background image

0507347110/160114/B SHIELD fire safety solutions (5k1)

| INSTALLATION | EN - 23

13.7 Solenoid valve  

13.8 FlameShield  

13.9 System control panel SCP  

13.10 Final  

   

The entire system including the ShieldControl panel must be 
tested periodically in accordance with the national fire 
protection association requirements or the authorities having 
local jurisdiction. 

The indicated maintenance intervals can vary depending on the 
specific working and ambient conditions. Therefore it is 
recommended to perform the first general maintenance check 
three months after commissioning and determine the future 
frequency based on the state of the system after this period. In 
any case the complete system must be checked at least once a 
year. 

Refer to the separate system components about method and 
frequency of maintenance. Maintenance activities have been 
summarized in the maintenance calendar below. 

14.1 Maintenance calendar

The maintenance activities in the table below indicated by [*] 
can be carried out by the user; other activities are strictly 
reserved for well trained and authorized service personnel. 

 

 

The post-fire procedure is strictly reserved to skilled and 
authorised service engineers. 

Carry out the post-fire procedure as written in paragraph 
18.2 on page 25.

  

Refer to electrical diagram on page 29. 

#

Check

OK

1.

Is the 3/2 solenoid valve mounted between 
compressed air reducer (CAR kit) and filter?

2.

Is the solenoid electrically and pneumatically 
correctly wired? When the solenoid is 
disconnected from power, the air of the 
compressed air tanks of the filter system should 
be released. 

3.

Is the solenoid functionally tested after a fire  
test alarm in the complete system set up?

#

Check

OK

1.

Are FlameShield modules undamaged?

2.

Is the correct number of FlameShield modules 
being installed?

3.

Are the FlameShield modules placed at the 
correct position? 

4.

Are the FlameShield modules pushed back to 
the middle stop of the mounting bracket to 
secure a 10° downwards release angle?

5.

Are all nuts and bolts well tightened?

6.

Are the cables tension free, well guided and 
fixed by the cable glands?

7.

Are the cable glands well tightened?

8.

Is the internal wiring/electrical activation 
checked by measuring resistance over the 
internal heating device of the FlameShield with 
a current less than 5 mA? The resistance must 
be 2 ohm.

9.

Are, in combination with ShieldControl 5k1, the 
EOL resistor-diodes of 5k1 placed in each 
junction box and the FlameShield connected to 
output 2, 3 or 4?

#

Check

OK

1.

Is the system control panel SCP correctly 
connected to the ShieldControl panel and 
peripheral equipment?

2.

Is the system control panel SCP functionally 
tested on a test alarm and performed expected 
actions (fan stops, sliding valves close, 3/2 
solenoid opens)?

#

Check

OK

1.

After all functional testing, reset all detectors 
and panels. When no alarm signals are visible, 
connect the FlameShield modules. Make sure 
that ShieldControl is on 

RUN

.

14

MAINTENANCE

Frequency

Component

* Ref. 

par.

page

Regularly, 
depending on 
intensity of use

Heat detectors

6.5

10

Spark detectors

7.5

12

Smoke detector

8.5

15

Whenever dirty

ShieldControl panel * 5.5

7

Every 6 months

Sliding valves

9.6

17

At least every 12 
months

FlameShield

11.6

20

Every year

ShieldControl panel

5.5

7

Every 4 years

ShieldControl panel

5.5

7

Every 10 years

FlameShield

11.6

20

15

POST-FIRE PROCEDURE

16

ELECTRICAL DIAGRAM

Содержание Shield 5k1

Страница 1: ...www plymovent com EN Fire safety solutions EN Installation and user manual shield 5k1...

Страница 2: ...general convenience of our clients It has been based on general data pertaining to construction material properties and working methods known to us at the time of issue of the document and is therefo...

Страница 3: ...B ranging from MDB 4 to MDB 48 other sizes on request central fan type SIF system control panel SCP round ductwork of the appropriate diameter 1 3 Functional description of SHIELD fire safety solution...

Страница 4: ...after activation thus preventing re ignition The amount of aerosol is proportional to the filter volume and can be easily adapted by adding generators The system control panel SCP M controls the filte...

Страница 5: ...cifications given in this installation manual must not be altered Modifications Modification of parts of the product is not allowed Product combinations Since the products are used in combination with...

Страница 6: ...es off fan motor is switched off release of compressed air through solenoid valve After a delay of 5 seconds sliding valves close release of aerosol by FlameShield generators during 60 seconds After a...

Страница 7: ...nect the FlameShield module s Make sure the panel is in RUN mode 5 1 Product description and operation ShieldControl 5k1 is a fire detection panel1 with a separate manual call point It has three detec...

Страница 8: ...the mains in accordance with the electrical diagram on page 29 5 5 Maintenance The ShieldControl panel itself does not require specific maintenance except for cleaning Do not use solvents or detergent...

Страница 9: ...10 160114 B SHIELD fire safety solutions 5k1 INSTALLATION EN 8 Fig 5 1 5 6 4 Reset Refer to paragraph 17 2 1 on page 24 for the reset procedure NC NO field wiring toggle switch white red terminal stri...

Страница 10: ...sets of temperature detectors must be wired in parallel The detectors act as one sensor and are connected to Zone 2 ref electrical diagram on page 29 End of line resistor REOL The last detector that...

Страница 11: ...status ShieldControl should indicate a fire in Zone 2 To perform the test proceed as follows Observe the functional testing instructions as described in paragraph 4 4 Functionally test all heat detect...

Страница 12: ...t of the tool Push the flange completely through the hole in the duct and insert the split washer by rotating it into the inside of the duct Gently pull the flange back through the hole with the inser...

Страница 13: ...having local jurisdiction Cleaning intervals differ per situation and regular checks need to be performed to set the cleaning interval for your specific situation To clean and test the spark detectors...

Страница 14: ...mount the smoke detector proceed as follows Drill a hole 51 mm 2 in in the duct at the intended mounting position Determine the correct tube length according to the table below Fig 8 2 Remove the end...

Страница 15: ...the supplied self tapping screws The arrow on the mounting bracket must correspond with the airflow direction through the duct Fig 8 4 Post installation checks Check that all screws are tightened Che...

Страница 16: ...LEDs extinguishes at the same time Place the cap back on the test opening 8 5 Maintenance The sensor wil become polluted over time When the sensor is 75 contaminated it must be replaced This is indic...

Страница 17: ...ed locally connection wire 5 x 20 AWG cable Wiring Connect the sliding valves to the system control panel SCP in accordance with the electrical diagram on page 29 Connect the reed contacts to the syst...

Страница 18: ...er the fire alarm Post installation checks Check electrical connections Check pneumatic connections Check bolts and nuts for correct tightening 9 5 Functional test The sliding valves can be tested man...

Страница 19: ...main compressed air line between pressure reducer and filter unit It is recommended to mount the valve on the filter housing Mount the solenoid valve at an appropriate position 10 3 Electrical connect...

Страница 20: ...lation position of FlameShield must be as follows Fig 11 1 A Filter cartridge B Junction box C Framework MDB D Mounting bracket FlameShield E FlameShield module Fig 11 1 To install the FlameShield mod...

Страница 21: ...A true functional check can be done by replacing the FlameShield module with the detonation simulator supplied and create a fire condition e g by removing one of the spark detectors After fire alarm t...

Страница 22: ...in RUN mode 6 Test the detectors and system control panel SCP as instructed to make sure that the system is reacting as expected and required 7 Reset the panel detectors and system control panel SCP...

Страница 23: ...functionally tested through exposure to daylight and the signal being monitored by ShieldControl Check OK 1 Is the smoke detector placed in the filter outlet duct 2 Is the mounting bracket correctly i...

Страница 24: ...sed 3 Is the solenoid functionally tested after a fire test alarm in the complete system set up Check OK 1 Are FlameShield modules undamaged 2 Is the correct number of FlameShield modules being instal...

Страница 25: ...s Reset alarm condition Determine cause e g fire and only push SYSTEM RESET after cause has been settled Panel will go to normal and display will show SYSTEM OK Program switch in RUN This action will...

Страница 26: ...maintenance procedure on spark detectors ref paragraph 7 5 Follow maintenance procedure on smoke detector ref paragraph 8 5 Disconnect the ShieldControl panel Replace the FlameShield module s Perform...

Страница 27: ...d After the life of the product dispose it of in accordance with federal state or local regulations activated FlameShield generators can be disposed of as non hazardous waste non activated FlameShield...

Страница 28: ...in a particular environment and to perform a specific task The entire installation must comply with the relevant directives and standards The assembly instructions given by the manufacturer as well as...

Страница 29: ...MDB 8 V MDB 8 H MDB 10 1x FS 200 1x FS 200 1x FS 500 1x FS 500 1x FS 500 MDB 4 MDB 12 MDB 12 V MDB 12 H MDB 16 MDB 16 H MDB 16 V 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 MDB 20 MDB...

Страница 30: ...SHIELD fire safety solutions 5k1 ELECTRICAL DIAGRAM 29 Electrical diagram 900010G0026 0 22 05 2014...

Страница 31: ......

Страница 32: ...www plymovent com 0507347110 160114 B SHIELD 5k1 EN...

Отзывы: