MVI56-CAS
♦
ControlLogix Platform
Installing and Configuring the Module
Teledyne CA Slave Module
Page 26 of 86
ProSoft Technology, Inc.
December 26, 2007
The BPFail parameter determines if the module should continue communicating
on the TCA network when the backplane transfer operation fails. A value of zero
indicates that the module should continue communicating when the backplane is
not operational. If the value is greater than zero, the backplane will be retried the
entered number of times before a failure will be reported and communication will
cease on the ports. When backplane communication is restored, the module will
start communicating on the network. For example, if you enter a value of 10 for
the parameter, the module will stop all TCA communications if 10 successive
backplane errors are recognized. When a successful transfer is recognized, the
module will resume communications on the network.
TCA Port Parameters (CASPort)
This object defines the parameters for the operation of each of the TCA ports on
the module. Refer to the Reference chapter for the definition of each parameter.