502 069 02
Manual
Power Monitor, PD 3260
59/79
9
Program Channel (channel D).
The Program Channel utilises Program Invocation Management, and specifies some general
information about a Calculator program in the PD 3260. The Calculator program is an application
program, which can be downloaded or uploaded via this channel, and the status of the program
can be supervised and changed.
The program in the library is indexed by a number, LibraryIndex, which is found in Library-
Control. The total number of programmes, which can be stored in the library memory is stated in
MaxLibraryIndex, which is found in LibraryStatus. The total number of programmes that can be
held within the PD 3260 module is 1.
The selected program can be controlled and supervised. The commands and program states
conform to the instructions specified in Manufacturing Message Specification (MMS).
Registers on Program Channel (channel n).
Channel identifier: Calculator
SWNo
Identifier
Memory Type
Read Out
Type
D0
ProgramControl
RAM Read Write
- - - - - - -
Record
D1
ProgramStatus
RAM Read Only
- - - - - - -
Record
D2
ProgramID
Read Only
- - - - - - -
Record
D5
SystemPointer
Read Only
Hex
LongInteger
D7
MemoryInfo
Read Only
- - - - - - -
Record
D8
IDAndCode
Special function
- - - - - - -
Record
D9
ChConfig
EEPROM RPW
- - - - - - -
Record
DA
LibraryControl
RAM Read Write
- - - - - - -
Record
DB
LibraryStatus
RAM Read Only
- - - - - - -
Record
DC
LibraryProgramID
Read Only
- - - - - - -
Record
DD
Maintenance
EEPROM RPW
- - - - - - -
Record
DE
ChType
PROM Read Only
- - - - - - -
Record
DF
ChError
RAM Read Only
- - - - - - -
Record
SWNo $D0: ProgramControl
ProgramControl is used to set and change the state of the current program, which has been
selected and invoked via the Program Channel. The selected program number is inserted and
shown as a part of ProgramControl. Commands can be sent to ProgramControl, to stop/start or
reset the program.