the provided MultiDrop UDTs for each tag used for each HART multidrop device as shown below Figure 4 6 Multidro...

Страница 58: ...t byte of the field device HART response status See the HART section at the end of this document for details regarding the HART status LastSecond_StatusByte SINT The second byte of the field device HA...

Страница 59: ...s code FVUnits SINT Fourth Variable engineering units code Tagname STRING8 Tag name of the field device Descriptor STRING16 Descriptor of the field device TagDescriptorDate STRING8 Date of the field d...

Страница 60: ...of this document for details regarding the HART status Last_Second_Status_Byte SINT The second byte of the field device HART response status See the HART section at the end of this document for detail...

Страница 61: ...larm Selection Code PV_Transfer SINT PV Transfer Function Code PV_URLLRV_Units SINT PV Upper and Lower Range Values Units Code Write_Protection_Code SINT Write Protection Code Private_Label_Code SINT...

Страница 62: ...age Type CIP Generic Service Type Set Single Attribute Service Code 10 Hex Set Single Attribute Class 40F Hex Instance Channel value 1 1 for Channel 0 2 for Channel 1 3 for Channel 2 4 for Channel 3 A...

Страница 63: ...riable CIP Parameters Parameter Value Description Message Type CIP Generic Service Type Get Single Attribute Service Code 0E Hex Get Single Attribute Class 40F Hex Instance Channel value 1 1 for Chann...

Страница 64: ...erface a Logix tag will need to be selected with the correct Logix UDT type ProsoftHART4CustomCommand See the PLX51 HART Logix example code for the UDT Figure 4 9 Custom HART command selected Logix Ta...

Страница 65: ...n the UDT to indicate the status of the transaction 0 Success 1 Response Timeout 2 HART device offline 3 No Multidrop Device configured ReqDataLen This parameter indicate the number of bytes to be sen...

Страница 66: ...Messages 1 4 Error Messages Sent 1 5 Error Messages Received 1 6 Checksum Error 1 7 HART Tx Count 1 20 30 40 50 HART Rx Count 1 21 31 41 51 Communication Errors 1 22 32 42 52 Command Errors 1 23 33 4...

Страница 67: ...Manufacturer ID 1 100 200 300 400 Manufacturer Device Type Code 1 101 201 301 401 Number of Preambles Required 1 102 202 302 402 Universal Command Rev 1 103 203 303 403 Specific Command Rev 1 104 204...

Страница 68: ...ration Utility the user can write the Update Key into the module using the Key tab in the Online Status window The key entered must match the Key Wrap Algorithm selected Thus if AES 128 Key Wrap was s...

Страница 69: ...4 Channel 3 Enabled Bit 5 Channel 0 HART Enabled Bit 6 Channel 1 HART Enabled Bit 7 Channel 2 HART Enabled Bit 8 Channel 3 HART Enabled 2 INT 0 Channel 0 Live List When using Multidrop functionality...

Страница 70: ...onfiguration in the Advanced Mapping section Example If bit 3 is set then Multidrop device at MD 3 is online for the specific channel 2 INT 8 Modbus Statistics Rx Packet Count 4 DINT 20 Tx Packet Coun...

Страница 71: ...50 HART channel command Note These are Write Only Registers HART communication inhibit When set to 1 the HART communication on the specific channel will be inhibited 2 INT 820 870 920 970 Register Typ...

Страница 72: ...HARTCommsFault HART communication failure Bit 7 RelayMessagesInhibited Relay HART messages inhibited set in configuration This prevents DTM and other class 2 communications 1 BYTE 400 500 600 700 Res...

Страница 73: ...at the device is online 2 INT 1000 2000 3000 4000 Manufacturer ID 1 BYTE 1001 2001 3001 4001 Mfg Device Type Code 1 BYTE Number of Preambles Required 1 BYTE 1002 2002 3002 4002 Universal Command Rev 1...

Страница 74: ...1107 2107 3107 4107 Max Number of Device Vars 1 BYTE Config Change Count 2 INT 1108 2108 3108 4108 Extended Device Status 1 BYTE 1109 2109 3109 4109 Pad Byte 1 BYTE Sensor Serial Number 3 BYTE 3 1110...

Страница 75: ...When set this bit will indicate that the device is online 2 INT 1300 2300 3300 4300 Manufacturer ID 1 BYTE 1301 2301 3301 4301 Mfg Device Type Code 1 BYTE Number of Preambles Required 1 BYTE 1302 2302...

Страница 76: ...ount 2 INT 1408 2408 3408 4408 Extended Device Status 1 BYTE 1409 2409 3409 4409 Pad Byte 1 BYTE Sensor Serial Number 3 BYTE 3 1410 2410 3410 4410 Units Code for Sensor 1 BYTE Sensor Upper Limit 4 REA...

Страница 77: ...e 2 INT 1600 2600 3600 4600 Manufacturer ID 1 BYTE 1601 2601 3601 4601 Mfg Device Type Code 1 BYTE Number of Preambles Required 1 BYTE 1602 2602 3602 4602 Universal Command Rev 1 BYTE Device Specific...

Страница 78: ...code 1 SINT TV units code 1 SINT 1109 2109 3109 4109 FV units code 1 SINT Multidrop Device Index MD 2 PV 4 REAL 1200 2200 3200 4200 SV 4 REAL 1202 2202 3202 4202 TV 4 REAL 1204 2204 3204 4204 FV 4 RE...

Страница 79: ...L 1504 2504 3504 4504 FV 4 REAL 1506 2506 3506 4506 PV units code 1 SINT 1508 2508 3508 4508 SV units code 1 SINT TV units code 1 SINT 1509 2509 3509 4509 FV units code 1 SINT Multidrop Device Index M...

Страница 80: ...5500 HR 5749 3 HR 5750 HR 5999 Each Custom HART command requires four mapping parameters in addition to the HART command Table 4 17 Custom HART command build parameters Modbus Parameter Description Tr...

Страница 81: ...nnel 1 offset HR 40 See the Custom HART message operation section for details regarding the format of the reply data The reply data format written to the Reply Offset Modbus Holding Register location...

Страница 82: ...1 Current Underrange reserved Bit 2 Current Overrange reserved Bit 3 Loop Shorted reserved Bit 4 Calibration Busy Bit 5 Calibration Failed Bit 6 HART Comms Fault Bit 7 Relay Message Inhibit N10 0 N11...

Страница 83: ...will need to write to the Scaled Value to update the analog signal being sent to the output HART device 4 5 1 Multidrop When multidrop is being used for HART devices the data from each device will au...

Страница 84: ...turer ID N10 25 N11 25 N12 25 N13 25 Device ID N10 26 N11 26 N12 26 N13 26 PV Unit N10 27 N11 27 N12 27 N13 27 SV Unit N10 28 N11 28 N12 28 N13 28 TV Unit N10 29 N11 29 N12 29 N13 29 FV Unit N10 30 N1...

Страница 85: ...53 Device ID N10 54 N11 54 N12 54 N13 54 PV Unit N10 55 N11 55 N12 55 N13 55 SV Unit N10 56 N11 56 N12 56 N13 56 TV Unit N10 57 N11 57 N12 57 N13 57 FV Unit N10 58 N11 58 N12 58 N13 58 Floats Multidr...

Страница 86: ...27 TV Value F20 28 F21 28 F22 28 F23 28 FV Value F20 29 F21 29 F22 29 F23 29 Multidrop Device Index MD 5 PV Value F20 30 F21 30 F22 30 F23 30 SV Value F20 31 F21 31 F22 31 F23 31 TV Value F20 32 F21 3...

Страница 87: ...egister EDS File Before FTView can access the HART data from the module the module s EDS file must be registered on that system There are multiple ways to achieve this One of which is to right click o...

Страница 88: ...RSLinx Enterprise server has been added To add the RSLinx Enterprise communication server right click on the project server in the project tree and select the Add New Server option and then the Rockwe...

Страница 89: ...pen Communication Setup The Communication Setup window allows the user to associate a Device Shortcut to the physical module This can be achieved by the following steps 1 Under Device Shortcuts select...

Страница 90: ...ion to continue and accept the changes Figure 4 21 Confirm RSLinx Enterprise shortcut 4 6 3 Displaying Process Variables A Numeric Display can now be added to a FTView display to show a HART module pa...

Страница 91: ...hanges have been to the communication setup Right click on the Folders tree on the left and select the Refresh All Folders option Figure 4 23 Tag Browser Refreshing All Folders Once refreshed all the...

Страница 92: ...as in this example it may be beneficial to set the format to Floating Point and select a suitable number of Decimal Places Figure 4 25 Configure Numeric Display The Numeric Display can be tested by u...

Страница 93: ...p Field Devices User Manual ProSoft Technology Inc Page 93 of 127 5 Diagnostics 5 1 LEDs The module provides six LEDs for diagnostics purposes as shown in the front view figure below A description of...

Страница 94: ...established to the field device Otherwise the LED will be red The LED will flash green each time a HART response was received from the connected field device If there was a HART communication error e...

Страница 95: ...5 3 Selecting online Status The Status monitoring window can be opened by either double clicking on the Status item in the Project Explorer tree or by right clicking on the module and selecting Status...

Страница 96: ...e module s unique Ethernet MAC address Temperature The internal temperature of the module Processor Scan The amount of time microseconds taken by the module s processor in the last scan Ethernet Cable...

Страница 97: ...atistics Statistic Description Current Class 3 Connections The number of current open class 3 connections Connection Failures The number of failed attempts at establishing a class 3 connection with a...

Страница 98: ...ual ProSoft Technology Inc Page 98 of 127 ENIP Failures This count increases when the ENIP Retry Limit is reached and no response has been received from the Logix Controller Tag Access General Errors...

Страница 99: ...the module Error Messages Tx The number of error DNP3 packets sent by the module Error Messages Rx The number of error DNP3 packets received by the module Checksum errors The number of corrupted DNP3...

Страница 100: ...e found in a single request DNP3 Message Queue Full The Hart 4 module has received too many simultaneous messages to process Node Mismatch The received message node number did not match the Hart 4 mod...

Страница 101: ...nged Authentication Failures The other device has provided invalid authentication information such as an incorrect MAC Authorization Failures Increases when a user is not authorized to perform a reque...

Страница 102: ...Input Output Diagnostics Multidrop Field Devices User Manual ProSoft Technology Inc Page 102 of 127 5 2 5 Modbus The Modbus Statistics will be displayed if the Modbus TCP IP protocol has been configu...

Страница 103: ...Data Alignment Errors The Modbus request and associated mapped item is not byte aligned with the destination Illegal Function The number of times the Modbus device responded with an Illegal Function e...

Страница 104: ...PLX51 HART 4I PLX51 HART 4O HART Input Output Diagnostics Multidrop Field Devices User Manual ProSoft Technology Inc Page 104 of 127 Figure 5 10 PCCC Statistics...

Страница 105: ...Client Not Found The number of requests rejected due to no matching connection Client Max Reached The number of connection request rejections due to maximum connection count reached File Not Found Th...

Страница 106: ...ice 16 characters Manufacturer The field device manufacturer Device Type The device type code assigned by the manufacturer PV and Units The primary variable displayed in engineering units with the eng...

Страница 107: ...Limit The upper limit of the sensor in the aforementioned engineering units Sensor Lower Limit The lower limit of the sensor in the aforementioned engineering units Preambles Required The minimum numb...

Страница 108: ...gged if the field device received a message with a parity error Overrun Error Flagged if the field device receive buffer is overrun Framing Error Flagged if the field device receives a message with an...

Страница 109: ...represented by the 20 mA analog signal Note The LRV URV and Range Units are updated together Range Units The engineering units in which the LRV and URV values are specified Note The LRV URV and Range...

Страница 110: ...e Parameters The Advanced Status tab displays the advanced and device specific status information of the field device Due to the manufacturer specific encoding of these parameters consult the field de...

Страница 111: ...perienced Relay Message Tx Count The number of HART packets sent via relay Class 2 messages DTMs etc Relay Message Rx Count The number of HART packets received for relay Class 2 messages DTMs etc Adva...

Страница 112: ...4 20 mA Filtered Scaled Value Digital Current Primary Variable PV Secondary Variable SV Third Variable TV Fourth Variable FV Figure 5 20 Channel Status Trend Once the source or sample rate has been mo...

Страница 113: ...n the user is using multiple devices on a single channel then more than one device will be displayed in this list Important When multiple devices are used on a single channel then the user must ensure...

Страница 114: ...rocess variables for each multidrop HART device Figure 5 23 Channel Status MultiDrop 5 6 Calibration The Calibration tab in the Channel status monitoring form can be used to display and modify the cal...

Страница 115: ...0 mA 5 Enter the exact milliamp value read from an external meter into the High Value Actual numeric inputs 6 Press the High Value 20 mA Capture button to capture the current un calibrated value into...

Страница 116: ...ox 6 The new Span and Offset calibration settings will be automatically calculated See figure below 7 Press Accept to write these new calibration figures to the module 8 The Calibration Type will then...

Страница 117: ...PLX50 Configuration Utility select the Event Viewer option in the Project Explorer tree Figure 5 27 Selecting the module Event Log The Event Log window will open and automatically read all the events...

Страница 118: ...s a web server allowing a user without the PLX50 Configuration Utility or RSLogix 5000 to view various diagnostics of the module This includes Ethernet parameters system event log advanced diagnostics...

Страница 119: ...sist you and the support team to diagnose any possible issues To invoke the capture of the module right click on the module when online in PLX50CU and select the HART Packet Capture item Figure 5 30 S...

Страница 120: ...nstructs and valid checksums Ch The HART channel where the packet was captured Dirn The direction of the packet either transmitted Tx or received Rx Addr The HART slave device short address Cmd The HA...

Страница 121: ...DT DTM Technology The module supports FDT DTM technology allowing the user to configure any field device using its DTM Device Type Manager in any standard FDT Frame Field Device Tool To use a field de...

Страница 122: ...ignal using Frequency Shift Keying FSK As the name implies FSK changes the frequency of the carrier to represent the binary data 0 or 1 A frequency of 1200 Hz represents a logical 1 and a frequency of...

Страница 123: ...itter specific error 7 In write protect mode 8 15 Command specific error 16 Access restricted 32 Device is busy 64 Command not implemented Second Byte Device Status Bit Description 0 PV out of limits...

Страница 124: ...Multidrop Field Devices User Manual ProSoft Technology Inc Page 124 of 127 8 Technical Specifications 8 1 Dimensions Below are the enclosure dimensions as well as the required DIN rail dimensions All...

Страница 125: ...ay terminal Conductors 24 18 AWG Enclosure rating IP20 NEMA UL Open Type Temperature 20 70 C Earth connection Yes terminal based Emissions IEC61000 6 4 ESD Immunity EN 61000 4 2 Radiated RF Immunity I...

Страница 126: ...of 127 8 5 Analog Output Channel PLX51 HART 4O Table 8 4 Analog Output channel specification Specification Rating Number of channels 4 DAC resolution 16 bit Drive 50 1170 Resistive 50 mH Inductive Acc...

Страница 127: ...Corporate Location Europe Middle East Africa Regional Office Phone 1 661 716 5100 info prosoft technology com Languages spoken English Spanish REGIONAL TECH SUPPORT support prosoft technology com Pho...

Отзывы: