EVOHD+ Installation Guide
Programmable Outputs
The control panel provides a maximum of 100 mA to PGM2 to PGM4. PGM1 is an open collector output and PGM5 is a 3A/28Vdc N.O./ N.C. relay output. Activating a
PGM changes it’s state from open to closed or closed to open. See “Programmable Outputs” on page 8.
PGM Programming
1.
Enter section
[0901]
-
[0932]
.
2.
Enter the eight-digit module or panel serial number and three-digit output number.
3.
Enter the three-digit Event Group, Feature Group, Start #, and End # for PGM activation.
4.
Enter the three-digit Event Group, Feature Group, Start # and End # for PGM deactivation.
5.
Define the PGM Delay value (001 to 255 x 1 sec./min.). Default is set to 15 minutes.
6.
Set your PGM options. Refer to table 8.
PGM1 Becomes a 2-wire Smoke Detector Input*
S
ECTION
[3030]: O
PTION
[1]
(default =
disabled
) When enabled, PGM1 acts as a zone input for two-wire smoke detectors. When programming Zone Numbering (see section on page 21), the
control panel will recognize PGM1 as input number 255. Please refer to section on page 17 for connection information.
* UL Note:
Not verified by UL.
Table 8: PGM Options
Option
Description
PGM #
OFF
ON
1
PGM deactivation after (OFF = deactivation event; ON = PGM timer)
2
PGM base time (OFF = seconds; ON = minutes)
3
Flexible PGM deactivation option (OFF = PGM timer only; ON = PGM timer and/
or deactivation event)
4
PGM initial state (OFF = normally open; ON = normally closed)
5
PGM Time base (OFF = follow options 2, ON = hour)
6
Voltage output (2-4) (OFF = negative trigger OV; ON = positive trigger 12V)
7 to 8
Future use
-
-