6 - 25
5. Test Pin
Mini VRF SYSTEM
Trouble Diagnosis
6
6. Inspection and Characteristics of Parts
2WAY SYSTEM
Trouble Diagnosis
Compressor
Type
5VD420XEB21
unit : ohm
0.659
0.670
0.650
Resistance
(at 20°C)
(6) Coil Resistance of Compressor Motor
U-4LE2E5, U-5LE2E5, U-6LE2E5
(7) Characteristics of Sensor
Resistor (kΩ
)
Resistor (kΩ
)
●
Outdoor air temp. sensor (TO)
●
Compressor intake temp.
sensor (SCT)
Temperature(
°C
)
Temperature(
°C
)
●
Outdoor coil liquid temp.
sensor (EXL)
●
Outdoor coil gas temp.
sensor (EXG)
●
Temp. sensor at refrigerant
gas outlet of dual-tube (SCG)
40
35
30
25
20
15
10
5
0
-10
-15
-20
20
20
30
40
50
60
15
10
5
0
-5
8
7
6
5
4
3
2
1
0
Resistor (kΩ
)
Temperature(
°C
)
●
Compressor discharge gas temp. sensor (DISCH)
0
90
80
70
60
50
40
30
20
10
0
40
60
80
100
120
140
160
180
200
20
U - V
U - W
V - W
Compressor
Type
5VD420XFA21
unit : ohm
2.510
2.561
2.475
Resistance
(at 20°C)
U-4LE2E8, U-5LE2E8, U-6LE2E8
U - V
U - W
V - W
7. Test Pin
2WAY SYSTEM
Trouble Diagnosis
When the test pin on the outdoor unit control PCB is short-circuited, each part can be operated individually.
•
After turning OFF the main unit power, short-circuit the test pin (black), then turn the power back ON.
Output is performed in the sequence shown in the table below, for 0.5 seconds each.
Operation
Operation
Output
U-4LE2E5, U-5LE2E5, U-6LE2E5
Relay RY508 Oil recovery valve (ORVR)
Relay RY506 Crankcase heater (CH)
Output
Relay RY504
3
4
1
2 Relay RY505 4-way valve (20s)
O
2
(OPTION)
Operation
Operation
Output
U-4LE2E8, U-5LE2E8, U-6LE2E8
Relay RY5
Oil recovery valve (ORVR)
Relay RY3
Crankcase heater (CH)
Output
Relay RY1
3
4
1
2
Relay RY2
4-way valve (20s)
O
2
(OPTION)
SM830258-01_欧州向け_1fan_mini_VRF.indb 25
18/03/13 17:29:26