79
14. Servicing Mode
14.1 Remove The Cabinet Front Plate
1. Remove the 5 mounting screws as shown in the illustration.
2. Slide the cabinet front plate downward to release the pawls.
Then, pull it toward front to remove it.
Cabinet Front Plate
Mounting screws
Mounting
screws
14.2 Test Run
1. Fill up the Tank Unit with water. For details refer to Tank Unit installation instruction and operation instruction.
2. Antifreeze agent must be added into water circuit to prevent freezing of water when outdoor ambient
temperatures is low. Recommended antifreeze: Propylene glycol: 40% (equivalent to -20°C)
3. Set ON to the Mono bloc unit and RCCB. Then, for remote control operation please refers to (Mono bloc) Air-
to-Water Heatpump’s operation instruction.
4. For normal operation, pressure gauge reading should be in between 0.05 MPa and 0.3 MPa. If necessary,
adjust the water pump speed accordingly to obtain normal water pressure operating range. If adjust water
pump speed cannot solve the problem, contact your local authorized dealer.
5. After test run, please clean the external filter. Reinstall it after finish cleaning.
14.3 Proper Pump Down Procedure
Strictly follow the steps below for proper pump down procedure. Explosion may occur if the steps are not
followed as per sequence.
1. Press the “SERVICE” switch on remote control to enter SERVICE mode. Operate the system in Sr : 01 mode
for pump down operation.
2. After 10~15 minutes, (after 1 or 2 minutes in case very low ambient temperatures (< 10°C)), fully close 2 way
valve.
3. After 3 minutes, fully close 3 way valve.
4. Press the “OFF/ON” switch on remote control to stop pump down operation.
5. Remove the refrigerant piping.
Содержание WH-MHF09G3E8
Страница 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Страница 33: ...33 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 34: ...34 10 2 1 1 Noise Filter Printed Circuit Board ...
Страница 47: ...47 Heat Mode Operation Time Chart ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 127: ...127 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 134: ...134 6 25 68 30 5 2 9 7 8 4 27 1 3 21 23 26 62 8 75 24 71 49 48 20 13 12 10 11 4 15 77 71 13 15 78 14 ...
Страница 138: ...138 19 2 Water System 44 46 17 16 4 34 42 18 43 3 33 9 1 45 45 47 2 35 48 36 19 ...