background image

Versions 4.4 (728ULT) & 4.1 (738ULT)

Reference & Installation Manual

&

728ULT

738ULT

Summary of Contents for ESPRIT 728 ULT

Page 1: ...Versions 4 4 728ULT 4 1 738ULT Reference Installation Manual 728ULT 738ULT ...

Page 2: ......

Page 3: ... 12 Hex Programming 12 Hex Streamlined Section Programming 13 Decimal Programming 13 Feature Select Programming 13 Panel Settings for Espload 14 Panel Answer Options 14 Panel Identifier 14 PC Password 14 Computer Telephone Number 15 Call Espload 15 Answer Espload 15 Cancel Communication 15 Call Back 15 Automatic Event Buffer Transmission 15 Event Reporting 16 Reporting Options 17 Reporting Disable...

Page 4: ...d Functions 40 Programming Master and User Codes 40 Regular Arming 40 One Key Regular Arming 40 Force Away Arming 40 Stay Arming 41 One Key Stay Arming 41 One Key Instant Arming 41 Fast Exit 41 Arming Disarming Partitions 41 One Key System A Arming 42 System Disarming 42 Alarm Memory 42 Keyswitch or Pushbutton Arming Disarming 42 Manual Zone Bypassing 42 Bypass Recall 42 Keypad Chime Zones on LED ...

Page 5: ...sistor output 738 Ultra Serial data output 1200 1 N for use with accessory modules not for use with UL systems Please refer to Warnings on page 45 for UL Specifications Specifications may change without prior notice Feature 728 Ultra V4 10 728 Ultra V4 20 4 40 738 Ultra V4 0 738 Ultra V4 1 2 wire smoke detector 9 9 9 Serial or parallel wiring for ATZ connections see page 27 9 9 9 9 Master Code Loc...

Page 6: ...olled outlets to power the transformer Use a 16 5Vac 50 60Hz transformer with a minimum 20VA 40VA recommended rating to provide sufficient AC power UL cUL listed systems require a Universal Model No UB1640W plug in transformer Connect the transformer as shown in Figure 2 The power supply can provide a maximum of 1 1A for battery charge current Do not connect the transformer or the backup battery u...

Page 7: ...up battery no AC At 8 5 volts the panel shuts down and all outputs close 2 3 5 Keypad Function Test We recommend conducting a power up test on keypads installed far from the control panel To do so temporarily connect the keypads near the control panel and connect the transformer After 10 seconds begin entering random commands on the keypad and verify that the keypad beeps in response to these comm...

Page 8: ...hrow dry contacts that follows the bell siren alarm output If the Bell Siren output is not being used connect a 1k9 resistor across the BELL and BELL terminals Figure 5 Bell Siren Output Connection 2 6 Programmable Outputs PGMs The 728 Ultra and 738 Ultra control panels include one 728 Ultra or two 738 Ultra fully programmable outputs PGM When a specific event or condition occurs in the system a P...

Page 9: ... keypad zone input terminal is not being used disable it by shorting the blue zone wire with the black COM wire of the keypad Disabling 642 Keypad Zones If the keypad zone input terminal is not being used disable it by setting option 2 Keypad Options key 1 to OFF Do not use the 646 LED and 642 LCD keypads for UL installations Both the 646 LED keypad and the 642 LCD keypad are not UL listed LED KEY...

Page 10: ...ram the keypad definitions as follows Keypad Programming Mode option 2 Keypad Options Key 1 ON Keypad Zone Enabled Keypad Programming Mode option 2 Keypad Options Key 2 ON Requires 1k9 EOL Keypad Programming Mode option 2 Keypad Options Key 3 OFF Keypad Zone 1 Keypad Programming Mode option 2 Keypad Options Key 3 ON Keypad Zone 2 Keypad Programming Mode option 2 Keypad Options Key 4 ON Keypad Comm...

Page 11: ...per cut and wire fault short recognition all detection devices must use normally closed contacts Connect the devices and program the control panel as shown in Figure 14 This setup will communicate an open or closed zone to the control panel and display open zones on the keypad The control panel will also communicate any detected tampers cuts and or wire faults short as per Tamper Wire Fault Recogn...

Page 12: ... the detection devices and program the control panel as shown in Figure 16 Do not use devices with normally open contacts as this will cause the system to remain in alarm This setup will communicate the status of each device to the control panel see Figure 15 on page 8 and display open zones on the keypad Figure 16 N C Contacts without EOL Resistor Control Panel Terminals Control Panel Terminals C...

Page 13: ...ee Figure 18 and display open zones on the keypad Any tampers cuts and or wire fault shorts detected on the system are communicated as per Tamper Wire Fault Recognition Options on page 38 Figure 18 N C Contacts with EOL Resistor with Tamper and Wire Fault Recognition UL cUL 2 11 4 N C Contacts With ATZ Parallel Wiring If your security installation does not require tamper or wire fault recognition ...

Page 14: ...ys are pressed at the same time see PGMs Programmable Outputs on page 35 Address 039 BYP 2ND Address 042 2ND 6 Address 040 5 0 Address 056 0 3 0 All smoke detectors must be connected using a daisy chain configuration 2 12 3 2 Wire Smoke Detector Connections Connect the 2 wire smoke detectors to input 3 as shown in Figure 22 Note that a fire zone must use a 1k9 EOL resistor If there is a line short...

Page 15: ...hen programming user codes an option for either 4 digit or 6 digit access codes can be programmed When the 4 digit option is selected entering a 4 digit code will allow the person access Using the 6 digit option entering 6 digits is required to allow access Key 9 OFF 6 digit Access codes Key 9 ON 4 digit Access codes ENTER Installer code 0 8 8 9 ON OFF ENTER twice 3 4 Duress Feature Select Program...

Page 16: ... its many features When programming with the keypad certain addresses are programmed using different methods These methods are described in detail below Each section in this manual will reference the appropriate programming method 4 2 1 Hex Programming Addresses 000 to 043 and 300 to 527 are programmed using the Hex Programming method In this mode you can enter any hex digit from 0 to F where keys...

Page 17: ...t address 044 to 061 The keypad will now display the current 3 digit data currently saved at this address as described in Figure 24 3 Enter 3 digit data decimal value After entering data you do not need to press ENTER the software will automatically save the data into the selected address 4 Return to step 2 to continue programming or press CLEAR to exit programming mode 4 2 4 Feature Select Progra...

Page 18: ... before the number of pre programmed rings has elapsed the control panel will keep the number of rings in memory for 64 seconds If you hang up and call the installation site back within 64 seconds the control panel will continue to count the number of rings from the first call After reaching the total number of rings the control panel will answer the call The number of rings can be set from 1 to 1...

Page 19: ...all communication and erase any unreported events in the buffer until the next reportable event Use the Master or User code 1 to cancel communication attempts with Espload ENTER Installer Master and User code 1 STAY 5 8 Call Back Feature Select Programming D Address 086 Key 4 Default Call Back Disabled For additional security when a PC using the Espload software attempts to communicate with the co...

Page 20: ... Features Auto Test Report Addresses 046 to 048 Manual Test Report BYP Key Access Power Failure Report Delay Address 054 Recent Close Delay Address 060 Report Zone Restore Options Address 088 BYP Report Disarm Option Address 088 TBL TRBL Valid report codes must be programmed into the addresses corresponding to the reportable events Section 11 to 67 Addresses 300 to 527 Addresses 300 to 527 do not ...

Page 21: ...quence again 6 1 3 Split Reporting When the system is not in alarm the control panel will report all Event codes to Monitoring Station Telephone 2 MSTN2 If communication fails the dialer will hang up wait a predetermined period and dial the number again The control panel will dial the number eight times until communication is established see Figure 26 on page 18 After eight unsuccessful attempts t...

Page 22: ...imum of 16 digits If you would like to enter any special keys or functions refer to Table 5 If the telephone number contains less than 16 digits press the TBL TRBL key to indicate the end of the telephone number ENTER Installer code 7 0 6 MSTN2 ENTER or TBL TRBL if number is less than 16 digits Both monitoring station telephone numbers must be programmed in order for event reporting to function pr...

Page 23: ...able 6 Communicator Formats 6 5 1 Ademco Contact ID All Codes Please note that this format must use a 4 digit system account code see section 6 4 Ademco Contact ID is a fast communicator format that uses tone transmission instead of pulse transmission This communicator format also uses a pre defined list of industry standard messages and event codes that should suit most of your basic installation...

Page 24: ...0 SYSTEM TROUBLE 2 2 110 FIRE ALARM 2ND 2 301 AC LOSS 2 3 111 FIRE SMOKE 2ND 3 302 LOW SYSTEM BATTERY 2 4 112 COMBUSTION 2ND 4 305 SYSTEM RESET 2 5 113 WATER FLOW 2ND 5 306 PROGRAM CHANGED 2 6 114 HEAT 2ND 6 309 BATTERY TEST FAIL 2 7 115 PULLSTATION 2ND 7 320 SOUNDER RELAY TROUBLE 2 8 116 DUCT 2ND 8 321 BELL 1 TROUBLE 2 9 117 FLAME 2ND 9 323 ALARM RELAY TROUBLE 2 0 118 NEAR ALARM 2ND 0 350 COMMUNI...

Page 25: ...length of time that the data will be continuously transmitted Enter 2ND or 1 to F to program a value from 8 seconds to 120 seconds Refer to Table 9 for the Pager Delay Values 6 7 Pager Format Transmission Options Feature Select Programming D Address 090 Key MEM Default Follow Pager Delay The Pager Reporting Format can be configured to transmit immediately or to transmit after a pager delay has ela...

Page 26: ...tra The control panel will send the programmed event code to the monitoring station as soon as the zone closes after having generated an alarm or as soon as the zone closes after bell cut off For more information please see Report Zone Restore Options on page 24 6 9 5 Zone Shutdown Codes Streamline Sections 48 to 50 D Hex Programming Addresses 448 to 457 728 Ultra Streamline Sections 48 to 52 D He...

Page 27: ...513 Panic 1 Keys 1 and 3 are pressed to activate a Panic 1 alarm 514 Panic 2 Keys 4 and 6 are pressed to activate a Panic 2 alarm see Keypad Panic Options on page 37 515 Panic 3 Keys 7 and 9 are pressed to activate a Panic 3 alarm 516 Late To Close Timed Auto Arming see page 32 is enabled and the system has not automatically armed itself at the specified time 517 No Movement No Movement Auto Armin...

Page 28: ... BYP ENTER 6 13 Power Failure Report Delay Decimal Programming D Address 054 Default 30 minutes After a power failure the control panel will delay transmission of the event code programmed at address 499 by the length of time programmed at this address 001 to 255 minutes ENTER Installer code 0 5 4 3 digit decimal value 001 to 255 ENTER 6 14 Recent Close Delay Decimal Programming D Address 060 Defa...

Page 29: ...fined Keypad Zone 1 2 Supervision Enabled Disabled Address 090 Keys STAY AWAY FORCE Independent Zone Definitions Only one of these options can be assigned to a zone If a zone is assigned more than one option the control panel will apply the option with the highest priority 1 to 5 Intellizones Address 092 Keys 1 to 10 0 Intellizone Time Delay Address 057 Silent Zones Address 096 Keys 1 to 10 0 24Hr...

Page 30: ...ddress 090 Keys STAY AWAY FORCE Independent Zone Definitions Only one of these options can be assigned to a zone If a zone is assigned more than one option the control panel will apply the option with the highest priority 1 to 5 Intellizones Addresses 092 94 Keys 1 to 12 Intellizone Time Delay Address 057 Silent Zones Addresses 096 98 Keys 1 to 12 24Hr Fire Zones Addresses 100 102 Keys 1 to 12 Gen...

Page 31: ...7 3 Intellizones 728 Ultra Feature Select Programming D Address 092 Keys 1 to 10 0 738 Ultra Feature Select Programming D Addresses 092 and 094 Keys 1 to 10 0 STAY 11 and FORCE AWAY 12 If an alarm condition occurs on a zone identified as Intellizone the control panel will trigger a timer and will not generate an alarm until one of the following conditions occurs within a specified period see Intel...

Page 32: ... smoke detector recognition disabled Enable this feature to have the control panel recognize 2 wire smoke detectors With this feature enabled input 3 or zone 3 will be reserved for 2 wire smoke detectors If ATZ is disabled on the 728 Ultra the 2 wire smoke detector will be assigned to zone 3 If ATZ is enabled on the 728 Ultra the 2 wire smoke detector will be assigned to zone 5 Zone 6 or zone 11 f...

Page 33: ...Disarmed Zones assigned to System B will arm disarm when the system is System B Armed Disarmed Zones assigned to both systems dual area will arm when the system is either System A Armed System B Armed or when both systems are armed and will disarm only when both systems disarm Zones not associated with any system common area will arm only when the system is both System A Armed and System B Armed a...

Page 34: ...ER 7 12 EOL Zones Enabled Disabled Feature Select Programming D Address 088 Key MEM Default Enabled No EOL If the system requires the use of 1k9 end of line resistors on zone input terminals disable this feature see Keypad Zone Connections on page 5 to Single Zone Input Terminal Connections on page 6 Key MEM OFF Input Zones use EOL Resistors Key MEM ON Input Zones do not use EOL Resistors ENTER In...

Page 35: ...A Stay Arming Address 088 key 8 Keyswitch Arming Address 086 keys 2 3 Bell Squawk Address 086 MEM key Exit Delay Address 049 Alarm Transmission Delay Address 059 Bell Cut Off Time Address 052 Beep on Exit Delay Address 088 key AWAY FORCE Bypass Access Addresses 074 076 and 078 all keys System B Away Arm Priority Addresses 068 070 and 072 all keys System A Stay Arm Priority Addresses 062 064 and 06...

Page 36: ...ing hours 2 digits representing minutes ENTER 8 1 2 Auto Arming Options Feature Select Programming D Address 090 Key 2 Default Regular Arming The Auto Arm feature will arm the system as described in Table 11 ENTER Installer code 0 9 0 2 ON OFF ENTER 8 2 No Movement Auto Arming Feature Select Programming D Address 086 Key 6 Default Disabled If the control panel does not detect any movement zone ope...

Page 37: ...it Delay Decimal Programming D Address 049 Default 60 seconds The exit delay applies to all zones This option determines how much time the user has to leave the protected area after entering a valid access code and before the system arms You can program the exit delay from 001 to 255 sec ENTER Installer code 0 4 9 3 digit decimal value 001 to 255 ENTER 8 8 Beep on Exit Delay Feature Select Program...

Page 38: ...des can arm System B Addresses 074 to 078 Selected keys indicate which user codes can bypass zones 8 13 Closing Delinquency Timer Decimal Programming D Address 061 Default Disabled Feature Select Programming D Address 090 Key 3 Default OFF At midnight everyday the 728 Ultra and the 738 Ultra will verify when the system was last armed If the last time the system was armed is greater than the progra...

Page 39: ...r Setting on page 35 If the PGM is triggered again before the period has elapsed the PGM will remain in its opposite state and reset the timer OR Logic Will trigger a PGM when at least one event occurs from a specific group of events e g key 1 and or key 2 is pressed on the keypad AND Logic The AND logic will trigger a PGM when all events or more occur from a specific group of events e g Keys 1 an...

Page 40: ...Mode This mode will display the 2 digit data for addresses 039 to 043 6 Record these numbers and program them into the control panel or use the Espload Software to download the data directly to the control panel If you do not have a copy of the Espload Software you can obtain a free copy from your local Paradox distributor Table 14 Commonly Used PGM Options State Option PGM1 PGM2 738 Ultra only 1s...

Page 41: ...o use the pulse dialing or tone DTMF dialing format Key 7 OFF Pulse Dialing Key 7 ON Tone DTMF Dialing ENTER Installer code 0 8 6 7 ON OFF ENTER 10 3 Dialing Pulse Rates Feature Select Programming D Address 086 Key 0 Default Pulse Europe 1 2 This selection determines the ratio between pulse time and quiet time Select Pulse Europe for a 1 2 ratio and select Pulse USA for 1 1 5 Must be set to pulse ...

Page 42: ...Programming D Address 088 Keys 0 and STAY Default Disabled If the control panel detects an open or a short on a zone when the system is armed regardless of the tamper wire settings it will always generate an alarm and trouble indicator key 9 Alarms will be audible or silent depending on individual zone definitions If an open or short occurs on a disarmed system the control panel will generate an i...

Page 43: ...y see Trouble Display Monitoring on page 43 10 11 Audible Trouble Warning Feature Select Programming D Address 090 Key 9 Default Disabled Trouble conditions will cause the keypad to emit an intermittent beep To silence the trouble warning press the TBL TRBL key 10 12 Power Down Reset Performing a power down reset will set the Installer and Master codes to factory default Values entered at addresse...

Page 44: ...xit delay the keypad will beep and the light will flash at a faster rate At the end of the exit delay the keypad will emit a confirmation beep the light will extinguish and the light will remain illuminated to indicate that the system is armed 11 2 1 One Key Regular Arming To use this feature enable the One Key Regular Arming option see page 32 When the light is on pressing and holding the 0 or AR...

Page 45: ...ill switch all entry delay zones to instant zones see Instant Zones Entry Delay 1 and Entry Delay 2 on page 29 Therefore any entry delay zone that is breached will immediately generate an alarm instead of waiting a pre determined period 11 4 3 Fast Exit This feature is only available when the system is Stay armed see Stay Arming on page 41 This feature will allow the user to exit premises while th...

Page 46: ...ut generating an alarm Do not use the 646 LED and 642 LCD keypads for UL installations Both the 646 LED keypad and the 642 LCD keypad are not UL listed 11 8 Keyswitch or Pushbutton Arming Disarming A keyswitch or push button can be used to Stay see Stay Arming on page 41 or Regular see Regular Arming on page 40 arm disarm the system If the system is ready and the button is pressed the system will ...

Page 47: ...d be replaced as it will not provide adequate back up current in case of AC loss If the control panel is currently running on battery power the illumination of the 1 key indicates that the battery voltage has dropped to 10 5 volts or lower 11 12 2 Power Failure Key 2 The control panel will detect a power loss if a continuous loss of AC less than or equal to 12 5V has occurred during the period bet...

Page 48: ... key will illuminate to indicate that the control panel has not detected the presence of a telephone line for 30 seconds 11 12 10 Fire Loop Trouble Key STAY The illumination of the STAY key indicates a wiring problem line open on zone 3 or zone 5 with 2 wire smoke and ATZ for 728 Ultra if identified as a fire zone see 24Hr and 4 Wire Smoke Detector Fire Zones and 2 Wire Smoke Detector Recognition ...

Page 49: ...terference will not occur in a particular installation If this equipment does cause harmful interference to equipment intermittently the user is encouraged to try to correct the interference by one or more of the following measures 1 re orient or relocate the receiving antenna 2 increase the separation between the equipment and receiver 3 connect the equipment to an outlet on a circuit other than ...

Page 50: ...gnal Code E Country of Origin CANADA CAN AC Ringer Equivalent Number 01B USOC Jacks RJ31X Equipment Description Control panel for residential burglar and fire warning systems Rechargeable Acid Lead or Gel Cell Backup Battery 12Vdc 4Ah 7Ah UL cUL 12Vdc 7Ah only Transformer Universal Model No UB1640W 16 5Vac 50 60Hz 20VA minimum 40VA recommended Do not connect the transformer to a switch controlled ...

Page 51: ... 33 Bypass Enabled Zones 29 Manual Zone 42 Recall 42 Tamper Options 39 C Call Back 15 Call Espload 15 Cancel Communication 15 Chime Zones Keypad 43 Closing Delinquency Timer 34 Code Priority 34 Commonly Used PGM Options Table 36 Communicator Formats Ademco Contact ID All Codes 19 Programmable Codes 20 Ademco Express 21 Pager 21 Standard Pulse Formats 21 Communicator Formats Table 19 21 Computer Te...

Page 52: ...er Options 14 Identifier 14 Settings for Espload 14 Time 38 Panic Codes 23 Keypad Options 37 Silent Option 34 Parallel Wiring ATZ 9 Partition Arming Disarming 41 Partitioning 29 PC Password 14 PGM Options 36 PGM Timer Setting 35 PGM Type Selection Table 35 PGM Types AND Logic 35 EQUAL Logic 35 OR Logic 35 Regular N O N C 35 Timed N O N C 35 PGMs Programming 35 Power 2 Power Down Reset 39 Power Fai...

Page 53: ...hone Line Monitoring TLM 37 Telephone Line Monitoring Table 37 Telephone Number Special Instructions Table 18 22 Test Battery 3 Keypad Function 3 Test Report Auto 23 Manual 24 Test Transmission Timed 24 Time Correction 38 Time Correction Table 38 Timed Auto Arming 32 Timed Test Transmission 24 Trouble Codes 23 Trouble Display Monitoring 43 Trouble Restore Codes 23 Troubles Bell Disconnected 43 Com...

Page 54: ...Notes ...

Page 55: ......

Page 56: ...o 8 00 p m EST For technical support outside Canada and the U S call 00 1 450 491 7444 Monday to Friday from 8 00 a m to 8 00 p m EST Please feel free to visit our website at www paradox ca 780 Industriel Blvd Saint Eustache Quebec J7R 5V3 CANADA Tel 450 491 7444 Fax 450 491 2313 www paradox ca PRINTED IN CANADA 03 2005 7X8ULT EI01 ...

Reviews: