52
Characteristic of heat pump thermo ON/OFF under tank side condition
Water Outlet Thermo condition
o
Heat pump THERMO OFF TEMP:
1. Heat pump THERMO OFF TEMP = 63°C + [+4°C].
2. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 90 seconds, heat pump OFF
and water pump continue ON.
o
Next THERMO ON TEMP:
1. THERMO ON TEMP = Water inlet when heat pump THERMO OFF + [-3°C].
2. If water outlet temperature < THERMO ON TEMP
AND
External Room Thermo OFF, heat pump ON.
Water Inlet Thermo condition
o
Heat pump THERMO OFF TEMP
1. Water inlet temperature > [65°C] for continuous 30 seconds, heat pump OFF, water pump continue ON.
o
Next THERMO ON TEMP:
1. THERMO ON TEMP = Water inlet temperature <65°C.
2. If water inlet temperature < THERMO ON TEMP
AND
External Room Thermo OFF, heat pump ON.
Solar Operation Condition (Only during solar priority is set condition)
o
When solar request ON, solar valve will ON, turn OFF heat pump and water pump and switch 3 ways valve to
room side.
o
THERMO ON TEMP:
1. THERMO ON TEMP = Heat pump tank target tempe [-8°C].
2. If tank temperature < THERMO ON TEMP
AND
External Room Thermo OFF
AND
Solar 3WV OFF, switch
to tank side. Turn ON heat pump after water pump turns ON for 3 minutes.
3. Backup heater control:-
o
During External Room Thermo ON time, follow normal backup heater control operation.
o
During External Room Thermo OFF time, Backup heater OFF.
4. Booster heater control:-
o
Booster heater ON/OFF follow normal operation.
* Under solar priority is set condition, when solar 3 way valve is ON, booster heater turn OFF.
5. Solar 3 way valve:
o
Solar 3 way valve operates follow solar operation specification.
* Under solar priority is set condition, when solar 3WV turns ON, booster heater will turns OFF and 3 ways
valve switch to room side.
* Under solar priority is not set condition, solar 3WV will OFF when heat pump operate to tank side.
o
2 way valve open.
Содержание WH-MHF09G3E8
Страница 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Страница 33: ...33 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 34: ...34 10 2 1 1 Noise Filter Printed Circuit Board ...
Страница 47: ...47 Heat Mode Operation Time Chart ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 127: ...127 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 134: ...134 6 25 68 30 5 2 9 7 8 4 27 1 3 21 23 26 62 8 75 24 71 49 48 20 13 12 10 11 4 15 77 71 13 15 78 14 ...
Страница 138: ...138 19 2 Water System 44 46 17 16 4 34 42 18 43 3 33 9 1 45 45 47 2 35 48 36 19 ...