Installation and Operator’s Manual
Page 32 of 108
(PVI-3.0/3.6/4.2-OUTD-x-US Rev: 2.1)
WARNING:
In order to thighten correctly the screw terminal of the switch
box apply the AWG size, temperature and torque listed in the following table.
The restrictions on minimum AWG value is due to cable gland. The
restrictions on maximum AWG value is due to National Electric Code
(ANSI/NFPA 70).
Wire Size
Temp
Torque
Models PVI-4.2(3.6)-
OUTD-S-US
AWG
(min-max)
°C Nm
In-
lbs
4-10 90
AC and GND field
wiring terminals
4-8 75
2.26 20
4-10 90
DC field wiring
terminals
4-8 75
2.26 20
4-10 90
Grounding Electrode
4-8 75
5.08 45
Wire Size
Temp
Torque
Models PVI-3.0-
OUTD-S-US
AWG
(min-max)
°C Nm
In-
lbs
4-10 90
AC and GND field
wiring terminals
4-8 75
2.26 20
4-12 90
DC field wiring
terminals
4-10 75
2.26 20
4-10 90
Grounding Electrode
4-8 75
5.08 45
Содержание AURORA PVI-3.0-OUTD-S-US
Страница 52: ...Installation and Operator s Manual Page 52 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 Fig 17 USB Port ...
Страница 80: ...Installation and Operator s Manual Page 80 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...
Страница 104: ...Installation and Operator s Manual Page 104 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...
Страница 105: ...Installation and Operator s Manual Page 105 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...
Страница 106: ...Installation and Operator s Manual Page 106 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...
Страница 107: ...Installation and Operator s Manual Page 107 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...
Страница 108: ...Installation and Operator s Manual Page 108 of 108 PVI 3 0 3 6 4 2 OUTD x US Rev 2 1 ...