69
12.14 Solar Operation (Optional)
12.14.1 Solar Operation:
1 External solar heat source signal can be connect to unit for proper control of heat source switching during
tank boiling time.
2 Control according to preset whether solar priority is set or not.
3 When tank connection is NOT set at SETTING mode, solar operation is disabled.
4 When Pump A (from solar pump station) is detected On through connection Y3 and Y4, then the Solar pump
3 Way Valve is requested ON (Refer to figure below).
Solar pump 3 Way
Valve
12.14.2 Solar Operation Control
When solar priority is SET
1 Operation condition:
a 3 way valve operates if all of the following conditions are fulfilled:
Power On. (regardless operation ON or OFF)
There is operation request from solar pump station.
Tank hot water temp is below solar on upper limit temp 72°C.
2 Stop condition:
a 3 way valve stops operating when:
No power supply to unit
OR
There is
NO
operation request from solar pump station
OR
Tank hot water temp is above solar off upper limit temp 80°C.
* heat pump OFF OR operate to room side when solar pump operate during solar priority set.
* booster heater OFF when solar pump operate during solar priority set.
When solar priority is NOT SET
1 Operation condition:
a 3 way valve operates if all of the following conditions are fulfilled:
Power On. (regardless operation ON or OFF)
There is operation request from solar pump station.
Tank hot water temp is below solar on upper limit temp 72°C.
Heat pump thermo OFF in tank mode OR Heat pump operate to room side
(during operation ON and tank mode selected).
2 Stop condition:
a 3 way valve stops operating when:
No power supply to unit
OR
There is
NO
operation request from solar pump station
OR
Tank hot water temp is above solar off upper limit temp 80°C.
Heat pump thermo ON and operate to tank side. (during operation ON and tank mode selected)
Содержание WH-MHF09G3E8
Страница 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Страница 33: ...33 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 34: ...34 10 2 1 1 Noise Filter Printed Circuit Board ...
Страница 47: ...47 Heat Mode Operation Time Chart ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 127: ...127 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 134: ...134 6 25 68 30 5 2 9 7 8 4 27 1 3 21 23 26 62 8 75 24 71 49 48 20 13 12 10 11 4 15 77 71 13 15 78 14 ...
Страница 138: ...138 19 2 Water System 44 46 17 16 4 34 42 18 43 3 33 9 1 45 45 47 2 35 48 36 19 ...