background image

0507347110/160114/B SHIELD fire safety solutions (5k1)

| INSTALLATION | EN - 16

9.1

Product description and operation

Double activated pneumatic sliding valve with 5/2 solenoid, to 
be installed by two pieces (before and after filter system).
When the filter system is in operation the valves are open. In 
case of an alarm or power failure or when the fan is switched off 
the valves are closed. Correct closing of the valves is monitored 
by the reed contact.
In case of fire, the sliding valves close automatically, operated 
by pneumatic cylinders. In sequence to a lack of oxygen the fire
is supposed to choke. This will also minimize risk of escalation 
or spreading of smoke. 

9.2

Installation

Location:

- 1st sliding valve: in filter inlet duct
- 2nd sliding valve: before or after spark and smoke sensors in 

filter outlet duct

- to be mounted in vertical position
 

It is strongly recommended that the sliding valves be installed 
indoors. If they are installed outside, however, ensure that they 
are protected from rain and snow. Avoid installation where 
compressed air can cool down below its dew point to prevent 
damage to the pneumatics.
 

The sliding valves can be mounted:
- during installation of a new ductwork
- in an existing duct
  

To mount the sliding valves, proceed as follows. 

Fig. 9.1

In case of installation in an existing duct: cut away a piece 
of the existing duct as indicated in the table below.  

Slide a connection flange (B) into both duct ends (A). 

Place the sliding valve (D) in between and fasten it using the 
quick release clamps (C). 

Fasten the connection flanges using self-tapping screws.

 

Fig. 9.1

9.3

Electrical connection

To be sourced locally:
- connection wire: 5 x 20 AWG cable

Wiring

Connect the sliding valves to the system control panel SCP 
in accordance with the electrical diagram on page 29. 

Connect the reed contacts to the system control panel SCP 
in accordance with the electrical diagram on page 29. 

9.4

Compressed air connection 

Connect the sliding valves to a compressed air source. 

9

SLIDING VALVES

Scope of supply:

- sliding valve incl. 5/2 

solenoid valve, reed 
contact, junction box and 
cable gland (3)

- connection flange (2)
- quick release clamp (2)

WARNING

Do 

not

 mount the sliding valves in horizontal position 

to avoid malfunction of the valves. 

ATTENTION

Allow sufficient space above the duct for the sliding 
valves to fully open;
- SV-10: + 14 in.
- SV-12: + 16 in.
- SV-16: + 20 in.
- SV-20: + 26 in.
- SV-24: + 32 in.

WARNING

Ensure that the ductwork can carry the weight of the 
sliding valves. It is recommended to use duct 
supports, especially for sliding valves type SV-16/20/
24.

ATTENTION

The sliding valves are equipped with eye bolts for 
lifting purposes during installation. The eye bolts 

cannot

 be used to mount the sliding valves 

permanently. 

Type of sliding valve

Duct length to be removed

SV-10

11.6 in.  +/- 0.4 in.

SV-12

11.6 in.  +/- 0.4 in.

SV-16

11.6 in.  +/- 0.4 in.

SV-20

15.0 in.  +/- 0.4 in.

SV-24

15.0 in.  +/- 0.4 in.

WARNING

The valves must be mounted straight and without 
tension on the shell/housing  to guarantee airtightness 
and to avoid noise by airflow. 

WARNING

If applicable, take precautions to ensure that people 
are not able to get into the blade's arc of movement.

WARNING

Keep wiring away from places that can become hot 
due to fire. Do not use filter or duct as support for 
electrical wires.

Compressed air specifications

Compressed air connection

6 mm

Recommended operational pressure 

5 bar (max. 9 bar)

Quality

dry and oil-free according to 

ISO 8573-3 class 6

B

A

B

A

C

D

C

Содержание Shield 5k1

Страница 1: ...www plymovent com EN Fire safety solutions EN Installation and user manual shield 5k1...

Страница 2: ...general convenience of our clients It has been based on general data pertaining to construction material properties and working methods known to us at the time of issue of the document and is therefo...

Страница 3: ...B ranging from MDB 4 to MDB 48 other sizes on request central fan type SIF system control panel SCP round ductwork of the appropriate diameter 1 3 Functional description of SHIELD fire safety solution...

Страница 4: ...after activation thus preventing re ignition The amount of aerosol is proportional to the filter volume and can be easily adapted by adding generators The system control panel SCP M controls the filte...

Страница 5: ...cifications given in this installation manual must not be altered Modifications Modification of parts of the product is not allowed Product combinations Since the products are used in combination with...

Страница 6: ...es off fan motor is switched off release of compressed air through solenoid valve After a delay of 5 seconds sliding valves close release of aerosol by FlameShield generators during 60 seconds After a...

Страница 7: ...nect the FlameShield module s Make sure the panel is in RUN mode 5 1 Product description and operation ShieldControl 5k1 is a fire detection panel1 with a separate manual call point It has three detec...

Страница 8: ...the mains in accordance with the electrical diagram on page 29 5 5 Maintenance The ShieldControl panel itself does not require specific maintenance except for cleaning Do not use solvents or detergent...

Страница 9: ...10 160114 B SHIELD fire safety solutions 5k1 INSTALLATION EN 8 Fig 5 1 5 6 4 Reset Refer to paragraph 17 2 1 on page 24 for the reset procedure NC NO field wiring toggle switch white red terminal stri...

Страница 10: ...sets of temperature detectors must be wired in parallel The detectors act as one sensor and are connected to Zone 2 ref electrical diagram on page 29 End of line resistor REOL The last detector that...

Страница 11: ...status ShieldControl should indicate a fire in Zone 2 To perform the test proceed as follows Observe the functional testing instructions as described in paragraph 4 4 Functionally test all heat detect...

Страница 12: ...t of the tool Push the flange completely through the hole in the duct and insert the split washer by rotating it into the inside of the duct Gently pull the flange back through the hole with the inser...

Страница 13: ...having local jurisdiction Cleaning intervals differ per situation and regular checks need to be performed to set the cleaning interval for your specific situation To clean and test the spark detectors...

Страница 14: ...mount the smoke detector proceed as follows Drill a hole 51 mm 2 in in the duct at the intended mounting position Determine the correct tube length according to the table below Fig 8 2 Remove the end...

Страница 15: ...the supplied self tapping screws The arrow on the mounting bracket must correspond with the airflow direction through the duct Fig 8 4 Post installation checks Check that all screws are tightened Che...

Страница 16: ...LEDs extinguishes at the same time Place the cap back on the test opening 8 5 Maintenance The sensor wil become polluted over time When the sensor is 75 contaminated it must be replaced This is indic...

Страница 17: ...ed locally connection wire 5 x 20 AWG cable Wiring Connect the sliding valves to the system control panel SCP in accordance with the electrical diagram on page 29 Connect the reed contacts to the syst...

Страница 18: ...er the fire alarm Post installation checks Check electrical connections Check pneumatic connections Check bolts and nuts for correct tightening 9 5 Functional test The sliding valves can be tested man...

Страница 19: ...main compressed air line between pressure reducer and filter unit It is recommended to mount the valve on the filter housing Mount the solenoid valve at an appropriate position 10 3 Electrical connect...

Страница 20: ...lation position of FlameShield must be as follows Fig 11 1 A Filter cartridge B Junction box C Framework MDB D Mounting bracket FlameShield E FlameShield module Fig 11 1 To install the FlameShield mod...

Страница 21: ...A true functional check can be done by replacing the FlameShield module with the detonation simulator supplied and create a fire condition e g by removing one of the spark detectors After fire alarm t...

Страница 22: ...in RUN mode 6 Test the detectors and system control panel SCP as instructed to make sure that the system is reacting as expected and required 7 Reset the panel detectors and system control panel SCP...

Страница 23: ...functionally tested through exposure to daylight and the signal being monitored by ShieldControl Check OK 1 Is the smoke detector placed in the filter outlet duct 2 Is the mounting bracket correctly i...

Страница 24: ...sed 3 Is the solenoid functionally tested after a fire test alarm in the complete system set up Check OK 1 Are FlameShield modules undamaged 2 Is the correct number of FlameShield modules being instal...

Страница 25: ...s Reset alarm condition Determine cause e g fire and only push SYSTEM RESET after cause has been settled Panel will go to normal and display will show SYSTEM OK Program switch in RUN This action will...

Страница 26: ...maintenance procedure on spark detectors ref paragraph 7 5 Follow maintenance procedure on smoke detector ref paragraph 8 5 Disconnect the ShieldControl panel Replace the FlameShield module s Perform...

Страница 27: ...d After the life of the product dispose it of in accordance with federal state or local regulations activated FlameShield generators can be disposed of as non hazardous waste non activated FlameShield...

Страница 28: ...in a particular environment and to perform a specific task The entire installation must comply with the relevant directives and standards The assembly instructions given by the manufacturer as well as...

Страница 29: ...MDB 8 V MDB 8 H MDB 10 1x FS 200 1x FS 200 1x FS 500 1x FS 500 1x FS 500 MDB 4 MDB 12 MDB 12 V MDB 12 H MDB 16 MDB 16 H MDB 16 V 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 MDB 20 MDB...

Страница 30: ...SHIELD fire safety solutions 5k1 ELECTRICAL DIAGRAM 29 Electrical diagram 900010G0026 0 22 05 2014...

Страница 31: ......

Страница 32: ...www plymovent com 0507347110 160114 B SHIELD 5k1 EN...

Отзывы: