Installation Procedure
Place the Permaconn PM1030 unit in the exact position where you intend to install it.
Screw the antenna onto SMA connector.
Unit is by default set up to operate with the DI300. If any other module is required remove
the two (2) jumpers from (JP2) and fit applicable IFM.
No additional module required for standalone operation.
Connect 14.5V DC power to power up.
The ‘HEART BEAT’ LED will blink.
The signal strength will be displayed as ‘High’, ‘Medium’ or ‘Low’.
The ‘Online/GPOL’ LED will blink to indicate connectivity with the Permaconn Network.
This may take to three (3) minutes.
Connect the DI300 or IFM module.
Program alarm panel.
Generate an event from the alarm panel.
The ‘Online/GPOL’ LED will stay on steady.
Test all inputs and outputs.
Carry out all tests on ‘Final Commissioning Check List’
Never leave site without achieving a steady ‘Online/GPOL’ LED.
A Three (3) wire connection is required between the DI300 and the PM1030. Negative
and A & B Data lines. Do not connect the red wire when using 14.5V DC plug pack.
Power for the DI300 is supplied from the Alarm panel.
The gray wire connects to Data line on keypad. The gray wire simply monitors and reports
the status of the alarm panel.
Cut the gray wire off at terminal if you do not use it, otherwise it will send false alarms.
The ‘COMMS’ LED will flash to indicate correct serial communication between the DI300
panel and the Permaconn PM1030.