background image

0507347110/160114/B SHIELD fire safety solutions (5k1)

| INSTALLATION | EN - 11

7.1

Product description and operation

Set of two infrared spark detectors. The spark detectors are 
sensitive to the near IR light between 0.4 to 1.1 microns 
wavelength.
When glowing particulate from the burning filter enters the field 
of view of the detector, the detector responds by sending an 
alarm to the ShieldControl fire detection panel. 

7.2

Installation 

Location:

- in filter outlet duct
- face to face (180° apart from each other) in the same vertical 

plane 

- min. 2,5x duct diameter from bend or branch

The spark detectors can be mounted without having access to 
the inside of the duct. In this case you will need the supplied 
insertion tool. 

In case of a new or disconnected duct 

allowing access to the 

inside

, proceed as follows. 

Fig. 7.1

Make a hole Ø 38 mm (1.5 in.) in the duct using the supplied 
hole saw. 

Mount the flange (D) in the duct using the split washer (C), 
washer (B) and nut (A). 

Tighten washer and nut on the flange. 

Fig. 7.1

In case of 

no access to the inside

 of the duct, proceed as 

follows. 

Fig. 7.2

Make a hole Ø 38 mm (1.5 in.) in the duct using the supplied 
hole saw. 

Slip nut (B), washer (C) and split washer (D) on the insertion 
tool (A) until the tool fits tightly on the flange (E). The nut 

and washer should be loose on the shaft of the tool. 

Push the flange completely through the hole in the duct and 
insert the split washer by rotating it into the inside of the 
duct. 

Gently pull the flange back through the hole with the 
insertion tool so it rests against the split washer inside the 
duct. 

Tighten washer and nut on the flange. 

Remove the insertion tool by loosening the wing nut and 
pulling straight back and twisting if required. 

Fig. 7.2

Fig. 7.3

Insert the spark detector lens (A) into the flange (C). 

Fasten the detector using the supplied fixation screw (B). 

Follow the same procedure for the second spark detector. 

Fig. 7.3

 

7.3

Electrical connection -Zone 1-

To be sourced locally:
- connection wire: 5 x 20 AWG shielded cable

Wiring

Fig. 7.4
The spark detectors (A) must be wired in parallel in the supplied 
junction box (B). Each set consists of one spark detector with 
EOL resistor (“EOL”) and one without (“no EOL”), which is 
marked on the spark detector housing. 

Fig. 7.4

7

SPARK DETECTOR SET

Scope of supply:

- spark detector*) + 

fixation screw

- spark detector REOL*) 

**)  + fixation screw

- junction box 
- installation set (hole saw 

Ø 38 mm + insertion 
tool)

*) with alarm resistor (RAL) 

**) with end of line resistor 

(REOL)

WARNING

To avoid dirtying the lens, never mount the spark 
detectors on the bottom of the duct. 

Installation is easier if the inside of the duct is 
accessible.

WARNING

To prevent false alarms, ensure that no light can get 
between the flange and the duct. Seal any holes with 
metal foil. Do 

not

 use duct tape since this may let 

through infrared light. 

Содержание Shield 5k1

Страница 1: ...www plymovent com EN Fire safety solutions EN Installation and user manual shield 5k1...

Страница 2: ...general convenience of our clients It has been based on general data pertaining to construction material properties and working methods known to us at the time of issue of the document and is therefo...

Страница 3: ...B ranging from MDB 4 to MDB 48 other sizes on request central fan type SIF system control panel SCP round ductwork of the appropriate diameter 1 3 Functional description of SHIELD fire safety solution...

Страница 4: ...after activation thus preventing re ignition The amount of aerosol is proportional to the filter volume and can be easily adapted by adding generators The system control panel SCP M controls the filte...

Страница 5: ...cifications given in this installation manual must not be altered Modifications Modification of parts of the product is not allowed Product combinations Since the products are used in combination with...

Страница 6: ...es off fan motor is switched off release of compressed air through solenoid valve After a delay of 5 seconds sliding valves close release of aerosol by FlameShield generators during 60 seconds After a...

Страница 7: ...nect the FlameShield module s Make sure the panel is in RUN mode 5 1 Product description and operation ShieldControl 5k1 is a fire detection panel1 with a separate manual call point It has three detec...

Страница 8: ...the mains in accordance with the electrical diagram on page 29 5 5 Maintenance The ShieldControl panel itself does not require specific maintenance except for cleaning Do not use solvents or detergent...

Страница 9: ...10 160114 B SHIELD fire safety solutions 5k1 INSTALLATION EN 8 Fig 5 1 5 6 4 Reset Refer to paragraph 17 2 1 on page 24 for the reset procedure NC NO field wiring toggle switch white red terminal stri...

Страница 10: ...sets of temperature detectors must be wired in parallel The detectors act as one sensor and are connected to Zone 2 ref electrical diagram on page 29 End of line resistor REOL The last detector that...

Страница 11: ...status ShieldControl should indicate a fire in Zone 2 To perform the test proceed as follows Observe the functional testing instructions as described in paragraph 4 4 Functionally test all heat detect...

Страница 12: ...t of the tool Push the flange completely through the hole in the duct and insert the split washer by rotating it into the inside of the duct Gently pull the flange back through the hole with the inser...

Страница 13: ...having local jurisdiction Cleaning intervals differ per situation and regular checks need to be performed to set the cleaning interval for your specific situation To clean and test the spark detectors...

Страница 14: ...mount the smoke detector proceed as follows Drill a hole 51 mm 2 in in the duct at the intended mounting position Determine the correct tube length according to the table below Fig 8 2 Remove the end...

Страница 15: ...the supplied self tapping screws The arrow on the mounting bracket must correspond with the airflow direction through the duct Fig 8 4 Post installation checks Check that all screws are tightened Che...

Страница 16: ...LEDs extinguishes at the same time Place the cap back on the test opening 8 5 Maintenance The sensor wil become polluted over time When the sensor is 75 contaminated it must be replaced This is indic...

Страница 17: ...ed locally connection wire 5 x 20 AWG cable Wiring Connect the sliding valves to the system control panel SCP in accordance with the electrical diagram on page 29 Connect the reed contacts to the syst...

Страница 18: ...er the fire alarm Post installation checks Check electrical connections Check pneumatic connections Check bolts and nuts for correct tightening 9 5 Functional test The sliding valves can be tested man...

Страница 19: ...main compressed air line between pressure reducer and filter unit It is recommended to mount the valve on the filter housing Mount the solenoid valve at an appropriate position 10 3 Electrical connect...

Страница 20: ...lation position of FlameShield must be as follows Fig 11 1 A Filter cartridge B Junction box C Framework MDB D Mounting bracket FlameShield E FlameShield module Fig 11 1 To install the FlameShield mod...

Страница 21: ...A true functional check can be done by replacing the FlameShield module with the detonation simulator supplied and create a fire condition e g by removing one of the spark detectors After fire alarm t...

Страница 22: ...in RUN mode 6 Test the detectors and system control panel SCP as instructed to make sure that the system is reacting as expected and required 7 Reset the panel detectors and system control panel SCP...

Страница 23: ...functionally tested through exposure to daylight and the signal being monitored by ShieldControl Check OK 1 Is the smoke detector placed in the filter outlet duct 2 Is the mounting bracket correctly i...

Страница 24: ...sed 3 Is the solenoid functionally tested after a fire test alarm in the complete system set up Check OK 1 Are FlameShield modules undamaged 2 Is the correct number of FlameShield modules being instal...

Страница 25: ...s Reset alarm condition Determine cause e g fire and only push SYSTEM RESET after cause has been settled Panel will go to normal and display will show SYSTEM OK Program switch in RUN This action will...

Страница 26: ...maintenance procedure on spark detectors ref paragraph 7 5 Follow maintenance procedure on smoke detector ref paragraph 8 5 Disconnect the ShieldControl panel Replace the FlameShield module s Perform...

Страница 27: ...d After the life of the product dispose it of in accordance with federal state or local regulations activated FlameShield generators can be disposed of as non hazardous waste non activated FlameShield...

Страница 28: ...in a particular environment and to perform a specific task The entire installation must comply with the relevant directives and standards The assembly instructions given by the manufacturer as well as...

Страница 29: ...MDB 8 V MDB 8 H MDB 10 1x FS 200 1x FS 200 1x FS 500 1x FS 500 1x FS 500 MDB 4 MDB 12 MDB 12 V MDB 12 H MDB 16 MDB 16 H MDB 16 V 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 MDB 20 MDB...

Страница 30: ...SHIELD fire safety solutions 5k1 ELECTRICAL DIAGRAM 29 Electrical diagram 900010G0026 0 22 05 2014...

Страница 31: ......

Страница 32: ...www plymovent com 0507347110 160114 B SHIELD 5k1 EN...

Отзывы: