(PVI-6000-OUTD-US-W Rev.2.0)
3.6
Electrical Connections
Step 1/6: Open the AC grid disconnect switch
Step 2/6: Open the Wind Generator AC disconnect breaker.
Step 3/6: Unscrew the 4 screws to open the front panel
Step 4/6: Connect the inverter to the AC grid disconnect switch
WARNING:
Use suitable low-impedance cables to connect the inverter
to the AC disconnect switch.
WARNING:
The inverter must be connected to the AC grid disconnect
switch using a three-wire cable with two line wires and a neutral wire.
1)
Route the cable from the inverter to the AC disconnect
2)
Connect the three-pole cable to AURORA using the cable gland on
the case
3)
Connect the three wires as follows:
-
terminal 1 – to Line 1
-
terminal 2 – to Line 2
-
terminal 3 – to Neutral (center tap of the split phase)
Fig.11 AC wire terminal block
WARNING:
Default connection of the inverter is to the grid configured
as a 240V split phase system. Contact Power-One if your grid is
configured as a single phase or a three-phase system.
Содержание AURORA PVI-6000-OUT-US-W
Страница 1: ...AURORA Wind Inverters INSTALLATION AND OPERATION MANUAL Model number PVI 6000 OUT US W Rev 2 0...
Страница 32: ...User Manual Page 32 of 77 PVI 6000 OUTD US W Rev 2 0 Fig 17 Data Transmission Options...
Страница 60: ...User Manual Page 60 of 77 PVI 6000 OUTD US W Rev 2 0...
Страница 73: ...User Manual Page 73 of 77 PVI 6000 OUTD US W Rev 2 0...
Страница 74: ...User Manual Page 74 of 77 PVI 6000 OUTD US W Rev 2 0...
Страница 75: ...User Manual Page 75 of 77 PVI 6000 OUTD US W Rev 2 0...
Страница 76: ...User Manual Page 76 of 77 PVI 6000 OUTD US W Rev 2 0...
Страница 77: ...User Manual Page 77 of 77 PVI 6000 OUTD US W Rev 2 0...