control goes in a parameterization position. As soon as parameters are
transferred, the LMS control must be unlocked transmission has ended.
Fault 183 parameterization is displayed.
Writing on stick: Starts writing the data from the LMS control to the stick.
This operation is only possible with WRITE sticks. The data is written in
to the previously set data set. Before writing of the data begins, it is
checked whether the stick has sufficient capacity for the data and that
the respective customer number is correct. The textWriting on stick re
mains until the operation is completed or a fault occurs.
PStick progress (7253)
The read or write progress is displayed as a percentage. If no operation is
active or a fault occurs, 0% is displayed.
PStick status (7254)
No stick: The LMS control has not detected a stick (the stick may not be
inserted).
Stick ready: Basic condition, stick is detected, no action active, no error
present.
Writing on stick: Data is copied (backup) from the LMS control to the
stick.
Reading from stick: Data is transferred from the stick to the LMS control.
EMC test active: Special function for EMC tests in the lab. A special
compiler switch must be set for this.
Writing error: An error occurred when copying the data from the LMS
control to the stick. The operation was aborted.
Reading error: An error occurred when copying the data from the stick to
the LMS control.. The operation was aborted. The control LMS is locked.
Status change to read lock.
Incompatible data set: Data set does not match LMS control. Compati
bility conditions are not met. The data set can not be imported.
Wrong stick type: Stick type does not match selected action. E.g. read
ing from write stick or writing to read stick is not possible.
Stick format error: Incorrect customer number on the stick or data format
on the stick is unknown and cannot be evaluated by the LMS control.
Check data set: During transmission of a data set from the stick to the
LMS control a problem occurred, but it did not lead to an abort.
Data set disabled: The data set may not be transferred into the LMS
control (read protected).
Reading disabled: The parameterization position is in the
ABORT
state.
Only limited actions are possible to cancel the parameterization position.
9.2.21 Configuration of extension modules
Function extension module 1 (7300), Function extension
module 2 (7375)
When a function is selected, the inputs and outputs are occupied on the
extension module with the functions according to the following table:
Connection ter
minal on module
QX21 QX22 QX23 BX2
1
BX2
2
H2/H21 H22
Multi-functional
*
*
*
*
*
*
*
Heating circuit 1
Y1
Y2
Q2
B1
*
*
*
Heating circuit 2
Y5
Y6
Q6
B12
*
*
*
Heating circuit 3
Y11
Y12
Q20
B14
*
*
*
Solar DHW
*
*
Q5
B6
B31
*
*
Primary control/
system pump
Y19
Y20
Q14
B15
*
*
*
* Freely selectable in QX.../ BX...
FS = DHW flow switch; AVS75.390 = H2; AVS75.370 = H21
9 Settings
7658013 - 02 - 15092016
Paramount four 30 – 115 kW
117