background image

0507347110/160114/B SHIELD fire safety solutions (5k1)

| GENERAL | EN - 3

suppression system. In case of alarm, a 

fire alarm sounder

 

(K) will go off. Operational reliability in the event of a power 
failure is assured by a battery pack. To secure the overall 
functionality, ShieldControl monitors open or short circuit of 
wiring loops of detectors and the suppression system. 

When a fire is detected, the system can be activated manually 
at the 

manual call point

 (L). 

Automatic detection is triggered by heat, sparks or smoke. The 
filter is fitted with 

heat detectors

 (H) above the dustbin and at 

the top of the filter. 

Spark detectors

 (C) are placed near the 

filter outlet and in the duct after the filter. A 

smoke detector

 

(D), suitable for air ducts, is placed in the duct after the filter. 

The inlet and outlet duct of the filter are fitted with pneumatic 

sliding valves

 (B). If there is a fire, the valves close and cut off 

the oxygen, thereby choking it. This constrains the risk of 
escalation. When the extraction system is switched off, the 
valves are closed as well to create a safe situation. The valves 
have reed contacts to monitor the closing function; the filter 
system software runs a periodic check.

The filter is fitted with one or more 

FlameShield

 (I) aerosol fire 

extinguishing generators. The generators are placed directly in 
the filter housing and do not require plumbing. FlameShield 
requires no maintenance and has a service life of 10 years. If 
there is a fire, FlameShield is activated by the fire detection 
panel after the sliding valves have closed. FlameShield self 
activates at 300°C (572°F). Fire suppression is rapidly achieved 
through interference between the aerosol and the flames’ free 
radicals, terminating propagation of the fire. The aerosol 
remains active during 30 minutes after activation, thus 
preventing re-ignition. The amount of aerosol is proportional to 
the filter volume and can be easily adapted by adding 
generators. 

The 

system control panel SCP 

(M) controls the filter and fan 

operation. If there is a fire, it will get a signal from the fire 
detection panel and close the sliding valves, stop the fan and 
shut off the supply of compressed air. The filter compressed air 
connection is fitted with a 

solenoid valve

 (G) that will allow the 

compressed air tanks to depressurize outside of the filter and 
prevent any fresh oxygen from reaching the fire.

Fig. 1.1

1.4

System maintenance

The entire system including the ShieldControl panel must be 
tested periodically in accordance with the national fire 
protection association requirements or the authorities having 
local jurisdiction.

The maintenance and testing procedure of the separate 
components is described in the relevant chapter. 
 

General instructions

If maintenance is required to any detector, the filter system or 
peripheral equipment, proceed as follows.

Isolate the FlameShield module(s).

   

After maintenance:

Follow commissioning instructions.

Make sure switch of ShieldControl panel is in 

RUN

 mode.

   

   

Refer to the available application data sheet about 
SHIELD fire safety solutions for more detailed 
information. 

A

E

F

D

H

C

B

J

G

L

K

I

M

ATTENTION!
Prior to performing any test: 

- notify the local fire brigade that you will be testing 

the fire safety system, especially when the 
installation is connected to the brigade control room

- inform all other parties involved, e.g. staff, fire 

safety coordinator, alarm monitoring department/
company

Testing the system may lead to acoustic fire alarm 
without activating the fire suppression method. 

WARNING!

Not isolating the FlameShield module(s) will cause 
accidental activation of the fire suppression method.

WARNING!

Not having the ShieldControl panel in 

RUN

 mode will 

disable automatic fire detection and extinguishing 
when the system is in operation. 

Содержание Shield 5k1

Страница 1: ...www plymovent com EN Fire safety solutions EN Installation and user manual shield 5k1...

Страница 2: ...general convenience of our clients It has been based on general data pertaining to construction material properties and working methods known to us at the time of issue of the document and is therefo...

Страница 3: ...B ranging from MDB 4 to MDB 48 other sizes on request central fan type SIF system control panel SCP round ductwork of the appropriate diameter 1 3 Functional description of SHIELD fire safety solution...

Страница 4: ...after activation thus preventing re ignition The amount of aerosol is proportional to the filter volume and can be easily adapted by adding generators The system control panel SCP M controls the filte...

Страница 5: ...cifications given in this installation manual must not be altered Modifications Modification of parts of the product is not allowed Product combinations Since the products are used in combination with...

Страница 6: ...es off fan motor is switched off release of compressed air through solenoid valve After a delay of 5 seconds sliding valves close release of aerosol by FlameShield generators during 60 seconds After a...

Страница 7: ...nect the FlameShield module s Make sure the panel is in RUN mode 5 1 Product description and operation ShieldControl 5k1 is a fire detection panel1 with a separate manual call point It has three detec...

Страница 8: ...the mains in accordance with the electrical diagram on page 29 5 5 Maintenance The ShieldControl panel itself does not require specific maintenance except for cleaning Do not use solvents or detergent...

Страница 9: ...10 160114 B SHIELD fire safety solutions 5k1 INSTALLATION EN 8 Fig 5 1 5 6 4 Reset Refer to paragraph 17 2 1 on page 24 for the reset procedure NC NO field wiring toggle switch white red terminal stri...

Страница 10: ...sets of temperature detectors must be wired in parallel The detectors act as one sensor and are connected to Zone 2 ref electrical diagram on page 29 End of line resistor REOL The last detector that...

Страница 11: ...status ShieldControl should indicate a fire in Zone 2 To perform the test proceed as follows Observe the functional testing instructions as described in paragraph 4 4 Functionally test all heat detect...

Страница 12: ...t of the tool Push the flange completely through the hole in the duct and insert the split washer by rotating it into the inside of the duct Gently pull the flange back through the hole with the inser...

Страница 13: ...having local jurisdiction Cleaning intervals differ per situation and regular checks need to be performed to set the cleaning interval for your specific situation To clean and test the spark detectors...

Страница 14: ...mount the smoke detector proceed as follows Drill a hole 51 mm 2 in in the duct at the intended mounting position Determine the correct tube length according to the table below Fig 8 2 Remove the end...

Страница 15: ...the supplied self tapping screws The arrow on the mounting bracket must correspond with the airflow direction through the duct Fig 8 4 Post installation checks Check that all screws are tightened Che...

Страница 16: ...LEDs extinguishes at the same time Place the cap back on the test opening 8 5 Maintenance The sensor wil become polluted over time When the sensor is 75 contaminated it must be replaced This is indic...

Страница 17: ...ed locally connection wire 5 x 20 AWG cable Wiring Connect the sliding valves to the system control panel SCP in accordance with the electrical diagram on page 29 Connect the reed contacts to the syst...

Страница 18: ...er the fire alarm Post installation checks Check electrical connections Check pneumatic connections Check bolts and nuts for correct tightening 9 5 Functional test The sliding valves can be tested man...

Страница 19: ...main compressed air line between pressure reducer and filter unit It is recommended to mount the valve on the filter housing Mount the solenoid valve at an appropriate position 10 3 Electrical connect...

Страница 20: ...lation position of FlameShield must be as follows Fig 11 1 A Filter cartridge B Junction box C Framework MDB D Mounting bracket FlameShield E FlameShield module Fig 11 1 To install the FlameShield mod...

Страница 21: ...A true functional check can be done by replacing the FlameShield module with the detonation simulator supplied and create a fire condition e g by removing one of the spark detectors After fire alarm t...

Страница 22: ...in RUN mode 6 Test the detectors and system control panel SCP as instructed to make sure that the system is reacting as expected and required 7 Reset the panel detectors and system control panel SCP...

Страница 23: ...functionally tested through exposure to daylight and the signal being monitored by ShieldControl Check OK 1 Is the smoke detector placed in the filter outlet duct 2 Is the mounting bracket correctly i...

Страница 24: ...sed 3 Is the solenoid functionally tested after a fire test alarm in the complete system set up Check OK 1 Are FlameShield modules undamaged 2 Is the correct number of FlameShield modules being instal...

Страница 25: ...s Reset alarm condition Determine cause e g fire and only push SYSTEM RESET after cause has been settled Panel will go to normal and display will show SYSTEM OK Program switch in RUN This action will...

Страница 26: ...maintenance procedure on spark detectors ref paragraph 7 5 Follow maintenance procedure on smoke detector ref paragraph 8 5 Disconnect the ShieldControl panel Replace the FlameShield module s Perform...

Страница 27: ...d After the life of the product dispose it of in accordance with federal state or local regulations activated FlameShield generators can be disposed of as non hazardous waste non activated FlameShield...

Страница 28: ...in a particular environment and to perform a specific task The entire installation must comply with the relevant directives and standards The assembly instructions given by the manufacturer as well as...

Страница 29: ...MDB 8 V MDB 8 H MDB 10 1x FS 200 1x FS 200 1x FS 500 1x FS 500 1x FS 500 MDB 4 MDB 12 MDB 12 V MDB 12 H MDB 16 MDB 16 H MDB 16 V 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 MDB 20 MDB...

Страница 30: ...SHIELD fire safety solutions 5k1 ELECTRICAL DIAGRAM 29 Electrical diagram 900010G0026 0 22 05 2014...

Страница 31: ......

Страница 32: ...www plymovent com 0507347110 160114 B SHIELD 5k1 EN...

Отзывы: