INSTALLATION
SOLUTION 3 - Fig. 34:
• The stove is installed in the room to be heated with the heat
channelled in three directions. One fan propels heat to both front
and rear of the stove via the Ydevice and a length of flexible pipe
of diameter 7.5 cm. The output of the second fan is directed to
the rear only via a flexible pipe of diameter 7.5 cm and maximum
length 6 metres (fig 34).
For the example shown in fig 34 the vent at the end of the
single redirection should be permanently open.
SOLUTION 4 - Fig. 35:
• Extending the previous solution, with the stove installed in the
room to be heated and the heat directed as in SOLUTION 3, with
the outlet from one fan doubled using a second Y connector at
the rear as shown. Use 7.5 cm-diameter flexible pipe with a
maximum total length of 6 meters (fig 35).
For the example shown in fig 35, for the redirection to
function correctly and to avoid overheating, it is necessary
to use non-closable vents as shown. During operation the
vent closest to the stove should be partially open but never
closed to avoid overheating.
Ducting through walls or floors - Fig. 36 / 39
To ensure efficient ducted heat distribution:
1) lag the pipe with insulating material to limit heat loss and
ensure a sufficiently high air temperature;
2)
do not exceed the total maximum hose length of 4.5 m.
Below are some examples of how the hose can be installed in walls
or floors (for better performance, lag the hose with suitable
insulating material).
Hot air outlet vent radiation area (mm) - Fig. 40
A safety area must be ensured around the hot air outlet vent within
which there must be no flammable objects (furniture, carpets,
curtains, etc.) or heat sensitive materials (wood, plastic, etc.).
The diagram to the side shows the measurements for this safety
area, which includes 600 mm from the upper edge of the vent.
6 m
1 m
DT2030219-00
Fig. 34
R600
600
600
600
DT2030172-00
Fig. 40
DT2030169-00
DT2030168-00
DT2030171-00
DT2030170-00
Fig. 36
Fig. 37
Fig. 38
Fig. 39
hot air outlet vent
non-closable vent
5 m
1 m
0,5 m
0,5 m
DT2030220-00
Fig. 35
partially open vent
open vent