Diagnostics consumers
Prog. no.
Level Standard value
Relay output QX22 module 1
Off | On
9051
C
Relay output QX23 module 1
Off | On
9052
C
Relay output QX21 module 2
Off | On
9053
C
Relay output QX22 module 2
Off | On
9054
C
Relay output QX23 module 2
Off | On
9055
C
Burner control
Prog. no.
Level Standard value
Prepurge time
9500
E
15 s
Required output prepurging
9504
E
Paramount four 30:
14,5 kW; Paramount
four 40: 19.5 kW
Paramount four 50:
32,0 kW; Paramount
four 60: 35,0 kW; Pa‐
ramount four 80: 50,0
kW; Paramount four
95: 50,8 kW; Para‐
mount four 115: 56.6
kW
Required output ignition
1)
9512
E
Paramount four 30:
14,5 kW; Paramount
four 40: 19.5 kW
Paramount four 50:
32,0 kW; Paramount
four 60: 35,0 kW; Pa‐
ramount four 80: 50,0
kW; Paramount four
95: 50,8 kW; Para‐
mount four 115: 56.6
kW
Required output LF
1)
9524
E
Paramount four 30:
5,6 kW; Paramount
four 40: 9.0 kW
Paramount four 50:
10,0 kW; Paramount
four 60: 14,0 kW; Pa‐
ramount four 80: 21,0
kW; Paramount four
95: 20,0 kW; Para‐
mount four 115: 25.0
kW
Required output HF
1)
9529
E
Paramount four 30:
30,0 kW; Paramount
four 40: 38.0 kW
Paramount four 50:
50,0 kW; Paramount
four 60: 58,0 kW; Pa‐
ramount four 80: 77,0
kW; Paramount four
95: 95,0 kW; Para‐
mount four 115:
115,0 kW
Postpurge time
9540
E
10 s
9 Settings
78
Paramount four 30 – 115 kW
7658013 - 02 - 15092016