Mini VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
4 - 12
4
2WAY SYSTEM
Outdoor Unit Maintenance Remote Controller
6. Mode Settings
Setting mode 1
<Operating procedure>
Press and hold the
1
2
(Check) button and
(Ventilation) button simultaneously for 4
seconds or longer.
Press the temperature setting
and
buttons to change the item code. The item codes
and setting data are shown in the table below.
Press the timer time
buttons to
change the setting data.
To confirm the changed setting data, press the
button.
(At this time, “ ” display stops blinking
and remains lit.)
During this mode, “ ” is displayed,
blinking. The outdoor unit address display section
displays “ALL,” the item code and number (DN
value in the table), and the setting data (6 digits).
(The setting data is displayed in 6 digits. The
display changes between the first 3 digits (Fig. A )
and the last 3 digits (Fig. B
B
B
A
A
).
When the first 3 digits are displayed, the bottom dot
of the colon is illuminated.)
To exit the setting mode, press the
(Check)
button.
Regarding the parameter setting, see the item "11. Detailed Settings in EEPROM of Outdoor Unit" under
the Section 1.
2
5
1
and
are displayed alternately.
(Example shows display of 000 001.)
Display of fi rst 3 digits
Display of last 3 digits
3
4
5
and
3
2
5
1
3
A
A
6. Mode Settings
SM830258-01_欧州向け_1fan_mini_VRF.indb 12
18/02/09 11:17:44