1 - 27
Mini VRF SYSTEM
Control Functions - Outdoor unit
1
9. Demand Control
2WAY VRF SYSTEM
Control Functions
(1)
The standard value of the limit current is shown in the table below.
U-4LE2E5, U-5LE2E5, U-6LE2E5
Demand control is performed to suppress the horsepower not to make the primary current exceed the setting
value.
10. Demand Control
Usual Demand Control
Type of outdoor unit
6HP
unit:Amp.
HP=Horsepower
unit:Amp.
20.3
19.1
5HP
17.0
18.1
4HP
13.3
12.2
Cooling mode
Heating mode
The system current value is controlled up to limit value or less without demand input as shown in the table below.
Limit value
Type of outdoor unit
6HP
Limited ratio against standard value
145%
27.44
Cooling mode
25.70
5HP
145%
22.65
24.25
4HP
145%
17.29
15.69
Heating mode
The standard value of the limit current is shown in the table below.
U-4LE2E8, U-5LE2E8, U-6LE2E8
Type of outdoor unit
6HP
unit:Amp.
HP=Horsepower
HP=Horsepower
HP=Horsepower
unit:Amp.
6.71
6.24
5HP
5.58
5.62
4HP
4.39
3.98
Cooling mode
Heating mode
The system current value is controlled up to limit value or less without demand input as shown in the table below.
Limit value
Type of outdoor unit
6HP
Limited ratio against standard value
160%
10.74
Cooling mode
9.98
5HP
180%
10.04
10.12
4HP
180%
7.90
7.16
Heating mode
2WAY VRF SYSTEM
Control Functions
10. Demand Control
(2)
When the Energy Saving button of the indoor unit remote controller is pressed, demand control is performed
according to EEPROM : 1A values.
The marking “
” indicated in the following table is applicable to the function of control.
Setting of Energy Saving button: Outdoor unit EEPROM Setting item DN18, DN19
Energy saving operation when the Energy Saving button is pressed provides 3 patterns of control.
Patterns:
Energy Saving Button (CZ-RTC5A / CZ-RTC5B)
Setting No.
0
1
Discharge air
temperature
control
Demand
control
Remarks
No controls
Pattern “C”: only discharge air temperature control
2
Pattern “B”: only demand control
3
(Factory preset mode)
Pattern “A”: demand control and discharge air
temperature control
Demand control is performed under the current limitation values set at the outdoor unit EEPROM setting
(DN1A).
In addition, the indoor unit controls the limitation of discharge air temperature.
Demand control is performed under the current limitation values set at the outdoor unit EEPROM setting
(DN1A).
Discharge air temperature limitation control is performed set at the indoor unit EEPROM setting.
Outdoor unit EEPROM setting (DN18) :
A.
B.
C.
Outdoor unit EEPROM setting (DN19):
Setting of control validity range when pressing the Energy Saving button
* When the pattern “A” and “B” are selected, energy saving control becomes valid in the same range as
the setting “1” although the Setting No. is set to “0”.
Setting No.
0
(Factory preset mode)
1
Control range
Energy saving activates where Energy Saving button is pressed as a unit of indoor
unit (group).
Energy saving activates where Energy Saving button is pressed as a unit of indoor
unit including all refrigerant system.
SM830258-01_欧州向け_1fan_mini_VRF.indb 27
18/03/06 9:09:52