Electrical Wiring
6
6.5 Solenoid Valve Kit – For 3-Way ECO-i System
6.5.1 Wiring
● Connect the 9P connector coming from the solenoid valve kit through the power
inlet of the PAW-VP-RTC5B-VRF to the 9P connector (red) of the Solenoid Valve
Control PCB (sold separately) (Fig. 6-1).
● Accessory wire length is 5 m.
● In case the wire is not long enough, cut the wire halfway and connect additional
wire (field supply) as an extension using a terminal box (field supply).
● Additional wire must be "H05VVF 0.5 mm2" or "60227 IEC53".
● Anchor the cabtyre cable using the binding bands inside the unit.
● Do not route the cabtyre cable through the same wiring conduit as the remote con
-
troller wiring or inter-unit control wiring.
● If the supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard
.
Fig. 6-1
Connection
Solenoid Valve Control PCB
Protective ground screw
Solenoid Valve