 13 

Specifications PM1030 V2 

Size:

   

 

 

142 x 100 mm 

Weight:

 

 

 

0.25 Kg 

Antenna:

   

 

Dual Band 2G & 3G 

3G & NEXT G Modem:

  Siemens 

Power: 

 

 

14.5V DC Plug pack must have approval 

Power Consumption:

  Standby: 0.05A 

                                        Transmitting: 0.60 A 

Power Reporting:  

Powered from 14.5V plug pack. 

DC-Loss   reported <11.8v 
DC-OK  

reported >12.8v 

Battery Low  

reported <11.6v 

Battery OK  reported >12.5v 

Backup Battery:

 

12V/1.2AH sealed lead acid battery (Powers unit for about 30 hours) 

Auxiliary Input:

   

TT, tamper input, (24Hr Zones)  

 

 

 

 

 

 

 

 

                                         State change detected every second 

Serial Interface:

   

Consult the relevant serial interface specifications 

Battery Low

 

Fail   

 

DCV<11.8 Report delay 10 minute 

Restore 

 

DCV>12.5 Immediate 

Communications Class:

 

As per compliance statement 

Size:

   

 

 

 

70 x 50 x 20 mm 

Power: 

 

 

 

10 – 15V DC 0.3A 

Power Consumption:

   

Standby: 0.12A 

Dialler Interface:

 

Accepts Contact ID (ADEMCO-685) 

 
Telephone Lead

Fail   

 

 

DCV< 4V for more than 18seconds 

Restore 

 

 

DCV > 5V for more than 8 seconds 

Interface Lead (Dialler): 

Fail   

            

 

DCV< 4V for more than 18seconds 

Restore 

 

 

DCV > 5V for more than 8 seconds 

Response Dialler Interface: 

< 10 sec typical (seizing line to receiving ACK) 

< 50 sec absolute maximum 

Serial Interface:

   

 

< 2 sec typical (dispatch to  

receiving ACK) 

                                                   < 50 sec absolute maximum 

RDCCO_2143_E_IN 

PM1030 Manual March 2019 v2.2  

Содержание PM1030

Страница 1: ...PERMACONN PM1030 Includes DI300 Installation Manual RDCCO Pty Ltd Unit 3 9 11 Stubbs Street Rydalmere NSW 2116 Telephone 02 9352 1777 Web www permaconn com...

Страница 2: ...conn PM1030 7 DI300 Powered by Panel PM1030 Powered Independent Supply 7 PM1030 V2 and DI300 Powered by Panel Transmission Delay Times 8 LED Status Indicators PM1030 9 LED Status Indicators DI300 10 F...

Страница 3: ...to the registered fault recognition time Features of the Permaconn PM1030 Four 4 Inputs and a dedicated box tamper Three 3 Outputs Contact ID interface requires DI300 module RS485 RS232 Interface requ...

Страница 4: ...ogram alarm panel Generate an event from the alarm panel The Online GPOL LED will stay on steady Test all inputs and outputs Carry out all tests on Final Commissioning Check List Never leave site with...

Страница 5: ...he DI300 Connect PSTN in Mode 3 Unit is supplied as GPRS primary with PSTN back up To make the PSTN primary and GPRS back up the PSTN jumper must be re moved from the DI300 The option of PSTN primary...

Страница 6: ...one number Panel must report Contact ID format Panel must be programmed with a Hard ID Disable telephone line monitoring feature from the panel Battery Charging A dedicated 14 5V power supply is requi...

Страница 7: ...30 and the device being switched Tamper input does not require an EOL resistor All other inputs must be terminated with a 10K resistor Defaulting the Permaconn PM1030 Apply Battery or 14 5V DC power f...

Страница 8: ...ered by the alarm panel Transmission Delay Times Tamper input status message are transmitted immediately Message originating from the panel are forwarded immediately Alarm panel interface fail sent if...

Страница 9: ...LED Activity Indication POWER On Indicates battery or 14 5 Volt Power Off Indicates unit is off GSM On Unit not activated or network is not available Blinking 1 sec On 1 sec Off Searching for 3G netwo...

Страница 10: ...es fault with wiring between PM1030 and DI300 Check blue and white wire PSTN On Indicates that there is no line voltage on the incoming telephone from the ex change Off Indicates PSTN line voltage Off...

Страница 11: ...panel Verify with monitoring centre that correct CID account and event received Test alarm panel PSTN communication Remove jumper from DI300 Generate event from alarm panel Verify with monitoring cen...

Страница 12: ...mmunicate Permaconn experienced trouble sending signals do not expect restore 351 0 954 956 Phone Line Fail 352 0 955 956 Dialer Interface Lead Fail Issue with dialer lead between Permaconn unit and t...

Страница 13: ...rface Consult the relevant serial interface specifications Battery Low Fail DCV 11 8 Report delay 10 minute Restore DCV 12 5 Immediate Communications Class As per compliance statement Size 70 x 50 x 2...

Страница 14: ...e with AS 2201 5 Clause 3 9 on Subject to the Standard Terms and Conditions set out on the Activation Form for this unit INSTALLATION MUST BE CARRIED OUT BY SERVICE PERSONNEL ONLY CAUTION RISK OF EXPL...

Страница 15: ...15 NOTES RDCCO_2143_E_IN PM1030 Manual March 2019 v2 2...

Отзывы: