SERIAL PORTS SETTINGS - PROFIBUS CONFIGURATION
CONNECTION SUBMENU
Message
Name
Description
Type Default
Range
EN.FBUS.
Enabling
Fieldbus
Enabling Profibus fieldbus;if OFF,
no error message regarding
the Profibus communication is
displayed
Sel.
OFF
OFF
ON
ADDR.PR.
Profibus Ad-
dress
Communication address of Profibus
protocol
Sel.
1
1 ÷ 126
INP.REG.
Dimension
Input area
Dimension of the input area for
Profibus fieldbus (values expressed
in bytes)
Sel.
128
32, 64, 96, 128
OUT.REG.
Dimension
Output area
Dimension of the output area for
Profibus fieldbus (values expressed
in bytes).
128
32, 64, 96, 128
SERIAL PORTS SETTINGS - PROFINET CONFIGURATION
CONNECTION SUBMENU
Message
Name
Description
Type Default
Range
EN.FBUS.
Enabling
Fieldbus
Enabling Profinet fieldbus;if OFF,
no error message regarding
the Profinet communication is
displayed
Sel.
OFF
OFF
ON
INP.REG.
Dimension
Input area
Dimension of the input area for
Profinet field (values expressed in
bytes).
Sel.
128
32, 64, 96, 128
OUT.REG.
Dimension
Output area
Dimension of the input area for
Profinet field (values expressed in
bytes).
Sel.
128
32, 64, 96, 128
The XML
“GSDML-V2.3-HILSCHER-NIC 50-RE PNS 32-20160122.xml”
configuration file is
provided. The size of the input and output areas set in the PLC (possible selections: 32, 64,
96 or 128 bytes) must correspond to the size of the input and output areas selected in the
instrument (“INP.ADJ.” And “OUT.ADJ.” Parameters).
The instruments are supplied with the parameter “Profinet Name” not setup and with an IP
address of 0.0.0.0.