Installing and Configuring the Module
MVI56-CAS
♦
ControlLogix Platform
Teledyne CA Slave Module
ProSoft Technology, Inc.
Page 21 of 86
December 26, 2007
Fill in the dialog boxes as shown adjusting the Name, Description and Slot
options for your application. You must select the
Comm Format
as
Data - INT
in
the dialog box. Failure to set the
Assembly Instance
and
Size
values correctly
will result in a module that will not communicate over the backplane of the
ControlLogix rack. Click Next to display the next dialog box.
Select the Request Packet Interval value for scanning the I/O on the module.
This value represents the minimum frequency the module will handle scheduled
events. This value should not be set to less than 1 millisecond. Values between 1
and 10 milliseconds should work with most applications.
After completing the module setup, the Controller Organization window will
display the module's presence. The data required for the module will be defined
to the application, and objects will be allocated in the Controller Tags data area.
An example of the Controller Organization window is shown below: