12.1.3 Tank Mode Operation
Control contents:
3 ways valve direction
o
3 ways valve switch to tank side during Tank Thermo ON condition. Switch 3 ways valve to room side when
tank achieve Tank Thermo OFF temperature and SOLAR turn ON condition.
Heat Pump Thermostat characteristic
o
Water set temperature = Tank set temperature or [60°C] whichever lower.
o
Heat pump Water Outlet set temperature is set to [63°C] at tank mode.
Tank Thermo ON/OFF characteristic
o
THERMO OFF TEMP:
1. THERMO OFF TEMP = Tank water set tempe [0°C].
2. Tank temperature > THERMO OFF TEMP for continuous 10 seconds after heat pump OFF, water pump
OFF or
3. Tank temperature > Tank set tempe [2°C] for continuously 20 seconds.
o
THERMO ON TEMP:
1. THERMO ON TEMP = Tank water set tempe [-8°C].
When detect tank temperature < THERMO ON TEMP, water pump ON for 3 minutes then heat pump ON.
Characteristic of heat pump thermo ON/OFF under Tank Mode condition:
Water Outlet Thermo Condition
o
Heat pump THERMO OFF TEMP:
1. Heat pump THERMO OFF TEMP = 63°C + [+4°C].
2. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump OFF.
o
Heat pump THERMO ON TEMP:
1. Heat pump THERMO ON TEMP = Water inlet during thermo OFF time + [-3°C].
2. Heat pump ON back when water outlet temperature < Heat pump THERMO ON TEMP.
Water Inlet Thermo Condition
o
Heat pump THERMO OFF TEMP:
1. Water inlet temperature > 65°C for continuous 60 seconds, heat pump OFF.
o
Heat pump THERMO ON TEMP:
1. Heat pump THERMO ON TEMP = Water inlet temperature < 65°C.
Booster heater control
o
Booster heater turns ON and OFF follow normal operation.
o
Booster heater turns ON condition:
1. During start up time (initialization), Booster heater turns ON after DELAY TIMER.
2. When tank temperature lower than HEATER ON TEMP.
3. 20 minutes from previous heater OFF.
o
Booster heater turns OFF CONDITION:
1. When tank temperature higher than tank set temperature for continuous 15 seconds.
Solar 3-way valve
o
Solar pump operates follow solar operation specification.
2 way valve closes
Other
o
Indoor backup heater cannot be ON during tank mode only.
Содержание WH-MHF09G3E8
Страница 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Страница 33: ...33 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 34: ...34 10 2 1 1 Noise Filter Printed Circuit Board ...
Страница 47: ...47 Heat Mode Operation Time Chart ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 127: ...127 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 134: ...134 6 25 68 30 5 2 9 7 8 4 27 1 3 21 23 26 62 8 75 24 71 49 48 20 13 12 10 11 4 15 77 71 13 15 78 14 ...
Страница 138: ...138 19 2 Water System 44 46 17 16 4 34 42 18 43 3 33 9 1 45 45 47 2 35 48 36 19 ...