User Manual
Page 70 of 77
(PVI-6000-OUTD-US-W Rev.2.0)
8.2
Output Value
Description
Value
PVI – 6000 – OUTD – US-W
Nominal output power
6,000 W
Grid voltage, maximum range
180 to 264 Vac
Grid connection, nominal
Split phase
Grid voltage, nominal
240 Vac
Grid voltage, operating range
82% to 115% of nominal voltage
(188.6 to 264Vac for V=230Vac)
Grid frequency, maximum range
47 to 63 Hz
Grid frequency, nominal
60 Hz
Grid frequency, operating range
59.72 to 60.28 Hz
Nominal output current
26 Arms
Max. output current
30 Arms
Output over current protection
40 Arms
8.3
Grid protection characteristics
Anti islanding protection
Complies with UL 1741 standard.