12.1.4 Heat + Tank Mode Operation
Setting 1: When Heating priority is set by control panel:
1. 3 ways valve control:
o
3 ways valve switch to room side during External Room Thermo ON
OR
Solar 3 ways valve ON
OR
Tank
Thermo OFF time, and switch to tank side at External Room Thermo OFF
AND
Solar 3 ways valve OFF.
2. Heat pump operation control:-
o
During External Room Thermo ON time
: (When room thermo ON, heat pump must operate to room side)
Heat pump operates follow normal operation at room side.
o
During External Room Thermo ON time
:
Switch 3 ways valve to tank side, IF
Under Solar Priority Set condition:
o
Tank temperature < Tank THERMO ON TEMP
AND
Solar Valve OFF
Under Solar Priority Not Set condition:
o
Tan temperature < Tank THERMO ON TEMP
Switch back 3 ways valve to room side, Heat pump and water pump turn OFF, IF
o
External Room Thermo ON back
OR
Under Solar Priority Set condition:
Tank temperature > Tank THERMO OFF TEMP for continuous 10 seconds
OR
Solar Valve ON.
Under Solar Priority Not Set condition:
Tank temperature > Tank THERMO OFF TEMP for continuous 10 seconds.
* Judge only after heat pump THERMO OFF
* THERMO ON and THERMO OFF point refer to case below.
Operation condition when 3 ways valve switch to tank side:
Tank water set temperature = tank set temperature or [60°C] whichever lower.
Heat Pump Water Outlet set temperature is set to [63°C] during tank interval.
Initial Tank THERMO ON TEMP = heat pump tank target tempe [-8°C].
Tank Thermo ON/OFF Characteristic
o
THERMO OFF TEMP:
1. THERMO OFF TEMP = Heat pump tank target tempe [0°C].
2. Tank temperature > THERMO OFF TEMP for continuous 10 seconds after heat pump OFF due to water
thermo, switch 3 ways valve to room side
OR
3. Tank temperature > Tank set tempe 2°C for continuous 10 seconds, switch 3 ways valve to room
side.
o
Next THERMO ON TEMP:
1. THERMO ON TEMP = Heat pump tank target tempe [2°C] or
2. If tank temperature < THERMO ON TEMP
AND
External Room Thermo OFF, switch to tank side.
Содержание WH-MHF09G3E8
Страница 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Страница 33: ...33 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 34: ...34 10 2 1 1 Noise Filter Printed Circuit Board ...
Страница 47: ...47 Heat Mode Operation Time Chart ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 127: ...127 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 134: ...134 6 25 68 30 5 2 9 7 8 4 27 1 3 21 23 26 62 8 75 24 71 49 48 20 13 12 10 11 4 15 77 71 13 15 78 14 ...
Страница 138: ...138 19 2 Water System 44 46 17 16 4 34 42 18 43 3 33 9 1 45 45 47 2 35 48 36 19 ...