Installing and Configuring the Module
MVI56-CAS
♦
ControlLogix Platform
Teledyne CA Slave Module
ProSoft Technology, Inc.
Page 23 of 86
December 26, 2007
The last step in the module setup is to add the ladder logic. If you are using the
example ladder logic, adjust the ladder to fit your application. If you are not using
the ladder example, copy the ladder logic shown in the Controller Organization
window below to your application.
The module is now set up and ready to be used with your application. Insert the
module in the rack and attach the TCA serial communication cables. Download
the new application to the controller and place the processor in run mode. If all
the configuration parameters are set correctly and the module is attached to a
TCA network, the module's Application LED (APP LED) should remain off and
the backplane activity LED (BP ACT) should blink very rapidly. Refer to the
Diagnostics and
Troubleshooting
section of this manual if you encounter
errors. Attach a computer or terminal to Debug/Configuration port on the module
and look at the status of the module using the Configuration/Debug Menu in the
module.
2.1 Module
Configuration
In order for the MVI56-CAS module to function, a minimum amount of
configuration data must be transferred to the module. The following table
provides an overview of the different types of configuration data that the module
will require, depending on the operating modes to be supported.
Module
Register
Address
Functional Modes
Affected
Name Description
5000 to 5009
Data Transfer
General Module
Configuration
This section of the configuration data contains the
module configuration data that defines the data
transfer between the module and the ControlLogix
processor.
5010 to 5039
and 5040 to
5069
Master and Slave
Port Configuration
These sections define the characteristics of each of
the TCA serial communication ports on the module.
These parameters must be set correctly for proper
module operation.
Refer to the Installing and Configuring the Module section for a description of the
configuration of the module. The MVI56-CAS module must be configured at least
once when the card is first powered, and any time thereafter when the
parameters must be changed.