background image

54 

EVOHD+ Installation Guide

Daylight Savings Time Schedule

S

ECTION

 [3022]

(default = 

18

Select the schedule followed for the Daylight Savings Time adjustment.

Digiplex Bus Speed

S

ECTION

 [3030]: O

PTION

 [8]

In large installations, set the speed to High. If you are experiencing communication troubles, set the speed to Normal or install a Hub (HUB2 or HUB4D). The control 
panel will restart when a change is made

NOTE: 

Please note that when the Digiplex bus speed is changed the following will occur and is considered normal operation:

The message COMM. TROUBLE CALL SERVICE will be displayed on keypads connected to the Digiplex bus.

The AC and STATUS LEDs will begin to alternately flash and all operations on the system will be suspended for approximately one minute while the system 
reconfigures.

Transmit Zone Status on Serial Port

S

ECTION

 [3035]: O

PTION

 [7]

When enabled, the control panel will transmit zone status information through the serial port. Use this when there are devices or software connected to the serial 
port like BabyWare.

Partitioning

S

ECTION

 [3031]: O

PTIONS

 [1] 

TO

 [8]

(default = 

partition 1 enabled

) The control panel can provide up to eight completely independent partitions. Most features and options can be independently set 

for each partition. All zones, keyswitch zones, user codes and system modules are assigned to specific partitions. 

Panel Partition Assignment

S

ECTION

 [3020]

(default = 

00

) The control panel will report system events as originating from one or all enabled partitions. The System Troubles can only be viewed through the 

partitions enabled in this section. Enter a 2-digit decimal number from 01 to 08 which represent partitions 1 to 8. Enter 00 to disable this feature.

Shabbat Feature

S

ECTION

 [3030]: O

PTION

 [4]

(default = 

disabled

) When enabled, addressable detectors and keypads in the system no longer display system status through the LCD and/or LEDs between noon 

Friday and midnight Saturday. Normal operation is re-instated Sunday at 12:00:01a.m. A user can access all the usual commands and features during the Shabbat 
period by pressing a key or by entering their access code (depending on how Confidential Mode is configured in the keypad). When no actions have occurred for 
two minutes, the Shabbat feature will re-activate. During the Shabbat period:

the LCD keypads only display the date and time

the backlight is disabled 

the LED indicators on modules are disabled 

00

Canada/United States/Mexico/St-
Johns/Bahamas/Turks and Caicos

01

Cuba

02

Brazil

03

Chile

04

Falkland Islands

05

Paraguay

06

European Union/United Kingdom/
Greenland

07

Russia and surrounding countries

08

South Australia/Victoria/Australian 
Capital Territory/New South Wales

09

Tasmania/Lord Howe Island

10

New-Zealand/Chatham

11

Tonga

12

Iraq/Syria

13

Israel (TBC)

14

Lebanon/Kirgizstan

15

Palestine

16

Egypt

17

Namibia

18

Canada/United States 2007 (default)

19

New Zealand

[8]

ON

High Speed

[8]

OFF

Normal Speed (default)

[1]

Partition 1

[3]

Partition 3

[5]

Partition 5

[7]

Partition 7

[2]

Partition 2

[4]

Partition 4

[6]

Partition 6

[8]

Partition 8

Содержание EVOHD+

Страница 1: ...EVOHD Installation Guide High Security Access System...

Страница 2: ...available to reduce risk and or damage of burglary fire or other emergencies such other tools include but are not limited to insurance coverage fire prevention and extinguish devices and sprinkler sys...

Страница 3: ...trict Arming on TLM Failure 31 Restrict Arming on Module Troubles 31 Restrict Arming on Anti Mask Troubles 31 Timed Auto Arming 32 No Movement Auto Arming 33 Auto Arming Options 33 Switch To Stay Armi...

Страница 4: ...rogramming Overview 64 Enable Access Control 64 Door Numbering 64 Access Levels 65 Access Schedules 65 Backup Schedules 65 Holiday Programming 65 Schedule Tolerance Window 65 Door Access Mode 66 Code...

Страница 5: ...n between the control panel and all its modules Supports up to 254 expansion bus modules Connect modules up to 914m 3000ft from the panel Sabotage proof technology without additional wiring Expandable...

Страница 6: ...l outputs are rated to operate between 11 4Vdc and 12 5Vdc Specifications may change without prior notice For latest product specifications and standards please visit www paradox com EN 50131 Complian...

Страница 7: ...on Once the location of the box has been completed install the panel as illustrated Figure 1 EVOHD Installation Earth Ground Connect the ground connector to the enclosure and cold water pipe or ground...

Страница 8: ...sume once the overload condition has restored Bell Siren Output The bell output supplies 12Vdc upon alarm and can support one 30 watt or two 20 watt sirens The bell output will automatically shut down...

Страница 9: ...nly The following specifications apply for the K641 K641R and K641 keypads only Dimensions 12 2 cm x 14 4cm 4 8in x 5 67 Weight 0 26 kg 0 58 lbs Humidity 5 90 Standards EN 50131 1 EN 50131 3 Grade 3 C...

Страница 10: ...er power Installer lock enabled 3 Panel reset 4 EBUS and Dialer used with VDMP3 Plug In Voice Module for voice reporting PCS Series Communicator Module 5 Serial 1 Used as the primary reporting channel...

Страница 11: ...__ x 450 mA __________ LCD keypads K641 K656 __________ x 110 mA __________ LCD keypads with built in reader K641R K641 __________ x 120 mA __________ TM70 TM50 __________ x 200 mA __________ Motion d...

Страница 12: ...5ft 15m 50ft DM70 E 30mA 7 5m 25ft ZX8 B 30mA 30m 100ft 22 AWG K641 F 110mA 15m 50ft K641 G 110mA 91m 300ft 290m 950ft DM60 C 30mA 305m 1000ft As indicated in table 2 on page 13 this run of wire can s...

Страница 13: ...22 AWG Surface 0 326 sq mm 30 m 100 ft 1382 24 AWG Surface 0 205 sq mm 30m 100 ft 869 61 m 200 ft 2000 61 m 200 ft 1718 61 m 200 ft 680 61m 200 ft 427 91 m 300 ft 1831 91 m 300 ft 1151 91 m 300 ft 45...

Страница 14: ...nections The control panel includes eight hardwired input terminals for use with traditional hardwired non Digiplex bus door contacts smoke detectors and or motion detectors The control panel also sup...

Страница 15: ...tor Terminals Zone input COM TAMPER SWITCH N C 1K Detector Terminals 1K EOL Detector Terminals 2 2K Zone input COM TAMPER SWITCH N O EOL 2 2K 1K 2 2K Zone input COM TAMPER SWITCH N C EOL 1K 1K 1K EOL...

Страница 16: ...ss Separate Buildings Strip the outer jacket at one end of the shielded cable to expose the shield In the same building as the control panel connect the exposed shield to any earth ground available wh...

Страница 17: ...s and a relay as shown in Figure 11 To comply with UL955 install the 4 wire smoke detectors with 18 gauge wire If power is interrupted the relay causes the control panel to transmit the Fire Loop Trou...

Страница 18: ...d Use the EVOHD Programming Guide to record how the sections were programmed To enter programming mode use a K641 K656 or K641R keypad refer to the table below For the TM70 TM50 press and hold the men...

Страница 19: ...ress For LCD Keypads 0 to 9 values 0 to 9 respectively STAY key A DISARM key D FORCE key B BYP key E ARM key C MEM key F Module Programming Mode To program a Module with a keypad using a K641 K656 or...

Страница 20: ...dwired Device C Zone 1 2 3 4 Section 0001 0002 0003 0004 Serial 21000033 1A000252 020000A2 34000041 Input N A N A 002 005 Keypad SN 1A000252 Keypad Zone Hardwired Device C Hardwired Device A Input Ter...

Страница 21: ...de for details of its input numbers input numbers not required for keypad zones NOTE If PGM1 is defined as a smoke detector input see section on page 52 the control panel will recognize it as input 25...

Страница 22: ...sed for perimeter protection 24Hr Burglary Zones SECTION 0400 FIRST DIGIT 6 SECTIONS 0101 TO 0196 FIRST DIGIT 6 When a 24Hr Burglary zone opens the control panel will immediately generate a burglary a...

Страница 23: ...can send a Zone Alarm report code page 40 send a Fire Loop Trouble Report page 43 if a tamper wiring fault occurs on a Fire Zone A Zone Fault Trouble will also appear in the keypad s Trouble Display g...

Страница 24: ...ition occurs on a zone with option 7 enabled the control panel triggers the Intellizone Delay Fire Zones cannot be set as Intellizones An alarm will only be generated if the selected conditions occur...

Страница 25: ...ion 6 3626 Partition 8 3826 Option Description 1 Intellizone Delay default disabled The zone stays in alarm for the entire IntellizoneDelay 2 Intellizone DoubleKnockout and Zone Crossing default disab...

Страница 26: ...s on page 16 For more information on EOL options please refer to the EVOHD programming guide Selectable Input Resistor SECTION 0402 default disabled To select a different value for EOL resistor please...

Страница 27: ...___ ___ ___ ___ ___ ___ ___ ___ 2918 ___ ___ 3 2903 ___ ___ ___ ___ ___ ___ ___ ___ 2919 ___ ___ 4 2904 ___ ___ ___ ___ ___ ___ ___ ___ 2920 ___ ___ 5 2905 ___ ___ ___ ___ ___ ___ ___ ___ 2921 ___ __...

Страница 28: ...ARM C STAY Utility Key 2 D DISARM D OFF Utility Key 3 E BYP E MENU Utility Key 4 F MEM F N A Section Description 2940 Default Button Template To select a button template as the default template enter...

Страница 29: ...2 FIRST DIGIT 2 To arm a partition using the Maintained Keyswitch turn the switch from the ON to the OFF position Disarm it by setting the key on the ON position Generates a Utility Key Event on Open...

Страница 30: ...ns 0601 to 0632 Option 3 When enabled the keyswitch can only disarm assigned partitions The type of disarming is determined by the other Keyswitch Options selected Stay Instant Disarm Option Keyswitch...

Страница 31: ...nabled the control panel prevent arming if it detects a loss of AC power Restrict Arming on Battery Failure SECTION 3035 OPTION 2 default disabled When enabled the control panel prevents arming if it...

Страница 32: ...Arm Timer Enter the time when the partition should arm in the desired section Postpone Auto Arming default 000 It is possible to postpone auto arming for a preset amount of time by entering a valid u...

Страница 33: ...s Force Arm when Regular Arming default disabled When enabled for a particular partition the system will Force arm that partition whenever Regular or Force arming is activated Stay and Instant arming...

Страница 34: ...in seconds for a special arming Special arming are any arming that do happen without interacting with a keypad i e scheduled arming keyswitch arming BabyWare arming no movement arming etc Keypad Lock...

Страница 35: ...he keypads will not display that zones have been bypassed while the system is armed Partition 1 3106 Partition 3 3306 Partition 5 3506 Partition 7 3706 Partition 2 3206 Partition 4 3406 Partition 6 36...

Страница 36: ...disabled Supervision Bypass Options SECTION 3034 OPTION 3 default disabled When enabled in section 3034 the Wireless Transmitter Supervision Options will follow the zone s bypass definition The contr...

Страница 37: ...rtition 1 3118 Partition 3 3318 Partition 5 3518 Partition 7 3718 Partition 2 3218 Partition 4 3418 Partition 6 3618 Partition 8 3818 5 6 Description OFF OFF Disabled default Displays zone open on the...

Страница 38: ...partition enable or disable options 1 through 6 Report Only The keypad emits a single confirmation beep and transmits the report code Audible Alarm The control panel activates the BELL output until a...

Страница 39: ...under Reporting Formats on page 45 2 Auto Report Code Programming on page 48 Dialing sequences for Arm Disarm Report Codes Partition 1 3127 Partition 5 3527 Partition 2 3227 Partition 6 3627 Partition...

Страница 40: ...when a zone closes or once the bell has cut off see section on page 36 Refer to Zone Restore Report Options in see section on page 48 Tamper and Tamper Restore Report Codes section 0400 Third and Fou...

Страница 41: ...l panel ends communication with BabyWare 3906 Installer In Installer enters programming mode 3907 Installer Out Installer exits programming mode 3908 to 3909 Future Use 3910 Auto Arming When Auto Armi...

Страница 42: ...med before Disarming Schedule see section on page 44 3927 Late to Open Partition disarmed after Disarming Schedule see section on page 44 3928 Remote Disarm Partition disarmed with InTouch Voice Assis...

Страница 43: ...Module Rf Interference ___ ___ Module low voltage ___ ___ Module self test error 3964 ___ ___ Module LAN trouble ___ ___ Module WAN trouble ___ ___ Future use ___ ___ Future use Section Data Descript...

Страница 44: ...Window lengthens the partition s Arming Disarming Schedule for some users User access codes with Add Tolerance Windows to Schedules enabled have the number of minutes programmed in these sections adde...

Страница 45: ...rtition where the event originated regardless of which MSTN is dialed Reporting Formats SECTION 3070 The control panel can use a number of different reporting formats Each monitoring station phone num...

Страница 46: ...nel will dial the selected backup telephone number For each section enable or disable the options default only option 1 enabled Maximum Dialing Attempts SECTION 3056 default 008 The number 001 to 255...

Страница 47: ...grammed into section 3902 every hour or after a period of time Partition 1 3109 Partition 3 3309 Partition 5 3509 Partition 7 3709 Partition 2 3209 Partition 4 3409 Partition 6 3609 Partition 8 3809 O...

Страница 48: ...es FF from the Automatic Report Codes List in the EVOHD Programming Guide Closing Delinquency Timer default 000 disabled When a partition in the system is disarmed the control panel will start the cor...

Страница 49: ...ol panel switches from tone dialing to pulse dialing on the fifth attempt to report events to the monitoring station The control panel continues to use pulse dialing until it establishes communication...

Страница 50: ...e PGM is in fact OFF Step English 1 Install Power down the EVOHD control panel Install the VDMP3 directly onto the EVOHD control panel s EBUS and DIALER connectors as shown in VDMP3 Installation Instr...

Страница 51: ...rvice the Answering Machine Override must be programmed The value programmed in section 3052 represents the delay period that the VDMP3 will wait between the first and second call The user must call t...

Страница 52: ...ault is set to 15 minutes 6 Set your PGM options Refer to table 8 PGM1 Becomes a 2 wire Smoke Detector Input SECTION 3030 OPTION 1 default disabled When enabled PGM1 acts as a zone input for two wire...

Страница 53: ...efault enabled When enabled the control panel adjusts the system s clock time for daylight saving changes 4040 Resets the programmable sections from 0001 to 3991 to default even if Installer Code Lock...

Страница 54: ...will report system events as originating from one or all enabled partitions The System Troubles can only be viewed through the partitions enabled in this section Enter a 2 digit decimal number from 01...

Страница 55: ...0301 to 0396 the Door Labels sections 2301 to 2332 and the Partition Labels sections 3100 3200 3300 3400 3500 3600 3700 and 3800 to all the modules in the system that support these labels To transmit...

Страница 56: ...les have been successful deleted you will be returned to the Manage Bus Modules menu Serial Number Viewing SECTION 4000 Enter section 4000 to view the serial number of the control panel and all the mo...

Страница 57: ...case and vice versa MEM Special Characters The cursor will turn into a flashing black square Enter the 3 digit number that represents the desired symbol see table 11 on page 57 table 15 on page 58 an...

Страница 58: ...4 210 226 242 035 051 067 083 099 115 163 179 195 211 227 243 036 052 068 084 100 116 164 180 196 212 228 244 037 053 069 085 101 117 165 181 197 213 229 245 038 054 070 086 102 118 166 182 198 214 23...

Страница 59: ...101 117 133 149 165 181 197 213 229 245 022 038 054 070 086 102 118 134 150 166 182 198 214 230 246 023 039 055 071 087 103 119 135 151 167 183 199 215 231 247 024 040 056 072 088 104 120 136 152 168...

Страница 60: ...methods with access to all partitions and can program all user access codes User Options Partition Assignments and Access Control Options The minimum number of variations of PIN codes for each user is...

Страница 61: ...artition 1 2 User Code has Access to Partition 2 3 User Code has Access to Partition 3 4 User Code has Access to Partition 4 5 User Code has Access to Partition 5 6 User Code has Access to Partition 6...

Страница 62: ...t SECTIONS 1002 TO 1999 LEVEL SCHEDULE SCREEN User access codes can only open the doors included in their assigned Access Level see section on page 65 In the first set of brackets enter the two digit...

Страница 63: ...ntrol ON User s Access Control feature is enabled and user has access when the control panel s Access Control feature is enabled OFF User s Access Control feature is disabled but the user access code...

Страница 64: ...open An Access Alarm will be triggered after that period Forced Door An Access Door was opened without an Access Granted or Request for Exit signal a silent or audible Access Alarm can be triggered R...

Страница 65: ...d Primary Schedule If there are linked schedules it will verify them The control panel will verify up to 8 linked Schedules Each Schedule from 001 to 032 can be linked to another Schedule in sections...

Страница 66: ...disabled When arming with an Access Card the system can arm with or without starting the Exit Delay Restrict Arming on Door SECTION 2251 TO 2282 OPTION 4 With option 4 ON the control panel can prevent...

Страница 67: ...In Event Buffer SECTION 3038 OPTION 2 default disabled When enabled the control panel can record the REX events generated from all the Doors in the Event Buffer but cannot report these events to the m...

Страница 68: ...representing the delay period the control panel will wait between the first and second call To use 1 Call the installation and with BabyWare press ENTER on the keyboard or hang up manually on the sec...

Страница 69: ...R S USB PORT OR 9 PIN SERIAL PORT DB 9 DB 9 Rx Tx PC LINK USB Product Link 307USB CV4USB BATTERY OR CONTROL PANEL AUX TO COMPUTER S USB PORT OR 9 PIN SERIAL PORT DB 9 OR CONV4USB NOTE K641 K641 and K6...

Страница 70: ...arming cancellation 1 464 Auto arm time extended CE Closing extend Cancel alarm with PC software 1 4A6 Cancel OR Disarm from alarm Voice disarm 1 4A7 Remote arm disarm OQ Remote disarming Disarm with...

Страница 71: ...FT Tamper restoral Combus fault 1 333 Expansion module failure ET Expansion trouble Module tamper 1 145 Expansion module tamper TA Tamper alarm Module ROM_RAM_error 1 3A4 ROM checksum bad YF Parameter...

Страница 72: ...in to follow LF Listen in to follow BabyWare login request 1 411 Call back Request RB Remote program begin PC software communication finished 1 412 Successful download access RS Remote program success...

Страница 73: ...B 303 RAM checksum bad 3C 304 ROM checksum bad 3D 305 System reset 3E 306 Panel program changed 3F 307 Self test failure 40 308 System shutdown 41 309 Battery test failure 42 310 Ground fault 43 311 B...

Страница 74: ...ng Code Value Sounder Relay Disables 520 530 520 Sounder relay disabled A9 521 Bell 1 disable AA 522 Bell 2 disable AB 523 Alarm relay disable AC 524 Trouble relay disable AD 525 Reversing relay disab...

Страница 75: ...e 10 In order to communicate its status to the control panel the keypad s input must be assigned to a zone in the control panel and the zone s parameters must be defined Programmable Output Each keypa...

Страница 76: ...connected to Z2 terminal NOTE If a door contact is not being used install a jumper or a 1kOhm resistor across the blk and z1 terminals depending on the control panel s EOL definition If the REX Reques...

Страница 77: ...gramming K641 K641R SECTIONS 101 TO 148 200 TO 204 AND 301 TO 396 Each section contains one message with a maximum of 16 characters For more details and to record any changes use the Digiplex Modules...

Страница 78: ...e control panel battery test Option 4 OFF Normal Mode default Option 4 ON Confidential Mode Option 5 OFF LCD screen activated by entering an access code default Option 5 ON LCD screen activated by pre...

Страница 79: ...follow the PGM Deactivation event the PGM will return to its normal state when the event programmed in sections 013 to 016 occurs Enter the sections that correspond to the Event Group Feature Group S...

Страница 80: ...Exit Delay beep disabled Option 2 ON Exit Delay beep enabled default Chime on Zone Closure SECTION 004 OPTION 4 Option 4 OFF Chime on Zone Closure disabled default Option 4 ON Chime on Zone Closure e...

Страница 81: ...ked longer This will allow those with this feature enabled on their User Access Codes extra time to enter Enter any value between 001 and 255 to determine the number of seconds to be added to the time...

Страница 82: ...Open Access Alarm SECTION 006 OPTION 3 When the Door Forced Open Alarm is disabled the following sections are also disabled Option 3 OFF Door Forced Open Alarm is disabled default Option 3 ON Door Fo...

Страница 83: ...Clock Loss 67 Closing Delinquency Timer 49 Code Access 67 Code Follows Schedule 64 Codes Special Alarm Report Codes 43 Special Arming Report Codes 42 Special Disarming Report Codes 43 System Trouble...

Страница 84: ...Battery Failure 32 Bell or Auxiliary Failure 32 Door 67 Module Troubles 32 Supervision Loss 32 Tamper 32 TLM Failure 32 Restrict Disarming on Door 67 Ring Counter 69 Ring back 36 S Schedule Assignmen...

Страница 85: ...d by qualified service personnel only Warranty For complete warranty information on this product please refer to the Limited Warranty Statement found on the website www paradox com terms Your use of t...

Страница 86: ......

Страница 87: ...We hope this product performs to your complete satisfaction Should you have any questions or comments please contact us at support paradox com Additional information can be found on our website www p...

Отзывы: