Installation and Operator’s Manual
Page 100 of 108
(PVI-3.0/3.6/4.2-OUTD-x-US Rev: 2.1)
The PVI-4.2(3.6,3.0)-OUTD-x-US voltage and frequency limits are listed in the
following table:
Trip Limits
Condition
Voltage (V)
Frequency (Hz)
Trip Times
(sec)
A
< 0.55 V
nor
b
Rated
(60
Hz) 0.12
B 0.55
V
nor
b
≤
V < 0.90
V
nor
Rated (60 Hz)
1.8
C 1.08
V
nor
b
< V <
max(1.18 V
nor
;
310Vac)
Rated (60 Hz)
0.9
D max(1.18
V
nor
;
310Vac)V
nor
≤
V
Rated (60 Hz)
0.12
E
Rated
f > rated + 0.42
0.12
F Rated
f
<
rated
–0.62
0.12
Accuracy 2%
0.02Hz
0.033
b
V
is the nominal output voltage rating.
8.7
Fault Current
The output current in case of fault (short circuit between lines or between line and
neutral) has been measured according to UL1741 requirements. The following tables
shows the corresponding current and duration:
Models Output
Voltage
Fault
Current
RMS (A)
Duration
(mSec)
3 cycles
Fault
Current
PK (A)
Total
Duration
(mSec)
208 13.5 49.92
122.4
119.0
240 14.7 49.92
164.4
120.9
PVI-4.2-
OUTD
Series
277 12.3 49.92
165.9
123.2
208 12.2 49.92
93.9 124.4
240 12.5 49.92
136.5
120.2
PVI-3.6-
OUTD
Series
277 11.3 49.92
164.6
116.3
Содержание AURORA PVI-3.0-OUTD-S-US
Страница 52: ...Installation and Operator s Manual Page 52 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 Fig 17 USB Port ...
Страница 80: ...Installation and Operator s Manual Page 80 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...
Страница 104: ...Installation and Operator s Manual Page 104 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...
Страница 105: ...Installation and Operator s Manual Page 105 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...
Страница 106: ...Installation and Operator s Manual Page 106 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...
Страница 107: ...Installation and Operator s Manual Page 107 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...
Страница 108: ...Installation and Operator s Manual Page 108 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...