Mini VRF SYSTEM
Remote Controller Functions
5 - 4
1. Simple Settings Function
5
List of Simple Setting Items
Item code
Item
Setting data
No.
Description
Filter sign ON time
(filter life time)
0000 Not displayed
0001 150 hours
0002 2,500 hours
0003 5,000 hours
0004 10,000 hours
0005 Use the filter clogging sensor.
Degree of filter fouling
0000 Standard (setting at time of shipping)
0001
Highly fouled
(Filter sign ON time is reduced to one-half the set time.)
Central control
address
0001 Central control address 1
0002 Central control address 2
0003 Central control address 3
0064 Central control address 64
0099 No central control address set (setting at time of shipping)
Operating mode
priority change
0000 Normal (setting at time of shipping)
0001 Priority
Fan speed when
heating thermostat is
OFF
Compressor ON
Compressor OFF
0000
L 1 min., LL 3 min.
LL
0001
L
LL
0002
LL
LL
0004
L 1 min., LL 3 min.
L
0005
L
L
0006
LL
L
Heating intake
temperature shift
0000 No shift
0001 Shifts intake temperature 1°C down.
0002 Shifts intake temperature 2°C down.
0003 Shifts intake temperature 3°C down.
0004 Shifts intake temperature 4°C down.
0005 Shifts intake temperature 5°C down.
0006 Shifts intake temperature 6°C down.
Electric heater
installation
0000 No heater
0001 Heater installed
Humidifying when
heater thermostat is
OFF
0000 No (setting at time of shipping)
0001 Yes
Change to remote
controller sensor
thermostat differential
0000 Thermostat OFF differential: − 1°C (setting at time of shipping)
0001 Thermostat OFF differential: − 0.5°C
(0B)
Function of EXCT
plug short-circuit
0000 Indoor unit does thermostat OFF (factory preset mode)
0001 Indoor unit gives “P14” alarm and transmits the refrigerant leakage signal.
(0D)
Permit/prohibit
automatic
heating/cooling
0000 Permit
0001 Prohibit
Cool-only
0000 Normal
0001 Cool only (Set “1” for item code OD.)
NOTE
•
In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF unless a
vaporizing humidifier is used.
•
Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
•
Do not change any setting data that does not appear in this list.