User Manual
Page 57 of 77
(PVI-6000-OUTD-US-W Rev.2.0)
5.5.6.12
UV Prot.time
This function is used to set the inverter connection time after the input voltage
drops below the undervoltage protection threshold that is set at 40V.
For example: if UV Prot.time is set at 60 seconds, and Vin voltage drops below
40V at 9:00am the inverter will stays connected to the grid (at 0 power) until
9:01am.
Power-One sets this time at 60 seconds. The user can change this setting and set it
from 1 second to 3,600 seconds.
5.5.6.13
Alarm Message
Is possible to program the error message to be shown in the display using the
following procedure:
Press to access the following submenu:
Use the button on the left side of the display to move UP (switch 2) and DOWN
(switch 3) the arrow and press ENTER (switch 4) to select the desiderate function.
Once the menu ENABLE/DISABLE is selected the following screen will appear. It
is possible to enable or disable the custom error message function in this screen:
Select the line ENABLE MESSAGE and press ENTER, the following screen will
appear on the display:
Enable / Disable
Compose message
Enable / Disable
Compose message
Enable message
Disabile message
Alarm message
Remote OFF
Waiting Rem.ON…
….to restart
Содержание AURORA PVI-6000-OUT-US-W
Страница 1: ...AURORA Wind Inverters INSTALLATION AND OPERATION MANUAL Model number PVI 6000 OUT US W Rev 2 0...
Страница 32: ...User Manual Page 32 of 77 PVI 6000 OUTD US W Rev 2 0 Fig 17 Data Transmission Options...
Страница 60: ...User Manual Page 60 of 77 PVI 6000 OUTD US W Rev 2 0...
Страница 73: ...User Manual Page 73 of 77 PVI 6000 OUTD US W Rev 2 0...
Страница 74: ...User Manual Page 74 of 77 PVI 6000 OUTD US W Rev 2 0...
Страница 75: ...User Manual Page 75 of 77 PVI 6000 OUTD US W Rev 2 0...
Страница 76: ...User Manual Page 76 of 77 PVI 6000 OUTD US W Rev 2 0...
Страница 77: ...User Manual Page 77 of 77 PVI 6000 OUTD US W Rev 2 0...