background image

0507347110/160114/B SHIELD fire safety solutions (5k1)

| INSTALLATION | EN - 22

13.1 ShieldControl

  

13.2 Heat detector set(s) 

13.3 Spark detector set

 

13.4 Smoke detector  

13.5 Manual call point and fire alarm sounder 

13.6 Sliding valves  

13

COMMISSIONING CHECKLIST

#

Check

OK

1.

Is the ShieldControl panel connected to a clean 
electrical group or a group not subject to regular 
power failures by other equipment?

2.

Is the panel placed in an environment without 
excessive dust in line with IP 30 or otherwise 
placed in a cabinet?

3.

Are all cables checked for correct connection in 
accordance with the electrical diagram? 

4.

Are the EOL resistors removed from the 
terminals that are in use and placed in the 
connected equipment?

5.

Are the cables well guided and fixed?

6.

Is a shielded cable being used for all detectors 
as well as the manual call point?

7.

Is the ShieldControl 5k1 switched to 

RUN

 mode?

8.

No fault signals on the ShieldControl panels?

#

Check

OK

1.

Are the heat detectors placed on top inside the 
filter housing and in the hopper just above the 
dustbin? 

2.

Number of heat detector sets = number of 
hoppers?

3.

Are the heat detectors wired in parallel and 
connected to Zone 2 of ShieldControl?

4.

Is an EOL resistor of 5k1 placed in the last heat 
detector?

5.

Is each heat detector being functionally tested 
by gently heating it with a heat gun or heat lamp 
and alarm signal being monitored  by 
ShieldControl?

#

Check

OK

1.

Are the spark detectors placed face to face in the 
filter outlet duct?

2.

Ensure that the spark detector is not mounted 
on the bottom of the duct. 

3.

Are the spark detectors shielded against any 
light and holes sealed with metal foil? Do not use 
duct tape since this may let through infrared 
light. 

4.

Are the spark detectors wired in parallel and 
connected to Zone 1 of ShieldControl?

5.

Is the last spark detector in the circuit provided 
with REOL of 5k1 in line with ShieldControl 5k1?

6.

Is the earth connection properly made?

7.

Are the lenses clean?

8.

Are the spark detectors being functionally tested 
through exposure to daylight and the signal 
being monitored by ShieldControl?

#

Check

OK

1.

Is the smoke detector placed in the filter outlet 
duct?

2.

Is the mounting bracket correctly installed in 
relation to the airflow? 

3.

Is the smoke detector connected to Zone 3 of 
ShieldControl? 

4.

Is the smoke detector being functionally tested 
by test spray? Is the signal being monitored by 
ShieldControl?

#

Check

OK

1.

Are the manual call points marked or placed 
close to the ShieldControl panel in order to avoid 
confusion with the general manual alarm boxes 
of the building?

2.

Is the REOL that was placed in the manual call 
point in line with the ShieldControl 5k1? 

3.

Are the fire alarm sounders placed close to the 
ShieldControl panel and fitted with the correct 
EOL resistor 5k1? 

4.

Is the sounder set to your local tone?

5.

Is sound level set to the maximum?

6.

Is the manual call point being functionally tested 
and monitored by the ShieldControl?

7.

Is the fire alarm sounder being tested and 
activated by ShieldControl?

#

Check

OK

1.

Can the ductwork carry the weight of the sliding 
valves? If not, make sure the duct is properly 
supported. 

2.

Are the sliding valves mounted straight and 
tension-free in the duct? Tension on the housing 
results in inadequate sealing and noise by 
airflow.

3.

Are the sliding valves pneumatically and 
electrically wired? 

4.

Are the reed contacts of the sliding valves 
connected to the system control panel SCP?

5.

Are sliding valves mounted indoors? If not, are 
they adequately protected against precipitation, 
such as rain and snow? 

6.

Is the compressed air pressure for the sliding 
valves 4-5 bar and the compressed air dry and 
oil-free? 

7.

Do the sliding valves close in 4-5 seconds? If 
not, reduce or increase pressure.

8.

Are the pneumatic and electrical wiring guided 
away from potential fire places like duct and 
filter?

9.

Make sure that the compressed air feed of the 
sliding valves is an independent line and not via 
the compressed air for the cleaning of the filter.

10.

Are the sliding valves functionally tested after a 
fire test alarm in the complete system set up?

11.

Do the sliding valves close when filter system is 
shut down and open at filter start up?

Содержание Shield 5k1

Страница 1: ...www plymovent com EN Fire safety solutions EN Installation and user manual shield 5k1...

Страница 2: ...general convenience of our clients It has been based on general data pertaining to construction material properties and working methods known to us at the time of issue of the document and is therefo...

Страница 3: ...B ranging from MDB 4 to MDB 48 other sizes on request central fan type SIF system control panel SCP round ductwork of the appropriate diameter 1 3 Functional description of SHIELD fire safety solution...

Страница 4: ...after activation thus preventing re ignition The amount of aerosol is proportional to the filter volume and can be easily adapted by adding generators The system control panel SCP M controls the filte...

Страница 5: ...cifications given in this installation manual must not be altered Modifications Modification of parts of the product is not allowed Product combinations Since the products are used in combination with...

Страница 6: ...es off fan motor is switched off release of compressed air through solenoid valve After a delay of 5 seconds sliding valves close release of aerosol by FlameShield generators during 60 seconds After a...

Страница 7: ...nect the FlameShield module s Make sure the panel is in RUN mode 5 1 Product description and operation ShieldControl 5k1 is a fire detection panel1 with a separate manual call point It has three detec...

Страница 8: ...the mains in accordance with the electrical diagram on page 29 5 5 Maintenance The ShieldControl panel itself does not require specific maintenance except for cleaning Do not use solvents or detergent...

Страница 9: ...10 160114 B SHIELD fire safety solutions 5k1 INSTALLATION EN 8 Fig 5 1 5 6 4 Reset Refer to paragraph 17 2 1 on page 24 for the reset procedure NC NO field wiring toggle switch white red terminal stri...

Страница 10: ...sets of temperature detectors must be wired in parallel The detectors act as one sensor and are connected to Zone 2 ref electrical diagram on page 29 End of line resistor REOL The last detector that...

Страница 11: ...status ShieldControl should indicate a fire in Zone 2 To perform the test proceed as follows Observe the functional testing instructions as described in paragraph 4 4 Functionally test all heat detect...

Страница 12: ...t of the tool Push the flange completely through the hole in the duct and insert the split washer by rotating it into the inside of the duct Gently pull the flange back through the hole with the inser...

Страница 13: ...having local jurisdiction Cleaning intervals differ per situation and regular checks need to be performed to set the cleaning interval for your specific situation To clean and test the spark detectors...

Страница 14: ...mount the smoke detector proceed as follows Drill a hole 51 mm 2 in in the duct at the intended mounting position Determine the correct tube length according to the table below Fig 8 2 Remove the end...

Страница 15: ...the supplied self tapping screws The arrow on the mounting bracket must correspond with the airflow direction through the duct Fig 8 4 Post installation checks Check that all screws are tightened Che...

Страница 16: ...LEDs extinguishes at the same time Place the cap back on the test opening 8 5 Maintenance The sensor wil become polluted over time When the sensor is 75 contaminated it must be replaced This is indic...

Страница 17: ...ed locally connection wire 5 x 20 AWG cable Wiring Connect the sliding valves to the system control panel SCP in accordance with the electrical diagram on page 29 Connect the reed contacts to the syst...

Страница 18: ...er the fire alarm Post installation checks Check electrical connections Check pneumatic connections Check bolts and nuts for correct tightening 9 5 Functional test The sliding valves can be tested man...

Страница 19: ...main compressed air line between pressure reducer and filter unit It is recommended to mount the valve on the filter housing Mount the solenoid valve at an appropriate position 10 3 Electrical connect...

Страница 20: ...lation position of FlameShield must be as follows Fig 11 1 A Filter cartridge B Junction box C Framework MDB D Mounting bracket FlameShield E FlameShield module Fig 11 1 To install the FlameShield mod...

Страница 21: ...A true functional check can be done by replacing the FlameShield module with the detonation simulator supplied and create a fire condition e g by removing one of the spark detectors After fire alarm t...

Страница 22: ...in RUN mode 6 Test the detectors and system control panel SCP as instructed to make sure that the system is reacting as expected and required 7 Reset the panel detectors and system control panel SCP...

Страница 23: ...functionally tested through exposure to daylight and the signal being monitored by ShieldControl Check OK 1 Is the smoke detector placed in the filter outlet duct 2 Is the mounting bracket correctly i...

Страница 24: ...sed 3 Is the solenoid functionally tested after a fire test alarm in the complete system set up Check OK 1 Are FlameShield modules undamaged 2 Is the correct number of FlameShield modules being instal...

Страница 25: ...s Reset alarm condition Determine cause e g fire and only push SYSTEM RESET after cause has been settled Panel will go to normal and display will show SYSTEM OK Program switch in RUN This action will...

Страница 26: ...maintenance procedure on spark detectors ref paragraph 7 5 Follow maintenance procedure on smoke detector ref paragraph 8 5 Disconnect the ShieldControl panel Replace the FlameShield module s Perform...

Страница 27: ...d After the life of the product dispose it of in accordance with federal state or local regulations activated FlameShield generators can be disposed of as non hazardous waste non activated FlameShield...

Страница 28: ...in a particular environment and to perform a specific task The entire installation must comply with the relevant directives and standards The assembly instructions given by the manufacturer as well as...

Страница 29: ...MDB 8 V MDB 8 H MDB 10 1x FS 200 1x FS 200 1x FS 500 1x FS 500 1x FS 500 MDB 4 MDB 12 MDB 12 V MDB 12 H MDB 16 MDB 16 H MDB 16 V 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 MDB 20 MDB...

Страница 30: ...SHIELD fire safety solutions 5k1 ELECTRICAL DIAGRAM 29 Electrical diagram 900010G0026 0 22 05 2014...

Страница 31: ......

Страница 32: ...www plymovent com 0507347110 160114 B SHIELD 5k1 EN...

Отзывы: