Installer manual Fleck 5800 XTR - Programming
80 / 126
Ref. MKT-IM-006 / E - 12.11.2019
6.3.7.3
Time Based
Aux. #: Time Based
start time 1
end time 1
5 m
1 m
start time #
: Time the relay will turn ON from the start of a regeneration cycle.
end time #
: Time the relay will turn OFF from the start of a regeneration cycle.
Press
to save and to pass to the second time settings screen or to the master settings screen.
Press
to return to the master settings screen without saving.
Set the second times and press
to save and to pass to the second relay settings screen if
present, or press
to return to the master settings screen without saving.
If already in second relay, or if second relay has not been activated, press
to save and to return
to the master settings screen or press
to return to the master settings screen without saving.
6.3.7.4
Volume Based
Aux. #: Volume Based
volume
duration
15 s
550
L
volume
: Volume to be treated to turn the relay ON.
duration
: Duration the relay will stay ON. Can be set for up to two hours.
Press
to save and to pass to the second relay settings screen if present, or press
to return
to the master settings screen without saving.
If already in second relay, or if second relay has not been activated, press
to save and to return
to the master settings screen or press
to return to the master settings screen without saving.
6.3.8
Meter screen
From the master settings screen press the
meter
button to display the meter screen.
Содержание Fleck 5800 XTR
Страница 1: ...FLECK 5800 XTR INSTALLER MANUAL WATER PURIFICATION...
Страница 17: ...Installer manual Fleck 5800 XTR Description Ref MKT IM 006 E 12 11 2019 17 126 3 3 Outline drawing...
Страница 103: ...Installer manual Fleck 5800 XTR Maintenance Ref MKT IM 006 E 12 11 2019 103 126...
Страница 126: ...www pentairaquaeurope com...