Power Monitor, PD 3260
Manual
The 8 bits in ChError.His and ChError.Act have the following meaning. When an error occurs,
the corresponding bit is set in both ChError.His and ChError.Act. When the error disappears, the
bit is cleared in ChError.Act.
7 6 5 4 3 2 1 0
Module error
Not used
Not used
Not used
Not used
Not used
Switch Error
Not used
Bit 7
Module Error: If this bit is set, the rest of the bits have no meaning, because a Module
error can lead to random error codes on individual channels (also see "Service channel").
Bit 1
Switch Error: Generator not connected, due to the fact that the generator frequency has
passed the line frequency by the frequency difference specified in StartSpeed. The value
inserted in StartSpeed may be too small.