DHW PAW-VP - Installation manual – 2020-05
Tubing Data and Refrigerant
4
4.2 Tubing data for cooling and heating tank
4.2.1 PAW-VP380L
Indoor Unit
Outdoor Unit
PAW-VP380L
U-200PE2E8A
Tubing data
Tubing size outer diameter
Refrigerant connection pipe
Liquid tube
[mm (inch.)]
Ø 9.52 (3/8)
Gas tube
[mm (inch.)]
Ø 22.22 (7/8)
Indoor unit pipe junction
Liquid tube
[mm (inch.)]
Ø brazing 12.7 (1/2)
Gas tube
[mm (inch.)]
Ø brazing 19.05 (3/4)
Outdoor unit pipe junction
Liquid tube
[mm (inch.)]
Ø flared connection 12.7 (1/2)
Gas tube
[mm (inch.)]
Ø flared connection 19.05 (3/4)
Wall thickness of the insulation
Liquid tube
[mm]
>10
Gas tube
[mm]
>19
Limit of tubing length (L)
[m]
30
Height differential of Indoor/
Outdoor units (H1)
Outdoor unit is placed higher [m]
30
Outdoor unit is placed lower [m]
30
Systems must be pre-charged with refrigerant
[kg]
1
Required additional refrigerant over 7,5 meters
[g/m]
45
Refrigerant charged at shipment R410A
[kg]
4.2