6 - 19
Mini VRF SYSTEM
Trouble Diagnosis
6
3. Mini VRF Alarm Codes
3WAY SYSTEM
Trouble Diagnosis
4. 3WAY Alarm Codes
P04 Alarm
Alarm code
Alarm meaning
High pressure swich is activated.
(1) High-pressure switch failure or wiring connection failure
(2) Failure to open the service valve of the outdoor unit
(3) Difference of characteristics of high-pressure sensor
(4) Clogging of the outdoor heat exchanger during cooling
(5) Air short circuit occurs during cooling.
(6) Failure of the outdoor fan during cooling
(7) Clogging of the air filter in the indoor unit during heating
(8) Air short circuit occurs during heating.
(9) Failure of the indoor fan during heating
(10) Clogging of the refrigerant circuit
(11) Failure of the expansion valve
(12) Too much refrigerant has been charged.
(1) High-pressure switch failure or wiring connection failure
Check under the section 6. "Inspection and Characteristics of Parts (1) High-pressure switch".
(2) Failure to open the service valve of the outdoor unit.
Check open/closed status of the outdoor unit service valve.
(3) Difference of characteristics of high-pressure sensor
(4) During cooling, check whether the outdoor unit heat exchanger is clogged. Remove any foreign material that
prevents ventilation.
(5) During cooling, check whether an air short blockage has occurred in the outdoor unit. The system is
operating normally unless the temperature around the outdoor unit is excessively high.
(6) During cooling, check for outdoor fan failure. Check whether the screws securing the fan are loose and
whether the fan connector in the outdoor unit PCB is properly connected.
(7) During heating, check whether the air filters in the indoor unit are clogged. If clogged, clean the filters.
(8) During heating, check whether an air short blockage has occurred in the indoor unit. The system operates
normally unless the temperature around the indoor unit is excessively high.
(9) During heating, check for indoor fan failure.
(10) Check whether the refrigerant circuit is clogged. Check that all service valves are closed.
Check whether welded locations are clogged.
(11) Check for expansion valve failure. Check whether the expansion valves make a clattering sound when the
power is reset. Since the expansion valve in the indoor unit is in a location that makes aural inspection
difficult, use an electric means to check. Check that the connector pin of the expansion valve on the PCB
outputs 4 V. In addition, check that the coil resistance of the expansion valve is several tens of Ohm ( Ω ).
(12) Check for solenoid valve kit failure. Removing a coil that is on will result in a clicking sound.
Also, removing a coil that is off will not produce such a sound.
(13) Check whether too much refrigerant has been charged. Too much refrigerant has been charged if the
sub-cool temperature of the condenser is 15°C or more.
(14) Check whether the wiring from the solenoid valve kit is actually connected to the different indoor unit.
(15)
Replace damaged components and correct the amount of charged refrigerant.
The system is that the multiple indoor units are connected at only one solenoid valve kit and also multiple
remote controllers are connected. Check whether "installation of the common use solenoid valve kit" from a
PC has been made. (Confirmation from the address setting software of a PC)
Connect a gauge to the high-pressure outlet and check for changes in the value displayed by the monitoring
software, and for large deviation of the gauge pressure.
Check whether the socket of the high-pressure switch is surely inserted into the Outdoor Unit Control PCB.
The operation of the electronic circuit in the high-pressure switch may short-circuit the terminal depending on the
pressure. A pressure of 3.8 MPa or above will short-circuit the terminal. Once the terminal is short-circuited, it will
remain in that state until the pressure goes below 3.15 MPa.
Alarm conditions
Probable cause
Check
Correction
P04
P05 Alarm
Alarm code
P05
Alarm meaning
AC power supply has abnormal.
Alarm conditions
AC power supply trouble.
Probable cause
(1) Instantaneous blackout
(2) Zero-cross (waveform input of power supply) error
(3) DC voltage charge failure
Check
(1) Check the power supply and power wiring.
(2) Check the wiring.
Check whether each wiring is missing or connector is damaged.
Correction
(1) Correct the power supply and power wiring.
(2) Correct the wiring failure.
(3) Replace the Outdoor Unit Control PCB or the HIC PCB.
Example
—
Notes
—
P14 Alarm
Alarm code
P14
Alarm meaning
O
2
sensor has activated.
Alarm conditions
(1) It is judged an error whenever the outdoor unit receives the signal “O
2
Alarm Generated” from
the indoor unit.
(*) It is judged an error whenever the outdoor unit's EEPROM setting (item code C1) is made at other
than "0". See Section 1.
(2) With the indoor unit's EEPROM setting (item code 0B) set to 0001, the EXCT input was shorted.
Probable cause
—
Check and
Correction
(1) System configuration
1-1 Is an O
2
sensor being used?
If “Yes”, see “3-1”.
If “No”, see “2-1”.
(2) Indoor EEPROM setting
2-1 Is the EEPROM setting, item code 0B, on the indoor control board set to 0001?
If “Yes”, change the setting of item code 0B to “0000”
from “0001”.
If “No”, see “3-1”.
(3) Indoor control board
3-1 Is the alarm triggered if the EXCT socket (wire) is disconnected, and the power is reset?
If “Yes”, see “3-3”.
If “No”, see “3-2”.
3-2 Since there is no error, see what happens.
3-3 Indoor control board defective
→
replace board
Example
—
Notes
—