12.19 Holiday Mode
Purpose:
Promotes energy saving by allowing the user to stop the system during holiday and enables the system to
resume at the preset temperature after holiday.
Control details:
o
Range of days can be set in holiday mode is from 1 to 999 days.
o
After days of holiday have been set, heat pump will stop and only resume operation at 12.00am at the
end of holiday countdown.
Start condition:
o
Unit is OFF and holiday mode is set.
* The day the holiday mode was set is counted as day 1.
Stop condition:
o
OFF/ON button is pressed.
o
Holiday counter is reached.
12.20 Dry Concrete Function
Purpose
Provide heat to floor heating panel and dry the wet concrete during installation.
Setting condition:
o
Dry concrete parameter can be set through control panel by selecting dry concrete menu.
o
Parameters are possible to set up to 99 days with different target set temperature.
Control details:
o
Dry concrete operation can be activate under Service Mode 3.
o
Once dry concrete function start, day 1 setting temperature will be send to indoor unit by control panel.
o
Unit will operate heat mode with dry concrete preset water outlet temperature. (No shift value added to
the preset water outlet temperature)
o
After complete day 1 setup operation, day 2 data will be send to indoor at 12.00am on the second day.
o
Each preset data will be send everyday until dry concrete mode is complete, unit will turns OFF and exit
dry concrete function.
o
3 ways valve and booster heater will turn OFF and 2 ways valve will turns ON.
Cancel condition:
o
Unit will turns OFF and exit dry concrete function.
o
OFF signal is received by pressing OFF/ON button or error H76 is occurred.
Содержание WH-MHF09G3E8
Страница 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Страница 33: ...33 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 34: ...34 10 2 1 1 Noise Filter Printed Circuit Board ...
Страница 47: ...47 Heat Mode Operation Time Chart ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 127: ...127 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 134: ...134 6 25 68 30 5 2 9 7 8 4 27 1 3 21 23 26 62 8 75 24 71 49 48 20 13 12 10 11 4 15 77 71 13 15 78 14 ...
Страница 138: ...138 19 2 Water System 44 46 17 16 4 34 42 18 43 3 33 9 1 45 45 47 2 35 48 36 19 ...