10
WARNING
The wiring must comply with all applicable regulations. The type and position of the fused isolators
must also comply with regulations. For safety reasons, these must be clearly visible and installed
within operating distance of the machine. All machines must be earthed throughout.
IMPORTANT
Operating a machine with the wrong voltage or with excessive phase asymmetry represents incorrect
use, which is excluded from the PicoEnergy guarantee. If the phase asymmetry exceeds 2 % (voltage)
and 1 % (current), please contact your power supply utility immediately, before commissioning the
heat pump.
9.2.
Supply
Connect the supply of the machine to the internal terminal block according to the scheme shown
below. The cable routing occurs through the special holes as shown in the previous schemes.
APPROXIMATE section of cables and internal protection:
9.3.
Power supply connections
Get access to the terminal block inside the unit by
removing the frontplate of the case. Now insert the
cables to the inlets
1
at the backplate of the case
and connect it with the terminal block
2
. Use the
cable ducts as good as possible and cable ties or
similar to fix the wires on pipes or parts exept the
compressor or heat exchangers.
RuralECO 230V
RuralECO 400V
Supply compressor
Supply Interface
230V - 50 Hz
230V - 50 Hz
400V - 50 Hz
230V - 50 Hz
Compressor Cable
Interface Cable
3x 6 mm²
3x 1,5 mm²
5x 2,5 mm²
3x 1,5 mm²
Protections of compressor
Protections of Interface
1x C25
1x B13
3x C16
1x B13