47
ID
Class
Designation
(Possible) cause/effect
Rectification/action
Quit
29 Warning Address conflict
Touch remote control
2 or more touch remote controls with
identical address exist. The touch remote
control processes no inputs
Check address in
visualization.
No
30 Warning Manual mode
terminated
The manual mode of the object will be
terminated due to an error. The object
switches to the normal operating status.
The message must be
confirmed.
Yes
32 Error
Communication error
Frequency converter
ATV
The communication to the listed module has
been aborted. Functional units based on this
module are not operating
Check bus connection,
bus address, power
supply of the affected IO-
module.
no
33 Error
ATV malfunction
Frequency converter has malfunction.
Functional units based on this module are not
operating
Check wiring, power
supply and bus
connection.
no
34 Error
Communication error
Frequency converter
Power
The communication to the listed module has
been aborted. Functional units based on this
module are not operating
Check bus connection,
bus address, power
supply of the affected IO-
module.
no
35
Error
Power malfunction
Frequency converter has malfunction.
Functional units based on this module are not
operating
Check wiring, power
supply and bus
connection.
no
50 Info
Sensor failure
The sensor reports an (internal) error.
-
-
51 Info
Sensor measuring range
undercut
The sensor reports undercut values for the
measuring range.
-
-
52 Info
Sensor measuring range
exceeded
The sensor reports exceeded values for the
measuring range.
-
-
53 Info
Sensor break
The sensor reports sensor failure and is not
functional.
Check the wiring to the
sensor.
-
54 Info
Sensor short circuit
The sensor reports a short-circuit. The sensor
is not functional.
Check the wiring to the
sensor.
-
55 Info
Sensor plausibility check The sensor value is outside of the stated
-
-