Keypad Lockout
Use the following section to program keypad lockout settings for your control panel. Use worksheet 29 to record your settings.
NOTE:
For EN 50131, the keypad lockout value must be set between three and ten attempts. The minimum delay to lock must be two minutes.
Dialer Options
Timers
Use worksheet 37 to record your settings for sections
[820]
to
[840]
.
[715]
___/___/___
000 to 255
Recycle alarm counter
(default: 000)
[723]
___/___/___
000 to 255 seconds
Panic shutdown**
(default: 010)
* For EN 50131, the maximum value is 45 seconds.
** For EN 50131, the section must be set to a minimum of 3 and a maximum of 10
Worksheet 54: Keypad Lockout
Section
Data
Description
Default
[716]
___/___/___
000 to 255 minutes
Keypad lockout delay
015 minutes
[717]
___/___/___
000 to 255 attempts before locking
Keypad lockout counter
005 attempts
Table 58: Description of section [801]
Option
Description
OFF
ON
Sec
tion
[801]
1
Report system disarming
Always
After alarm
2
Report zone restore on closure
Bell cutoff
Zone closure
3 & 4
Auto-test report transmission
Disabled
Enabled
5
Contact ID override
Disabled
Enabled
6
Future use
7
Future use
8
Future use
= Default
Worksheet 55: Communication Timers
Section
Data
Description
Default
[820]
___/___/___
000 to 255 hours
Fail to comm. clear event timer
000 = disabled
[830]
___/___/___
000 to 255 x 2 seconds
TLM fail delay (landline only)
016
[831]
___/___/___
000 to 032
Maximum dialing attempts monitoring station (landline only)
002
[832]
___/___/___
000 to 127 seconds
Delay between dialing attempts* (landline only)
020
[833]
___/___/___
000 to 255 seconds
Delay alarm transmission
000
[836]
___/___/___
000 to 127 seconds
Personal reporting delay*
005
[837]
___/___/___
000 to 010
Personal reporting message repetition*
003
[838]
___/___/___
000 to 255 seconds
Recent closing delay
000
[839]
___/___/___
000 to 255 minutes
Power failure report delay**
015
[840]
___/___/___
000 to 255 days
Auto test report (see
001
* Also applicable when using a VDMP3 Plug-in Voice Dialer.s
**The maximum value for power failure is 60 minutes.
Worksheet 53: System Timers
Section
Data
Description
Section
Data
Description