Mini VRF SYSTEM
Control Functions - Outdoor unit
1 - 2
1
1. Introduction
Mini VRF SYSTEM is a multi system that is connected to a single outdoor unit. The outdoor unit contains an inverter
compressor.
To operate this system, the below settings must be made at the time of the test run.
Table 1-1
Setting item
At shipment
from factory
Settable range
System address
1
System 1 – 30
No. of indoor units
1
1 – 12 units
Table 1-2
4 HP
5 HP
6 HP
Maximum number of connected indoor units
7
(10)
8 (12)
9 (12)
The numbers in parenthesis are available with the capacity of 1.5 kW indoor unit connection.
Be sure to connect indoor units so that the resulting indoor-outdoor capacity ratio (total capacity of all indoor units
compared with the outdoor unit capacity) is within the range of 50% – 130%.