Mini VRF SYSTEM
Test Run
7 - 6
7
3. Main Outdoor Unit P.C.Board Setting
Setting the System Address
[SW2: Rotary switch (Yellow), SW1: 2P DIP (Black)]
Outdoor
system
address
SW2
setting
SW1 setting
1P
(10s digit)
2P
(20s digit)
Link wiring
1
1
OFF
OFF
2
2
OFF
OFF
3
3
OFF
OFF
4
4
OFF
OFF
5
5
OFF
OFF
6
6
OFF
OFF
7
7
OFF
OFF
8
8
OFF
OFF
9
9
OFF
OFF
10
0
ON
OFF
11
1
ON
OFF
12
2
ON
OFF
13
3
ON
OFF
14
4
ON
OFF
15
5
ON
OFF
16
6
ON
OFF
17
7
ON
OFF
18
8
ON
OFF
19
9
ON
OFF
Outdoor
system
address
SW2
setting
SW1 setting
1P
(10s digit)
2P
(20s digit)
Link wiring
20
0
OFF
ON
21
1
OFF
ON
22
2
OFF
ON
23
3
OFF
ON
24
4
OFF
ON
25
5
OFF
ON
26
6
OFF
ON
27
7
OFF
ON
28
8
OFF
ON
29
9
OFF
ON
30
0
ON
ON
Number of indoor units
System address No.
System address (SW1)
(2P DIP switch)
10 20
System address (SW2)
(Rotary switch)
Indoor unit setting (SW3)
(1P DIP switch)
10
Indoor unit setting (SW4)
(Rotary switch)
1
ON
10 - 12 unit
1 - 9 unit
(factory setting : 1 unit)
1
ON
Set to 0 - 2
Set to 1 - 9
OFF
ON
Both OFF
Both ON
1 ON
2 ON
Set to 1
Set to 1
Set to 1
Set to 0
The number of indoor units settings (SW3, SW4)
Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used) (SW1, SW2)
DO NOT exceed the maximum number of indoor units when making connections.
The indoor unit address setting should also be set less than “12”.
In the event of setting more than “13”, the communication cannot be made between the outdoor and indoor units.
2
SW 2
LED 1
LED 2
CN-RC
AP
MODE
CN-TERMINAL
SW 1
SW 4
SW 3
A. ADD
DEF
CHK
STOP
RUN
CN-SILENT
CN-ROM
CN-OC
CN-EMG
LED 2
LED 1
SW 2
SW 1
SW 4
SW 3
DEF
A. ADD
CHK
AP
STOP
RUN
MODE
CN-SILENT
CN-ROM
CN-OC
CN-EMG
CN-RC
CN-TERMINAL
U
U-4LE2
E
5, U-5LE2
E
5, U-6LE2
E
5
U-4LE2
E
8, U-5LE2
E
8, U-6LE2
E
8
00_300268_2WAY_Eng.indb 48
2017/12/14 13:04:45
SM830258-01_欧州向け_1fan_mini_VRF.indb 6
18/02/14 8:59:47
Содержание S-22ML1E5
Страница 54: ... MEMO 1 44 ...
Страница 175: ...201803 ...