Solid fuel boiler
Prog. no.
Level Standard value
Locks other heat sources
Off | On
4102
E
Off
Setpoint min
4110
E
65 °C
Temp diff on
4130
E
8 °C
Temp diff off
4131
E
4 °C
Comparative temp
Hot water sensor B3 | Hot water sensor B31 | Buffer sensor B4 | Buffer sensor
B41 | Flow temp setpoint | Setpoint min
4133
E
Buffer sensor B41
Pump overrun time
4140
E
20 min
Buffer storage tank
Prog. no.
Level Standard value
Auto generation lock
None | With B4 | With B4 and B42/B41
4720
E
With B4
Auto heat gen lock SD
4721
E
5 °C
Temp diff buffer/CH
4722
E
-3 °C
Min st tank temp heat mode
4724
E
- - - °C
Charging temp max
4750
E
80 °C
Recooling temp
4755
E
60 °C
Recooling HW/CHs
Off | On
4756
E
Off
Recooling collector
Off | Summer | Always
4757
E
Off
With solar integration
No | Yes
4783
E
Yes
Temp diff on return div
4790
E
8 °C
Temp diff off return div
4791
E
4 °C
Compar temp return div
With B4 | With B41 | With B42
4795
E
With B4
Optg action return diversion
Temp decrease | Temp increase
4796
E
Temp increase
Full charging
Off | Heating mode | Always
4810
E
Off
Full charging temp min
4811
E
8 °C
Full charging sensor
With B4 | With B42/B41
4813
E
With B42/B41
Prog. no.
Level Standard value
Forward shift charging
5011
E
60 min
Flow setpoint boost
5020
E
18 °C
Transfer boost
5021
E
10 °C
Type of charging
Recharging | Full charging | Full charging legio | Full charg 1st time day | Full
charg 1st time legio
5022
E
Full charging
Switching diff
5024
E
4 °C
Charging time limitation
5030
E
120 min
Discharging protection
Off | Always | Automatically
5040
E
Automatically
Charging temp max
5050
E
69 °C
Recooling temp
5055
E
80 °C
9 Settings
7658013 - 02 - 15092016
Paramount four 30 – 115 kW