ProSoft Technology inRAx MVI56-CAS Скачать руководство пользователя страница 44

MVI56-CAS 

 ControlLogix Platform 

Diagnostics and Troubleshooting 

Teledyne CA Slave Module  

 

Page 44 of 86  

ProSoft Technology, Inc. 

December 26, 2007 

 

 

4.2 

LED Status Indicators 

The LEDs indicate the module's operating status as follows: 

ProSoft 
Module 

Color Status 

Indication 

On 

Data is being transferred between the module and a remote 
terminal using the Configuration/Debug port. 

CFG Green 

Off 

No data is being transferred on the Configuration/Debug 
port. 

On 

Data is being transferred between the module and the TCA 
network on its TCA Port 1. 

P1 Green 

Off 

No data is being transferred on the port. 

On 

Data is being transferred between the module and the TCA 
network on its TCA Port 2. 

P2 Green 

Off 

No data is being transferred on the port. 

On 

The MVI56-CAS is working normally. 

APP Amber 

Off 

The MVI56-CAS module program has recognized a 
communication error on one of its TCA ports. 

On 

The LED is on when the module is performing a write 
operation on the backplane. 

BP ACT 

Amber 

Off 

The LED is off when the module is performing a read 
operation on the backplane. Under normal operation, the 
LED should blink rapidly on and off. 

Off 

The card is not receiving any power and is not securely 
plugged into the rack. 

Green 

The module is operating normally. 

OK Red/ 

Green 

Red 

The program has detected an error or is being configured. If 
the LED remains red for over 10 seconds, the program has 
probably halted. Remove the card from the rack and re-
insert the card to restart the module's program. 

Off 

The battery voltage is OK and functioning. 

BAT Red 

On 

The battery voltage is low or battery is not present. Allow 
battery to charge by keeping module plugged into rack for 24 
hours. If BAT LED still does not go off, contact ProSoft 
Technology, as this is not a user serviceable item. 

During module configuration, the OK LED will be red and the APP and BP ACT 
LEDs will be on. If the LEDs are latched in this mode for a long period of time, 
look at the configuration error words in the configuration request block. The 
structure of the block is as shown below. 

Offset Description 

Length 

0 Reserved 

1 9000 

Module Configuration Errors 

Port 1 Configuration Errors 

Port 2 Configuration Errors 

5 to 248 

Spare 

244 

249 

-2 or -3 

If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this 
indicates a serious problem with the module. Call Prosoft Technology support to 
arrange for repairs.  

Содержание inRAx MVI56-CAS

Страница 1: ...MVI56 CAS ControlLogix Platform Teledyne CA Slave Module User Manual December 26 2007 ...

Страница 2: ...hange without notice and does not represent a commitment on the part of ProSoft Technology Improvements and or changes in this manual or the product may be made at any time These changes will be made periodically to correct technical inaccuracies or typographical errors Warnings UL Warnings A Warning Explosion Hazard Substitution of components may impair suitability for Class I Division 2 B Warnin...

Страница 3: ... T4 DEMKO 07ATEX0710717X Your Feedback Please We always want you to feel that you made the right decision to use our products If you have suggestions comments compliments or complaints about the product documentation or support please write or call us ProSoft Technology 1675 Chester Avenue Fourth Floor Bakersfield CA 93301 1 661 716 5100 1 661 716 5101 Fax http www prosoft technology com Copyright...

Страница 4: ......

Страница 5: ... 3 LADDER LOGIC 29 4 DIAGNOSTICS AND TROUBLESHOOTING 31 4 1 Reading Status Data From the Module 31 4 1 1 The Configuration Debug Menu 31 4 1 2 Required Hardware 32 4 1 3 Required Software 33 4 1 4 Using the Configuration Debug Port 33 4 1 5 Main Menu 34 4 1 6 Data Analyzer 37 4 1 7 Data Analyzer Tips 39 4 1 8 Database View Menu 42 4 2 LED Status Indicators 44 4 2 1 Clearing a Fault Condition 45 4 ...

Страница 6: ... Us Sales and Support 76 6 2 Return Material Authorization RMA Policies and Conditions 77 6 2 1 All Product Returns 77 6 3 Procedures for Return of Units Under Warranty 77 6 4 Procedures for Return of Units Out of Warranty 78 6 4 1 Un repairable Units 78 6 4 2 Purchasing Warranty Extension 79 6 5 LIMITED WARRANTY 79 6 5 1 What Is Covered By This Warranty 79 6 5 2 What Is Not Covered By This Warran...

Страница 7: ...and Troubleshooting Verifying Communication page 31 Diagnostics and Troubleshooting page 31 This section describes how to verify communications with the network Diagnostic and Troubleshooting procedures Reference Product Specifications Functional Overview Glossary Reference page 47 Functional Overview page 49 Product Specifications page 47 These sections contain general references associated with ...

Страница 8: ...MVI56 CAS ControlLogix Platform Start Here Teledyne CA Slave Module Page 8 of 86 ProSoft Technology Inc December 26 2007 ...

Страница 9: ...nnel or equipment to unsafe or inappropriate working conditions Safety quality and experience are key factors in a successful installation 1 1 System Requirements The MVI56 CAS module requires the following minimum hardware and software components Rockwell Automation ControlLogix processor with compatible power supply and one free slot in the rack for the MVI56 CAS module The module requires 800mA...

Страница 10: ...nts are included with your MVI56 CAS module and are all required for installation and configuration Important Before beginning the installation please verify that all of the following items are present Qty Part Name Part Number Part Description 1 MVI56 CAS Module MVI56 CAS Teledyne CA Slave Module 1 Cable RS232 Null Modem For RS232 Connection to the CFG Port 3 Cable Cable 14 RJ45 to DB9 Male Adapt...

Страница 11: ...ion shows the MVI56 CAS jumper configuration 1 Set the PRT 2 for application port 1 and PRT 3 for application port 2 jumpers for RS232 RS422 or RS485 to match the wiring needed for your application The default jumper setting for both application ports is RS 232 2 The Setup Jumper acts as write protection for the module s flash memory In write protected mode the Setup pins are not connected and the...

Страница 12: ... to verify that suitable safety procedures are in place before installing or servicing the device After you have checked the placement of the jumpers insert MVI56 CAS into the ControlLogix chassis Use the same technique recommended by Rockwell Automation to remove and install ControlLogix modules Warning When you insert or remove the module while backplane power is on an electrical arc can occur T...

Страница 13: ... the sample program to work correctly Slot numbers are identified on the green circuit board backplane of the ControlLogix rack 6 Turn power ON Note If you insert the module improperly the system may stop working or may behave unpredictably Note If you are installing MVI56 CAS with other modules connected to the PCI bus the peripheral modules will not have holding clips Make sure all of the module...

Страница 14: ...lLogix processor Note The key switch on the front of the ControlLogix module must be in the REM position 1 If you are not already online to the processor open the Communications menu and then choose Download RSLogix will establish communication with the processor 2 When communication is established RSLogix will open a confirmation dialog box Click the Download button to transfer the sample program...

Страница 15: ...o switch the processor from Program mode to Run mode Note If you receive an error message during these steps refer to your RSLogix documentation to interpret and correct the error 1 6 1 Configuring RSLinx If RSLogix is unable to establish communication with the processor follow these steps 1 Open RSLinx 2 Open the Communications menu and choose Configure Drivers This action opens the Configure Dri...

Страница 16: ...onfigure This action opens the Configure Allen Bradley DF1 Communications Device dialog box 4 Click the Auto Configure button RSLinx will attempt to configure your serial port to work with the selected driver 5 When you see the message Auto Configuration Successful click the OK button to dismiss the dialog box Note If the auto configuration procedure fails verify that the cables are connected corr...

Страница 17: ...ur PC to the Module With the module securely mounted connect your PC to the Configuration Debug port using an RJ45 DB 9 Serial Adapter Cable and a Null Modem Cable 1 Attach both cables as shown 2 Insert the RJ45 cable connector into the Configuration Debug port of the module 3 Attach the other end to the serial port on your PC or laptop ...

Страница 18: ...MVI56 CAS ControlLogix Platform Start Here Teledyne CA Slave Module Page 18 of 86 ProSoft Technology Inc December 26 2007 ...

Страница 19: ... in offline mode to add the module to a project 2 Modify the example ladder logic to meet the needs of your application and copy the ladder logic to the processor Example ladder logic files are provided on the CD ROM Note If you are installing this module in an existing application you can copy the necessary elements from the example ladder logic into your application The rest of this chapter desc...

Страница 20: ...nfiguring the Module Teledyne CA Slave Module Page 20 of 86 ProSoft Technology Inc December 26 2007 This action opens the following dialog box Select the 1756 Module Generic 1756 Module from the list and click OK The following dialog box is displayed ...

Страница 21: ...the ControlLogix rack Click Next to display the next dialog box Select the Request Packet Interval value for scanning the I O on the module This value represents the minimum frequency the module will handle scheduled events This value should not be set to less than 1 millisecond Values between 1 and 10 milliseconds should work with most applications After completing the module setup the Controller...

Страница 22: ...play the User Defined Data Types shown below The next step in module setup is to define the data to be used to interface with the module and the ladder logic Open the Controller Tags Edit Tags dialog box and enter the values shown in the following example The MVI56 CAS module is defined in the example as CAS1 You can set the tag name to any valid tag name you desire If you are using the example la...

Страница 23: ...g Configuration port on the module and look at the status of the module using the Configuration Debug Menu in the module 2 1 Module Configuration In order for the MVI56 CAS module to function a minimum amount of configuration data must be transferred to the module The following table provides an overview of the different types of configuration data that the module will require depending on the ope...

Страница 24: ... written to issue a Write Configuration command block 9997 to the module A remote device can set a value of 9997 at address 6800 in the module to download the configuration to the processor Alternatively the configuration debug port on the module can be used to issue the command directly to the module All three of these methods will force the module to download the configuration to the ControlLogi...

Страница 25: ... type under the User Defined Data Type option in the Controller Organization window Data Transfer Parameters CASModule This object defines the parameters for data movement between the module and the processor Values entered determine the ladder logic and data size required in the application The ReadData and WriteData arrays must be sized to or larger than the count values entered The ladder logic...

Страница 26: ...e will be retried the entered number of times before a failure will be reported and communication will cease on the ports When backplane communication is restored the module will start communicating on the network For example if you enter a value of 10 for the parameter the module will stop all TCA communications if 10 successive backplane errors are recognized When a successful transfer is recogn...

Страница 27: ...bjects These objects hold data to be transferred between the processor and the MVI56 CAS module The user data is the read and write data transferred between the processor and the module as pages of data up to 200 words long The read data ReadData is an array set to match the value entered in the ReadRegCnt parameter of the CASModule object For ease of use this array should be dimensioned as an eve...

Страница 28: ...ssed from the processor to the module for status and control information for use in other nodes on the network 2 1 5 TCA Message Data The module s program relies on the pass through mode Write messages sent to a slave port are passed directly through to the processor It is the responsibility of the ladder logic to process the message received using this feature Three data objects are required for ...

Страница 29: ...ladder logic are module data transfer special block handling and status data receipt Additionally a power up handler may be needed to handle the initialization of the module s data and to clear any processor fault conditions The sample ladder logic on the ProSoft Solutions CD ROM is extensively commented to provide information on the purpose and function of each rung For most applications the samp...

Страница 30: ...MVI56 CAS ControlLogix Platform Ladder Logic Teledyne CA Slave Module Page 30 of 86 ProSoft Technology Inc December 26 2007 ...

Страница 31: ... configuration This data is transferred to the ControlLogix processor continuously with each read block For a complete listing of the status data object refer to the Module Set Up section 4 1 1 The Configuration Debug Menu The Configuration and Debug menu for this module is arranged as a tree structure with the Main Menu at the top of the tree and one or more sub menus for each menu command The fi...

Страница 32: ...of these characters will require you to use the Shift Ctrl or Alt keys to enter them correctly For example on US English keyboards enter the command as Shift Also take care to distinguish capital letter I from lower case letter l L and number 1 likewise for capital letter O and number 0 Although these characters look nearly the same on the screen they perform different actions on the module 4 1 2 ...

Страница 33: ...ull modem cable 2 Start the communication program on your computer and configure the communication parameters with the following settings Baud Rate 57 600 Parity None Data Bits 8 Stop Bits 1 Software Handshaking None 3 Open the connection When you are connected press the key on your keyboard If the system is set up properly you will see a menu with the module name followed by a list of letters and...

Страница 34: ...eless Please be careful when pressing keys so that you do not accidentally execute an unwanted command Opening the Data Analyzer Menu Press A to open the Data Analyzer Menu Use this command to view all bytes of data transferred on each port Both the transmitted and received data bytes are displayed Refer to Data Analyzer for more information about this menu Important When in analyzer mode program ...

Страница 35: ...mation when calling for technical support on the product Values at the bottom of the display are important in determining module operation The Program Scan Counter value is incremented each time a module s program cycle is complete Tip Repeat this command at one second intervals to determine the frequency of program execution Warm Booting the Module Caution Some of the commands available to you fr...

Страница 36: ...Ports 1 and 2 Use this command to view communication status and statistics for the selected port This information can be informative when troubleshooting communication problems Viewing Port Configuration Press 6 or 7 from the Main Menu to view configuration information for ports 1 and 2 Use this command to display detailed configuration information for the selected port Exiting the Program Caution...

Страница 37: ... disconnecting from the Config Debug port please press S to stop the data analyzer and then press M to return to the main menu This action will allow the module to resume its normal high speed operating mode Analyzing Data for the first application port Press 1 to display I O data for the first application port in the Data Analyzer The following illustration shows an example of the Data Analyzer o...

Страница 38: ...l be displayed An example display is shown below The Data Analyzer displays the following special characters Character Definition Data enclosed in these characters represent data received on the port Data enclosed in these characters represent data transmitted on the port R These characters are inserted when the RTS line is driven high on the port R These characters are inserted when the RTS line ...

Страница 39: ...Tips From the main menu press A for the Data Analyzer You should see the following text appear on the screen After the Data Analyzer mode has been selected press to view the Data Analyzer menu You will see the following menu From this menu you can select the Port the format and the ticks that you can display the data in For most applications HEX is the best format to view the data and this does in...

Страница 40: ...t a directory to store the file in In this example we are creating a file ProSoft txt and storing this file on our root C drive After you have done this press the button Now you have everything that shows up on the HyperTerminal screen being logged to a file called ProSoft txt This is the file that you will then be able to email to ProSoft Technical Support to assist with issues on the communicati...

Страница 41: ...tion back And finally all characters shown in the brackets is information being received from another device by the module After taking a minute or two of traffic capture you will now want to stop the Data Analyzer To do so press the S key and you will then see the scrolling of the data stop When you have captured the data you want to save open the Transfer menu and choose Capture Text On the seco...

Страница 42: ...ck one page of data Goes back five pages of data Selects page 0 1000 2000 or 3000 Displays data in decimal format Goes forward one page of data Goes forward five pages of data Displays data in text format Displays data in floating point format Displays data in hex format S Show Again Redisplays last selected page of data Display Menu Redisplays refreshes this menu Viewing Register Pages To view se...

Страница 43: ...t and display the next 100 registers of data Viewing Data in Decimal Format Press D to display the data on the current page in decimal format Viewing Data in Hexadecimal Format Press H to display the data on the current page in hexadecimal format Viewing Data in Floating Point Format Press F from the Database View menu Use this command to display the data on the current page in floating point form...

Страница 44: ...uld blink rapidly on and off Off The card is not receiving any power and is not securely plugged into the rack Green The module is operating normally OK Red Green Red The program has detected an error or is being configured If the LED remains red for over 10 seconds the program has probably halted Remove the card from the rack and re insert the card to restart the module s program Off The battery ...

Страница 45: ...lease contact ProSoft Technology Technical Support Processor Errors Problem Description Steps to take Processor Fault Verify that the module is plugged into the slot that has been configured for the module Verify that the slot in the rack configuration has been set up correctly in the ladder logic Processor I O LED flashes This indicates a problem with backplane communications Verify that all modu...

Страница 46: ...MVI56 CAS ControlLogix Platform Diagnostics and Troubleshooting Teledyne CA Slave Module Page 46 of 86 ProSoft Technology Inc December 26 2007 ...

Страница 47: ... compatible devices 5 1 1 Features and Benefits The MVI56 CAS module acts as an input output module between the TCA network and the ControlLogix backplane The data transfer from the ControlLogix processor is asynchronous from the actions on the TCA network A 5000 word register space in the module exchanges data between the processor and the TCA network 5 1 2 General Specifications Single Slot 1756...

Страница 48: ...re handshaking control providing radio modem and multi drop support Software configurable communication parameters Baud rate 110 to 115 200 baud depending on protocol RS 232 and 422 Parity none odd or even Data bits 5 6 7 or 8 Stop bits 1 or 2 RTS on off delay 0 to 65535 milliseconds App Ports P1 P2 Serial modules RJ45 DB 9M with supplied cable RS 232 handshaking configurable 500V Optical isolatio...

Страница 49: ... of how the MVI56 CAS module transfers data using the CAS protocol You should understand the important concepts in this chapter before you begin installing and configuring the module 5 2 1 General Concepts The following topics describe several concepts that are important for understanding the operation of the MVI56 CAS module On power up the module begins performing the following logical functions...

Страница 50: ...running state the module will resume communications on the network Backplane Data Transfer The MVI56 CAS module communicates directly over the ControlLogix backplane Data is paged between the module and the ControlLogix processor across the backplane using the module s input and output images The update frequency of the images is determined by the scheduled scan rate defined by the user for the mo...

Страница 51: ...sor over the backplane is through the input and output images Ladder logic must be written in the ControlLogix processor to interface the input and output image data with data defined in the Controller Tags All data used by the module is stored in its internal database This database is defined as a data table with addresses from 0 to 6999 The following illustration shows the layout of the database...

Страница 52: ...hrough read input image and write output image blocks Refer to the Module Set Up section for a description of the data objects used with the blocks and the ladder logic required The structure and function of each block is discussed below Read Block These blocks of data transfer information from the module to the ControlLogix processor The structure of the input image used to transfer this data is ...

Страница 53: ...ntroller or by a command request from a node on the TCA network or operator control through the module s Configuration Debug port Write Block These blocks of data transfer information from the ControlLogix processor to the module The structure of the output image used to transfer this data is shown in the following table Offset Description Length 0 Write Block ID 1 1 to 200 Write Data 200 201 to 2...

Страница 54: ... 244 249 2 or 3 1 If there are any errors in the configuration the bit associated with the error will be set in one of the three configuration error words The error must be corrected before the module starts operating 5 2 4 Write Configuration This block is sent from the ControlLogix processor to the module to force the module to write its current configuration back to the processor This function ...

Страница 55: ...hat requires a hardware reset The structure of the control block is shown in the following table Offset Description Length 0 9999 1 1 to 247 Spare 247 5 2 5 Pass Through Control Blocks The module will pass blocks with identification codes of 9991 9992 and 9994 to the processor for each received write command Ladder logic must handle the receipt of all TCA write functions to the processor and to re...

Страница 56: ...Module Register Data storage Register Data Processor Memory CAS Module Backplane Interface Configuration Status Read Functions Write Functions Step Description 1 The TCA slave port driver receives the configuration information from the ControlLogix processor This information configures the serial port and define the slave node characteristics Additionally the configuration information contains dat...

Страница 57: ...parameter to 1 5 3 1 RS 232 Configuration Debug Port This port is physically an RJ45 connection An RJ45 to DB 9 adapter cable is included with the module This port permits a PC based terminal emulation program to view configuration and status data in the module and to control the module The cable for communications on this port is shown in the following diagram Disabling the RSLinx Driver for the ...

Страница 58: ...browsed network 3 Notice how the DF1 driver is opened and the driver is looking for a processor on node 1 If the network is being browsed then you will not be able to stop this driver To stop the driver your RSWho screen should look like this Branches are displayed or hidden by clicking on the or the icons 4 When you have verified that the driver is not being browsed go to Communications Configure...

Страница 59: ...m port to connect to the debug port of the module Note You may need to shut down and restart your PC before it will allow you to stop the driver usually only on Windows NT machines If you have followed all of the above steps and it will not stop the driver then make sure you do not have RSLogix open If RSLogix is not open and you still cannot stop the driver then reboot your PC 5 3 2 RS 232 When t...

Страница 60: ...is required between the module and a modem or other communication device The Use CTS Line parameter for the port configuration should be set to Y for most modem applications RS 232 Null Modem Connection Hardware Handshaking This type of connection is used when the device connected to the module requires hardware handshaking control and monitoring of modem signal lines ...

Страница 61: ...7 RS 232 Null Modem Connection No Hardware Handshaking This type of connection can be used to connect the module to a computer or field device communication port Note If the port is configured with the Use CTS Line set to Y then a jumper is required between the RTS and the CTS line on the module connection 5 3 3 RS 422 ...

Страница 62: ... three wire cable The Common connection is optional and dependent on the RS 485 network The cable required for this interface is shown below RS 485 and RS 422 Tip If communication in the RS 422 RS 485 mode does not work at first despite all attempts try switching termination polarities Some manufacturers interpret and A B polarities differently 5 3 5 DB9 to RJ45 Adaptor Cable 14 ...

Страница 63: ...ion of the database 5 5 MVI56 CAS Status Data Definition This section contains a description of the members present in the CASInStat object This data is transferred from the module to the processor as part of each read block Offset Content Description 202 Program Scan Count This value is incremented each time a complete program cycle occurs in the module 203 to 204 Product Code These two registers...

Страница 64: ...ead Block Count This field contains the total number of read blocks transferred from the module to the processor 226 Write Block Count This field contains the total number of write blocks transferred from the processor to the module 227 Parse Block Count This field contains the total number of blocks successfully parsed that were received from the processor 228 Command Event Block Count This field...

Страница 65: ...de on the network and is read from the ControlLogix processor when the module first initializes 5 6 1 Port 1 Group Register Content Description Backplane Setup 5000 Status Length This parameter specifies the number of status words in the module 0 to 250 5001 Analog Length This parameter specifies the number of analog words in the module 0 to 250 5002 Meter Length This parameter specifies the numbe...

Страница 66: ...his parameter specifies the minimum number of milliseconds to delay before responding to a request message This pre send delay is applied before the RTS on time This may be required when communicating with slow devices 5018 Use CTS Line This parameter specifies if the CTS modem control line is to be used If the parameter is set to 0 the CTS line will not be monitored If the parameter is set to 1 t...

Страница 67: ... are 0 to 65535 5047 Minimum Response Time This parameter specifies the minimum number of milliseconds to delay before responding to a request message This pre send delay is applied before the RTS on time This may be required when communicating with slow devices 5048 Use CTS Line This parameter specifies if the CTS modem control line is to be used If the parameter is set to 0 the CTS line will not...

Страница 68: ...ontains the number of command errors processed on the port These errors could be due to a bad response or command 6012 Port 1 Requests This field contains the total number of messages sent out of the port 6013 Port 1 Responses This field contains the total number of messages received on the port 6014 Port 1 Errors Sent This field contains the total number of error messages sent out of the port 601...

Страница 69: ...the current error code returned For a master port this field contains the index of the currently executing command 6030 Port 1 Last Error For a slave port this field contains the value of the last error code returned For a master port this field contains the index of the command with an error 6031 Port 2 Current Error For a slave port this field contains the value of the current error code returne...

Страница 70: ...ansferring general configuration information Ladder logic must handle the 9997 command No ladder logic is required when using the warm or cold boot commands 5 8 Protocol Commands The ProSoft Technology CAS module communication driver supports several data read and write commands When configuring an application it may be important to understand how the commands function in order to determine how to...

Страница 71: ...and is supported in the ProSoft module The following Data Select Types are available from the module Status Inputs Data Select 1 bit 7 Analog Inputs Data Select 1 bit 6 Meter Accumulator Inputs Data Select 1 bit 5 Current Tank Data Data Select 1 bit 2 Maximum Analogs Register Data Select 1 bit 1 Local Freeze Analog Data Data Select 1 bit 0 Local Freeze Meter Data Data Select 2 bit 7 Local Freeze T...

Страница 72: ...5 Setpoint Select Operate These control commands are recognized by the module If the Operate command is received out of sequence must be received in next communication sequence after Select command the command is disregarded If the module is configured for Direct Control then the Master need only send the Operate command for action to occur In TCAP vernacular the Card Number upper 7 bits is combin...

Страница 73: ...anges enough to meet exception requirements into an exception table The data must change more than the default dead bands in order to record an exception The default dead bands are Analog Dead Band 1000 Meter Dead Band 100 Tank Dead Band 0 Status Dead Band 0 Function Function Name Description 50 Exception Data Request Two modes are supported Current Exceptions and All Exception Data The mode is se...

Страница 74: ...MVI56 CAS ControlLogix Platform Reference Teledyne CA Slave Module Page 74 of 86 ProSoft Technology Inc December 26 2007 ...

Страница 75: ...contact us at Internet Web Site http www prosoft technology com support E mail address support prosoft technology com Those of us at ProSoft Technology Inc want to provide the best and quickest support possible so before calling please have the following information available You may wish to fax this information to us prior to calling 1 Product Version Number 2 System architecture 3 Network detail...

Страница 76: ...1 Jalan SS20 27 47400 Petaling Jaya Selangor Malaysia 603 7724 2080 asiapc prosoft technology com Languages spoken include Chinese Japanese English China Pacific office in China 86 21 64518356 x 8011 86 21 64756957 Fax 4 F No 16 Hongcao Road Shanghai China 200233 China 86 21 64518356 x 8011 zhang prosoft technology com Languages spoken include Chinese English Europe Middle East Africa office in To...

Страница 77: ...number is to be prominently marked on the outside of the shipping box Customer agrees to insure the Product or assume the risk of loss or damage in transit Products shipped to ProSoft without an RMA number will be returned to the Customer freight collect Contact ProSoft Technical Support for further information 4 Out of warranty returns are not allowed on RadioLinx accessories such as antennas cab...

Страница 78: ... immediate exchange a new module may be purchased and sent to Customer while repair work is being performed Credit for purchase of the new module will be issued when the new module is returned in accordance with ProSoft s shipping instructions and subject to ProSoft s policy on non warranty returns This is in addition to charges for repair of the old module and any associated charges to Customer 4...

Страница 79: ...hed specifications prepared approved and issued by ProSoft and 2 will be free from defects in material or workmanship provided these warranties only cover Product that is sold as new This Warranty expires one year or in the case of RadioLinx modules three years from the date of shipment the Warranty Period If the Customer discovers within the Warranty Period a failure of the Product to conform to ...

Страница 80: ...unctions or any other non conformance defects losses or damages caused by or attributable to any of the following i shipping ii improper installation or other failure of Customer to adhere to ProSoft s specifications or instructions iii unauthorized repair or maintenance iv attachments equipment options parts software or user created programming including but not limited to programs developed with...

Страница 81: ...MITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE 6 5 5 LIMITATION OF REMEDIES IN NO EVENT WILL PROSOFT OR ITS DEALER BE LIABLE FOR ANY SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES BASED ON BREACH OF WARRANTY BREACH OF CONTRACT NEGLIGENCE STRICT TORT OR ANY OTHER LEGAL THEORY DAMAGES THAT PROSOFT AND ITS DEALER WILL NOT BE RESPONSIBLE FOR INCLUDE BUT ARE NOT LI...

Страница 82: ...e to convey to Customer any right to make or have made any Product supplied by ProSoft D Customer is granted no right or license to use any software or other intellectual property in any manner or for any purpose not expressly permitted by any license agreement accompanying such software or other intellectual property E Customer agrees that it shall not and shall not authorize others to copy softw...

Страница 83: ...ontrolling Law and Severability This Warranty shall be governed by and construed in accordance with the laws of the United States and the domestic laws of the State of California without reference to its conflicts of law provisions If for any reason a court of competent jurisdiction finds any provisions of this Warranty or a portion thereof to be unenforceable that provision shall be enforced to t...

Страница 84: ...MVI56 CAS ControlLogix Platform Support Service Warranty Teledyne CA Slave Module Page 84 of 86 ProSoft Technology Inc December 26 2007 ...

Страница 85: ...4 62 Diagnostics and Troubleshooting 7 31 Disabling the RSLinx Driver for the Com Port on the PC 33 57 DISCLAIMER OF ALL OTHER WARRANTIES 81 DISCLAIMER REGARDING HIGH RISK ACTIVITIES 81 Displaying the Current Page of Registers Again 42 Displaying Timing Marks in the Data Analyzer 37 Download the Sample Program to the Processor 14 E Exception Data Commands 73 Exiting the Program 36 F Features and B...

Страница 86: ... 62 RS 485 and RS 422 Tip 62 S Setting Jumpers 11 Skipping 500 Registers of Data 43 Slave Driver 56 Start Here 7 9 Starting the Data Analyzer 38 Status 68 Status Object CASInStat 27 Stopping the Data Analyzer 38 Support Service Warranty 7 75 System Requirements 9 T TCA Message Data 28 TCA Port Parameters CASPort 26 The Configuration Debug Menu 31 Time Limit for Bringing Suit 81 Transferring Module...

Отзывы: