DHW PAW-VP - Installation manual - 2020-05
Electrical Wiring
6
6.2 Recommended Wire Diameter
Power supply wiring
(B) Power supply cable control box
Model name
Power supply
Minimum power
supply cables L1/N/PE
Circuit breaker
(minimum capacity)
CZ-RTC5B
Single phase 220/230/240 V
0.75 mm
2
2 A
Power supply cable backup heater
Model name
Power supply
Minimum power
supply cables L1/N/PE
Circuit breaker
(minimum capacity)
PAW-VP750LDHW
3-phases 380/400/420 V
2.5 mm
2
16 A
PAW-VP1000LDHW
3-phases 380/400/420 V
2.5 mm
2
16 A
PAW-VP380L
3-phases 380/400/420 V
2.5 mm
2
16 A
Control wiring
(B) Inter-unit (between outdoor and indoor units) control wiring
Control wiring U1 U2
Length (m)
0.75 mm
2
(AWG #18)
Use shielded wiring*
2
Max. 100