Mini VRF SYSTEM
Remote Controller Functions
5 - 26
3. Remote Controller Servicing Functions
5
<Procedure of CZ-RTC4>
1 Press and hold the
and
buttons
simultaneously for 4 seconds or longer.
2 The unit No. “X-X” (main unit No.), item code “
”
(sensor address), and servicing monitor “
”
(sensor temperature) are displayed on the remote
controller LCD display.
3 Press the temperature setting
/
and select the item code to the address of the
buttons
sensor to monitor.
4 If group control is in effect, press the
to select the unit to monitor.
button
Press the temperature setting buttons to select the
item code to change.
5 Press the
button to return to normal remote
controller display.
NOTE
The temperature display appears as “- - - -” for unit that are not connected.
* If monitor mode is engaged while normal operation is in progress, only the parts of the LCD display shown in the
figure will change. Other parts continue to display the same information as during normal operation.
* Display shows a discharge temperature of
00XX at unit No. 1-1.
A
°
°
3
3
4
1
2
4
5
4
Indoor unit sensors
00
Room temp. controlled*
01
Remote controller temp.
02
Indoor unit intake temp. (TA)
03
Indoor unit heat exchanger
temp. E1 (E1)
04
—
05
Indoor unit heat exchanger
temp. E3 (E3)
06
Discharge air temp. (BL)
07
Discharge air temp. setting
08
Indoor unit MOV pulse (MOV)
Outdoor unit sensors
Unit No.1
0A
Discharge temp. (DISCH)
0C
High-pressure sensor temp.
0D
Heat exchanger gas (EXG)
0E
Heat exchanger liquid (EXL)
11
Outdoor air temp. (TO)
12
Inverter secondary current
13
Inverter primary current (L2 phase) (Three phase only)
15
MOV pulse 1 (MOV1)
19
Inverter actual operating frequency
1A
Sub cooler (MOV4)
1B
Inverter primary current (L1 phase)
1D
Low-pressure sensor temp.
1E
Suction temp. (SCT)
21
Inverter primary current (L3 phase) (Three phase only)
24
Temp. sensor at refrigerant gas outlet of dual-tube temp. (SCG)
26
High-pressure
27
Low-pressure
*Room temp. controlled: = Controlled room temperature
•When body thermostat controlled:
Controlled room temperature = Indoor unit intake temp. (TA) – Intake temperature shift (*1)
•Remote control thermostat controlled:
Controlled room temperature = Remote controller temp.
*1 Intake temperature shift: This is the shift value considered the temperature difference between the upper area
and lower area of the room in heating mode.
It is the value of the code “06” in the indoor unit’s EEPROM setting.
Cooling mode: = 0
3. Remote Controller Servicing Functions
VRF SYSTEMS Indoor Unit
4
,
and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
5
Press the
6
or
/
button to see each menu.
Select "13. nanoe" on the LCD display and press the
button.
The nanoe™ X module status of all indoor units will be
displayed.
Normal : The nanoe™ X module is operating normally.
Unsupported : The indoor unit is not available to the
nanoe™ X function.
*1-1 and 1-2 represent the unit number.
*In the case of "Unsupported", select "8. Detailed
settings" and check the setting data of the Code no. 9.
*If the setting data is "0000", the nanoe™ X module is
not recognized. Check the status of the connection.
If the display other than "Normal" or "Unsupported"
appears, check the Step
⑦
next page.
Check that the nanoe™ X module status is "Normal".
The indoor unit on the display can be scrolled up or
down using buttons.
While operating in FAN mode (more than 5 minutes
have elapsed), press the
1
Switch On the earth leakage circuit breaker.
2
Wait until the remote control display returns to
normal.
3
Operate the unit in FAN mode.
<Procedure of CZ-RTC5A
/ CZ-RTC5B
>
■
nanoe™ X Display
When the
appears on the remote controller (CZ-RTC5A
/ CZ-RTC5B
), the status of the nanoe™ X
can be checked i
n the following way.
SM830232-03_欧州向けVRF Indoor SM&TRSM.indb 56
17/06/27 20:22:09
SM830258-01_欧州向け_1fan_mini_VRF.indb 26
18/02/09 18:58:56